Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Fire Safety work of District Hospital (Male) Akbarpur Kanpur Dehat District-Kanpur Dehat (U.P.) |
| 2 | Fire Alarm System (Main Building)Supply, Installation, Testing & Commissioning of Fault isolater complete with base as required. (Make: Morley/Farenhyt/GST). |
| 3 | Supply, Installation, Testing & Commissioning of intelligent addressable programmable sounder complete as required. |
| 4 | SITC of Manual call point break glass type housed in MS sheet, including connection Make-Agni/ Daksh. |
| 5 | Supplying installaion testing and commissioning of micro processor based intelligent addressable main fire alarm panel central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (2305 %V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless tegration with analogidigital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for BMS system with open protocol BACnet/ Modbus over IP complete as per specifications 10 LOOP PANEL. |
| 6 | Supplying, installation, testing & commissioning of intelligent analog addressable photo thermal detector complete with mounting base complete as required. |
| 7 | Supply , Installation , Testing and Commissioning of response indicator on surface / recess M S box having two LED metallic cover complete with all connections etc. as required. |
| 8 | Supply and laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed cooper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. grade Powder Cable. The cable shall with laid in tray / in trenches/on wall/ floor etc. As required |
| 9 | Supplying and fixing suitable size G I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Wiring for light / power plug with 2 x 4.00 sq. mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, along with 1 No. 4.00 sq. mm FRLS PVC insulated copper conductor single core for loop earthing as required. |
| 11 | Supply and fixing of fire extinguisher, ABC Type 6.0 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 12 | Supply and fixing of CO2 type Fire extinguisher, 4.50 Kg. capacity (ISI marked IS: 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 13 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. |
| 14 | Fire Hydrant System (Main Building)Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1010 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.(A) Upto 35.00 sq. mm |
| 15 | (B) Above 35.00 sq. mm & Upto 95 sq.mm |
| 16 | Supply and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.10 KV grade as required.(A) 16 sq. mm x 4 (28 mm) |
| 17 | (B) 95 sq. mm x 3½ (28 mm) |
| 18 | SITC of Main Pump Electrical oprated TEFC type induction motor of 65 HP including suitable pump 70 Mtr. head with 2850 LPM complete installation with concrete foundation & suitable base plate of iron channel complete work as requirement. |
| 19 | SITC of Disel Engine driven Pump 2850 LPM 70 mtr. 2300 RPM 69 HP Horizontal Fire Pump with water cooled Diesel Engine with flaxible coupling commen installation on concrete foundation & suitable base plate etc. for mounting the Diesel Engine and Punp complete in all respect. |
| 20 | Supply, Installation testing and commissioning of Electric driven Pressurisation Pump (Jockey Pump) suitable for automatic operation and consisting of following, complete in all respects, as required : (a) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal confirming to IS 1520 . (b) Suitable HP Squirrel cage induction motor, TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class - 'F' insulation, confirming to IS - 325. (c) M S fabrication, common base plate, coupling, cuopling guard , foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads.Fire Jocky Pump, Capacity - 180 LPM at 70.00 Meter Head . Make : Kirloskar. |
| 21 | SITC of Electrical Driven Terrace pump, TEFC type induction motor of 15 HP suitable for 450 LPM complete installation with concrete foundation & suitable base plate by iron channel complete work as requirement. Make Kiloskar/ other standard make. |
| 22 | Incoming - 1 No. 800A, 50 KA 4 Pole MCCB, Ics = 100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-800 A) with selector switch & Cts etc. LED type RYB phase indicating lamps, ON, OFF, trip including set of copper Bus Bar 1000 Amps. (a) MAIN FIRE PUMP : 250 Amp., 50 KA TPN MCCB, Ics=100% Icu, with fully automatic Star Delta starter suitable for pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation, selector switch for local / remote, auto / manual / OFF operation. - 2 Set (b) JOCKY PUMP : 125 Amp., 50 KA TPN MCCB , Ics=100%, with suitable HP fullY automatic Star Delta starter with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation, selector switch for local / remote, auto / manual / OFF operation. - 02 Set (c) DIESEL ENGINE CONTROL Control for Diesel Engine comprising - Automatic / Manual selector switch and 3 attempt starting device, timers and relays as required, push buttons, start / stop in manual mode. Indicating lamp for high / low Lub., oil pressure, High Water Temperature and Engine on indication. Battery charger suitable for 12 V / 24 V DC with boost and trickle salector switch, 0-30 V DC Voltmeter , and 0-20 A DC Ammeter. |
| 23 | Providing, laying, testing and commissioning of 'C' Class Heavy Duty M S pipe conforming to IS:3589 / IS:1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall / ceiling with suitable clamp / support frame and painting with two or more coats of red oxide and P O red synthetic enamel paint complete in all respects as required. Make Jindal (As per approved specification) (A) 25 mm |
| 24 | (B) 32 mm |
| 25 | (C) 40 mm |
| 26 | (D) 50 mm |
| 27 | (E) 65 mm |
| 28 | (F) 80 mm |
| 29 | (G) 100 mm |
| 30 | (H) 150 mm |
| 31 | (I) 200 mm |
| 32 | Supplying and fixing of internal hydrant valve with instantaneous Gunmetal / Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked confirming to IS:5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required ; Single headed Stainless Steel. |
| 33 | Supplying and fixing of external hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal / Stainless Steel coupling and cast iron wheel ISI marked confirming to IS:5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required ; Single headed Stainless Steel. |
| 34 | Supplying, fixing, testing and commissioning mmiecinning of of butterfly butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to 1S 13095 of following (a) 80 mm |
| 35 | (b) 100 mm |
| 36 | (c) 150 mm |
| 37 | Supplying, fixing, testing and commissioning of Double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze / gun metal seat, ISI marked complete with ing sizes confirming to IS:5312 complete with nuts, bolts, washers, gaskets conforming to IS:780 of following sizes as required : (a) 80 mm dia. |
| 38 | (b) 100 mm dia. |
| 39 | (c) 150 mm dia. |
| 40 | S/F of Orifice plate plate made out of 6 mm thick stainless steel ( Grade 304) with orfice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 41 | (b) 100 mm dia. |
| 42 | (c) 150 mm dia. |
| 43 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304 sheet with 3 mm dia holes with stainless steel flange (a) 100 mm dia |
| 44 | (b) 150 mm dia |
| 45 | Supplying and fixing of 63 mm dia, 15 Metre long RRL hose pipe with 63 mm dia male and female couplings duly bound with G I wire, rivets etc. confirming to IS:636(type - A) as required : stainless steel Grade (304) |
| 46 | Supplying and fixing of first aid hose reel with M S construction spray painted in post office red, conforming to IS:884 complete with the following as required : 20 mm nominal internal dia water hose thermoplastic(Textile reinforced) type - 2 as per IS:12585. 20 mm nominal internal dia gun metal globe valve and nozzle. Drom and brackets for fixing the equipment on wall. Connections from riser with 25 mm dia stop gum metal valve and M S pipe and socket. 30 Metre |
| 47 | Supplying and fixing of 63 mm dia short branch pipe with 20 mm nominal internal daimeter size nozzle confirming to IS:903 suitable for instantaneous connection to interconnect hose pipe coupling as required stainless steel Grade (304) |
| 48 | Supplying and fixing of Fire brigade connection of cast iron body with gun metal male instantaneous inlet coupling complete with cap and chain as required for suitable dia M S pipe connection confirmingto IS : 904 as required . 4 Way - 150 mm dia M S Pipe |
| 49 | Supplying and fixing of Air Vessel made of 250 mm dia, 8 mm thick M S sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required . |
| 50 | Providing, Fixing, testing and commissioning of 15 mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : (UL/FM listed / Approved). Pendent Sprinkler. |
| 51 | Supplying and fixing of Pressure Switch in M S pipe line including connection etc. as required. |
| 52 | 100 mm dia |
| 53 | Providing, Fixing, Testing and commissioning of installation, control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulucally driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc. of following sizes as required. 150 mm dia |
| 54 | Supplying and installing following size of perforated painted with powder coating M.S.cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. (a) 100 mm width X 50 mm depth X 1.6 mm thickness |
| 55 | (b) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 56 | S&F of Fire extinguisher, ABC Type 6.00 Kg. capacity (ISI marked IS: 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 57 | S&F of Co2 type Fire extinguisher, 4.5 Kg. capacity (ISI marked IS: 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 58 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. |
| 59 | S&F of shock treatment chart (Prescribed under I.E Rule) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work. |
| 60 | S&L of 1800 mm x 900 mm x 12 mm thick chequered rubber matting of tested quality. |
| 61 | SITC of Automatic priming Arrangement for all fire pump including necessary pipe, fitting, water level controller, 1 HP pump etc. complete in all respect. |
| 62 | SITC of pressure Gauge ranging from 0 to 14 kg. per sq.mm ISI marked from approved manufactures complete in all respect. |
| 63 | Supply & laying of Alluminium conductor PVC insulated armoured served sheathed 1100volt grade at a depth of 750mm below ground lvl on surface the cable run shall be fixed on MS complete of following size (a) 16 sq.mm x 4 core. |
| 64 | (b) 25 sq.mm x 3½ core. |
| 65 | (c) 95 sq.mm x 3½ core. |
| 66 | S/F of Warrraping coating for in ground M.S. pipe. |
| 67 | SITC of Rubber expention 100 mm complete. |
| 68 | SITC of Rubber expention 150 mm complete. |
| 69 | SITC of Anuciator Panel 4 Zone complete. |
| 70 | SITC of Signage Board |
| 71 | UG TANKEXCAVATION in foundation in ordinary Soil ( Loam clay or sand ) including all lift and lead upto 30.0 m & including filling watering and ramming of excavated earth into the space between the building & sides of foundation trenches or into the plinth and removal & disposal surplus earth as directed by the engineer I/C within a lead of 30 m.from foundation trenches. |
| 72 | Providing and laying in position cement concrete of specified gradeexcluding the cost of centering and shuttering - All work up to plinthlevel :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 73 | R.C.C. work with cement approved coarse sand and 2cm Gauge approved stone ballast in the proportion of 1:1.5:3 in RCC raft foundation and footing, excluding its fixing and binding wire and including necessary centering and shuttering etc and also including S/o all materials required for proper completion of the work. Binding wire to be supplied by the contractor free of cost. |
| 74 | R.C.C. work with cement approved coarse sand and 2cm Gauge approved stone ballast in the proportion of 1:1.5:3 in COLUMN, excluding its fixing and binding wire and including necessary centering and shuttering etc and also including S/o all materials required for proper completion of the work. Binding wire to be supplied by the contractor free of cost. |
| 75 | R.C.C. work with cement approved coarse sand and 2cm Gauge approved stone ballast in the proportion of 1:1.5:3 in , excluding its fixing and binding wire and including necessary centering and shuttering etc and also including S/o all materials required for proper completion of the work. Binding wire to be supplied by the contractor free of cost. But in slab |
| 76 | Thermo-Mechanically Treated bars of grade Fe-500D or more work such as in reinforced concreted or reinforced brick work (when not included in overall rates) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage. |
| 77 | 12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand) in single coat on smooth side of single or half brick wall. |
| 78 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, includi |
| 79 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. (a) For vertical surface two coats @ 0.70 kg per sqm |
| 80 | (b) For horizontal surface one coat @1.10 kg per sqm. |
| 81 | Supplying and fixing C.I. cover without frame for manholes : 560 mm diameter C.I. cover (heavy duty) the weight of the cover to be not less than 108 kg |
| 82 | Centering and shuttering including strutting, propping etc. and removal of form for : (a) Foundations, footings, bases of columns, etc. for mass concrete |
| 83 | (b) Columns, Pillars, Piers, Abutments, Posts and Struts |
| 84 | (c) Suspended floors, roofs, landings, balconies and access platform. |
| 85 | FIRE ROOMEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All Kind of Soil |
| 86 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift. |
| 87 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) (Base Concrete) |
| 88 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 89 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Footing) |
| 90 | Concrete of M25 grade with minimum cement content of 330 kg /cum (Beam) |
| 91 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Column upto plinth) |
| 92 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Column) |
| 93 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Lintel) |
| 94 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Beam) |
| 95 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.:)Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M25 grade with minimum cement content of 330 kg /cum (Slab) |
| 96 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 97 | Brick work with common burnt clay F.P.S. (non modular) bricks of class-150 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 98 | Brick work with common burnt clay F.P.S. (non modular) bricks of class-150 in superstructure above plinth level up to floor V level in all shapes and sizes in :(1 cement : 6 coarse sand) (230mm wall) |
| 99 | Providing 40x5 mm flat iron hold fast 400 mm long including fixing toframe with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 300x100x150 mm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 100 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 2.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer.Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 101 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 102 | Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS, 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge.Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately.Three track three panels sliding window with two glazed & one wire mesh panels with Aluminium channel for roller track, wool pile, nylon rollers with SS 304 body.Using R3 series with frame (98 mm & above) x (40 mm & above) & both glazed and fly screen sash (30 mm & above) x (55 mm & above) with zinc alloy (Zamak) powder coated handle on every glazed panel along with multi-point locking system. (Height upto 1.8m). |
| 103 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 104 | Providing and fixing fly proof stainless steel grade 304 wire gauge, to windows and clerestory windows using wire gauge with average width of aperture 1.4 mm in both directions with wire of dia. 0.50 mm all complete. |
| 105 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. |
| 106 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 300x16mm |
| 107 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 300x16mm |
| 108 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 125 |
| 109 | 12mm thick plaster in inner walls with proportion of 1:6 cement & approved coarse sand |
| 110 | 15mm thick plaster in Outer walls with proportion of 1:6 cement & approved coarse sand |
| 111 | 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 112 | Providing and applying white cement based putty of average thickness 1mm, of approved brand and manufacturer, over the plastered wall surfaceto prepare the surface even and smooth complete. |
| 113 | One priming coat & one coat oil distemper on new work including supply of material, labour T&P etc. required for proper completion of the work. (Two Coat) |
| 114 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 115 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture |
| 116 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 117 | Centering and shuttering including strutting, propping etc. and removal of form for Footing |
| 118 | Centering and shuttering including strutting, propping etc. and removal of form for Plinth Band |
| 119 | Centering and shuttering including strutting, propping etc. and removal of form for Column upto plinth |
| 120 | Centering and shuttering including strutting, propping etc. and removal of form for Column |
| 121 | Centering and shuttering including strutting, propping etc. and removal of form for Lintel Band |
| 122 | Centering and shuttering including strutting, propping etc. and removal of form for Beam |
| 123 | Centering and shuttering including strutting, propping etc. and removal of form for Slab |
| 124 | FIRE ROOM (ELECTRICAL WORK)Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C (a) Light Point |
| 125 | (b) Fan Point |
| 126 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 127 | (b) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 128 | (b) 2X4 sq. mm + 1X4 sq. mm earth wire |
| 129 | (c) 2X6 sq. mm + 1X6 sq. mm earth wire |
| 130 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connection etc. as required. |
| 131 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 132 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. (a) 1 or 2 Module (75mmX75mm) |
| 133 | (b) 6 module (78mm X 205 mm X 50 mm) |
| 134 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 135 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm |
| 136 | Providing and fixing LED Light 50 watt LED complete in all respect. |
| 137 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way, Double door |
| 138 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single Pole |
| 139 | (b) Single Pole Neutral |
| 140 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A |
| 141 | PUBLIC ADRESSING SYSTEMSupplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
| 142 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 143 | Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required. |
| 144 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
| 145 | Supplying, installation, testing & commissioning of digital audio amplifier 450 Watt, 25V rms operating at 240 volt AC supply complete as required. |
| 146 | Supply, Installation, Testing & Commissioning of 42 U floor mount rack with fans , 2 cable managers , satationary shelf , 2 Nos. of hardware pkts. |
| 147 | Supply, Installation, Testing and Commissioning of 4 pair, U/UTP, 24 AWG solid copper CAT6 cable. |
| 148 | Supply, Installation, Testing and Commissioning of CAT6 UTP RJ-45 Patch Cords Solid Conductor 7ft |
| 149 | Supplying & laying of 2 X1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 150 | Speaker cable Two pair , 2-core, 1.5 sqmm |
| 151 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 152 | GST Extra as applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail