| 1 | Supply of 400 sq. mm 3 core high conductivity aluminum strand compacted circular conductor XLPE armoured 33 KV cable neutral earthed system confirming to IS 7098-Part-Il (1985) with latest amendment complete in all respects as per direction of E/L Make: Gloster/Universal/Polycab/Havells. (UPERC P-47) |
| 2 | Laying of one number additional XLPE power cable of 33 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. DSR Electrical 8.7.2 |
| 3 | S/Making of Straight through joint suitable for 400sq.mm x 3 core 33 KV armoured cable as per ISS & complete as per the direction and satisfaction of Ell (Raychem, Denson, Cabseal Make) (UPERC P-47) |
| 4 | S/Making of Cable Jointing kit outdoor for 400sq.mm x 3 core 33 KV armoured cable as per ISS & complete as per the direction and satisfaction of El (Raychem, Denson, Cabseal Make) (UPERC P-47) |
| 5 | Providing and Fixing of 3mm thik MS CNC cut Greel with primer and two or more coat of PU paint complete with all respects as per direction of Engineer- Incharge. |
| 6 | Providing and laying of 200 mm dia 6 mm thickness through trenchless method including jointing of pipe. Excative of thrust pit and receiving pit of required size with all T&P and the excation & back filling with compaction complete as per specification for road crossing by H.D.D. machine method pipoe will be installed at minumum depth 2M to 3M below the ground surface or download as per site condition in required slope. (AOR) |
| 7 | Supply and buring of safe earthing electrode T-19 (Hot dip galvanized), length up to 2000mm outer type 50mm, inner pipe, 22mm terminal dia 12mm, outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip galvanization up to 100 micron filled with crystalline conductive mixture(CCM) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good micture of retaining capicity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25x3 G.I. strip will be extra as per PS No. 725A |
| 8 | Demolighing R.C.C. Work mannually by mechnical means including stacking of steel bars and disposal of unservicable material within 50 mtr. Lead as per direction of E/I. (AOR) |
| 9 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 KGS activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25mm x 3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. PS. No. 725 (B) |
| 10 | Supply of one number 3 core 185 sqmm , XLPE Al. conductor cable of 11kv grade and PVC sheathed XLPE Power cable of 11kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 11 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : DSR Electricals 10.5.2 120 sq. mm |
| 12 | Laying of One number XLPE Power cable of 11 KV grade of following size the existing RCC/HUME/METAL/HDPE pipe as required (DSR in elect 2018 Item No 8.3.2 /P-44) above 120 sqmm and upto 400 sqmm |
| 13 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : upto 240 sq. mm DSR Electricals 10.6.3 |
| 14 | SITC of flexible copper power cable 3cx2.5 somm (AOR) |
| 15 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 metre and upto 12.00 metre DSR Electrical 2018/I.No. 11.3.4 |
| 16 | Supply of Steel Tubular Pole 11 M long designated . complete in all respects UPERC P-40 |
| 17 | Painting of the electric pole with 2 coats of aluminium paint over red oxide primer complete in all respect. PS No. 634 |
| 18 | S/F Of straight MS channel 50x100 mm (9.2 per kg) 1.15 MTR Long including S/E of suitable clamp made of MS flat 50x6 mm including all nuts and bolts fixing on pole. T off channel UPERC P-48 |
| 19 | S/E of straight MS Channel 2.24 M long as per design 50x 100mm (9.2 kg/M)with required clamps made of M. S. adt of size 50x6 MM with all nuts and bOlts etc. as per direction of E/I UPERC P-39 |
| 20 | dismantling of pole/ street light standard/ stru embedded in cement concrete foundation etc. as equired. DSR Electrical 2018/1. No. 12.42 |
| 21 | Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required. DSR Electrica 2018/I.No. 12.40 |
| 22 | Supply & erection of overhead line with ACSR conductor on poles / service bracket including binding etc. complete in all respects. |
| 23 | Supply and laying of 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc.PS 506 (F) 120 sq. mm 3 core |
| 24 | S/Laying of heavy density poly ethylene pipes ISI marked anti rediant grade OD 160mm dia PN-8 PE 100 (PE 400) grade as per IS code 4984 with excavation at Depth of 1.20 M below ground level i/c the cost of cutting of pipes for making up to length and making joints complete all respects as per direction of E/I (creator poly extrusion/rex/times/narendra plast/ Pioneer/make) (AOR) |
| 25 | S/L of 3\\" (80mm) dia G.I. Pipe 'B' Class in the ground level including road cutting Complete in at respects as per direction of Eli DSR Electrical 12.38 |
| 26 | Supply and fixing following capacity of automaticstreet light cubicle control panel painted with anticorrosive alkali and acid proof paint consisting oftime switch TSO 100 series with contactors, HRC fuses, isolating switch metering instrument &instrument box with CTs etc. in case of TPN, complete in all respect. 40 A TPN UPPWD SOR 2018 Item no. (807 (le) i) electrical |
| 27 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement: 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) AOR Please Enable Macros to View BoQ information |