| 1 | Contract Details |
| 2 | Taking down carefully copper /aluminium point wiring (light,fan,socket or power ) complete fittings such as switches and fixtures ceiling roses, pendants, regulators, sockets, lamp holders, bracket light fittings, bulk heads fittings, tube light fittings etc removing the materials from site and making good disturbed surfaces of walls, floors etc complete all as specified and directed. |
| 3 | S&F point wiring for one light point/ fan/ bell/ 5Amps socket out let (independent)point controlled by one, one way switch with 1.5Sqmm size, PVC insulated and unsheathed 1100volts grade, single core stranded (multistrand) copper conductor (FRLS) PVC cable drawn into & including medium grade PVC conduit (not less than 20mm outer dia )with all fittings and accessories fixed concealed (including chase cutting in brick/ stone masonry walls for fixing conduit and plastering and whitewash/colouring the external surface and matching the same with existing surface) and sunk cast iron or pressed steel terminal boxes for mounting fittings like switches, sockets & fan regulators etc with 3 mm thick plastic laminated sheet covers fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.5 Sqmm multistranded copper conductor cable earth wire and connected to earth dolly complete all as specified and directed (a) One light/One fan/one bell point controlled by one switch. |
| 4 | All as per item no. 2 above but for one light point controlled by Two way switch. |
| 5 | All as per item no. 2 above but for one socket outlet 5 pin 5 amps controlled by one switch on same board. |
| 6 | All as per item no. 2 above but for one socket outlet 5 pin 5 amps controlled by one switch on independent board. |
| 7 | All as per item No 2 herein before but wiring with 2.5 sqmm copper wire (FRLS) PVC and 2.5 sqmm earth wire for socket outlet 6 pin 16 amps on independent board. |
| 8 | S & F point wiring for one light point / fan point / bell point / 5 Ampere socket outlet point (independent point), controlled by one, one way switch with 1.50 sqmm size PVC insulated unsheathed 1100 volts grade single core multi-stranded) copper conductor cable (FRLS) drawn into and including PVC casing capping of suitable size with its all necessary fittings and accessories on wooden / stone / brick masonry wall surface and sunk cast iron or pressed steel terminal boxes for mounting fittings like switches, sockets, lamp holders, sketch fittings and covered with 3 mm thick plastic laminated bakelite sheet cover fixed with brass screws and cup washers including one continuous run of PVC insulated (green colour) 1.50 sqmm size solid copper conductor cable as in earth wire and connected to common earth dolly complete all as specified and directed.(a) One light/one fan/one bell point controlled by one, one way switch. |
| 9 | All as per item no. 7 above but for One socket outlet 5 pin 5 amps controlled by one switch on same board. |
| 10 | All as per item no. 7 above but for One socket outlet 5 pin 5 amps controlled by one switch on independent board. |
| 11 | All as per item No 7 herein before but wiring with 2.5 sqmm copper wire (FRLS) PVC and 2.5 sqmm earth wire for socket outlet 6 pin 16 amps on independent board. |
| 12 | S&F switch piano flush type single pole, one way 5 Amp complete all as specified and directed. |
| 13 | S&F switch piano flush type single pole, Two way 6 Amp complete all as specified and directed. |
| 14 | S&F socket out let multi 5 pin, 5 Amps, flush type complete all as specified and directed. |
| 15 | S&F switch piano flush type single pole, one way 15 Amp complete all as specified and directed. |
| 16 | S&F socket out let 2 in1,3 pin, 5 and 15 Amp, flush type complete all as specified and directed. |
| 17 | S&F ceiling rose, PVC/ Poly carbonate,isolated body three terminal complete all as specified and directed. |
| 18 | S & F lamp holder angle type PVC/Poly carbonate type insulated body with back plate suitable for batten/wall fitting complete all as specified and directed. |
| 19 | S & F call bell ding dong AC, 230V single pole complete all as specified and directed, |
| 20 | S&F bell push piano flush type single pole, one way 5 Amp complete all as specified and directed. |
| 21 | Supply and fix High quility LED T5 integrated batten tube light 20 Watt with aluminium extrusion with frosted PMMA/PC diffuser, internaly pre wired of 1.5 sqmm twin twisted flexible cable all as specified & directed. |
| 22 | S & F in repair MCB single pole, 240 volts, 5 to 32 Ampere, rupturing capacity 10 KA, ‘B’ curve type in the MCB DB including taking down complete all as specified and directed. |
| 23 | S & F in repair MCB single pole and neutral, 240 volts, 16-32 Amp, rupturing capacity 10 KA, ‘B’ curve type complete all as specified and directed. |
| 24 | S & F in repair MCB Four pole, 415 volts, 40 to 100 Ampere, rupturing capacity 10 KA, ‘B’ curve type complete all as specified and directed. |
| 25 | S&F in repair sheet metal enclosure for DBs(double door type) single pole and neutral 8 way including blacking platge as required with 200 Amps rated bus bar, 240 volts fixed complete all as specified and directed . |
| 26 | S&F in repair sheet metal enclosure for DBs(double door type) single pole and neutral 4 way including blacking platge as required with 200 Amps rated bus bar, 240 volts fixed complete all as specified and directed . |
| 27 | S&F in repair sheet metal enclosure for DBs(double door type) Triple pole and neutral 4 way including blacking platge as required with 200 Amps rated bus bar, 240 volts fixed complete all as specified and directed. |
| 28 | Taking out old U/S Sub main wiring for replacement including S&F sub main wiring with two single core FRLS PVC insulated and sheathed 1100 Volts grade, 4 Sqmm size cables, PVC insulated stranded copper conductor fixed in PVC conduite pipe 25mm dia with all accessories and one continuous run of 4 Sqmm copper conductor PVC (Note :- Two single core cables along with earth wire and conduit shall be measured as one unit length). |
| 29 | Taking out old U/S Sub main wiring for replacement including S&F sub main wiring with two single core FRLS PVC insulated and sheathed 1100 Volts grade, 6 Sqmm size cables, PVC insulated stranded copper conductor fixed in PVC conduite pipe 25mm dia with all accessories and one continuous run of 6.0 Sqmm copper conductor PVC (Note :- Two single core cables along with earth wire and conduit shall be measured as one unit length). |
| 30 | S&F sub main wiring with two single core FRLS PVC insulated and sheathed 1100 Volts grade, 10 Sqmm size cables, PVC insulated stranded copper conductor fixed in PVC conduite pipe 25mm dia with all accessories and one continuous run of 10.0 Sqmm copper conductor PVC (Note :- Two single core cables along with earth wire and conduit shall be measured as one unit length). |
| 31 | Taking out old U/S service connection cable for replacement including S&F service connection cable, 1100 volts grade heavy duty PVC insulated aluminium conductor, 16 Sqmm 2 core size, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular, complete all as specified and directed. |
| 32 | M&L for earthing complete with galvanised steel, earth plate electrode 600x600mm x 6mm thick burried directly in ground verticaly (earth pit not less than 2.25 mtrs below ground level ) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electrical plate No 3 on page 497 of MES schedule 2009 part - I connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handle to cover, GI protection pipe 15mm dia light grade up to 7.5mtr from electrode GI pipe to be fixed with complete all as specified and directed.Note :- (i) Earth lead beyond 7.5 mtr from electrode to earth terminal point/main switch & GI pipe light grade 15mm dia for protection against mechanical damage to lead shall be measured separately. (ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost. |
| 33 | Supply and fix High quility LED lighting fixture mirror type with high output diffuser 2 feet 1x 10 Watt. 220V AC,complete with polycarbonate tube, white/warm white suitable for mirror light internally pre wired of 1.5 sqmm three core flexible cable complete all as specified & directed. |
| 34 | S & F Exhaust fan plastic body heavy duty ISI mark, 250 mm size with louvers including all connecting accessories and cutting opening on wall and making good as per existing surface complete all as specified and directed |
| 35 | Disconnecting , taking down & removing carefully the existing ceiling fan, exhaust fans, wall bracket fans and air circulating fans etc. of any description, any sweep, for repairs, servicing , overhauling, painting and numbering with white synthetic enameled paint etc., dismantling & opening of the fans, checking serviceability of parts, overhauling by necessary cleaning, oiling & greasing and painting, fixing the serviceable parts in position, including replacement of burned copper winding, bearing, fan blade and any other defective/ unserviceable parts with new parts, reassembling the fans, making necessary adjustment and proper alignment of blades, hanging / fixing the repaired fans in position, connecting to existing electric sources and testing at site to the entire satisfaction complete all as specified and directed. |
| 36 | Supply and fix in repair modular type switch single pole, one way 6 Amp complete all as specified and directed. |
| 37 | Supply and fix in repair socket out let multi 3 pin, 6 Amps, Modular type complete all as specified and directed. |
| 38 | Supply and fix in repair switch modular type single pole, one way 16 Amp complete all as specified and directed. |
| 39 | Supply and fix in repair socket out let 2 in1,3 pin, 6 and 16 Amp, modular type complete all as specified and directed. |
| 40 | Supply and fix in repair modular cover plate 3 module complete all as specified and directed. |
| 41 | Supply and fix in repair modular cover plate 6 module complete all as specified and directed. |
| 42 | S & F in repairs Plug top 3 pin 15 amp, complete all as specified and directed |
| 43 | Supply & fix in repair electronic fan regulator stepped type 5Amps, flush type on the existing phenolic laminated sheet complete all as specified and as directed |
| 44 | Disconnecting and taking down the existing Geyser of any description and any capacity (25 / 50 Ltrs) and any position from the existing location and Dismantling the Geyser of any capacity and of any description material and labour for cleaning and de-scaling the inner tank and other parts/ accessories including inlet, outlet, overflow Geyser element, thermostat, ‘U’ assembly etc. with brush, cleaning rod, and using de-scaling solution mixed with water in suitable proportion till the complete deposits /scale is removed as approved by Engineer-in-Charge, brazing for stopping leakage of copper inner tank/gas welding for inner steel tank, re- assembling the complete Geyser after cleaning, painting of geyser with white synthetic enameled paint and fixing and installation of Geyser in position and testing to the entire satisfaction of Engineer-in-Charge. Note :- Spare parts if any required replacement shall be measured and paid separately |
| 45 | Supply & fix in repairs Indicating lamp of size /shape as per existing suitable for 230 Volts AC supply. complete all as specified and directed |
| 46 | Supply & fix in repairs Geyser thermostat of size /shape as per suitable for 25 ltrs & 50 ltr cap heavy duty copper material used 230 Volts AC supply. complete all as specified and directed |
| 47 | Supply & fix in repairs geyser heating element of 1.5 & 2 Kw cap heavy duty copper material used and round cup or triangle cup shape with rubber washer .complete all as specified and directed |
| 48 | Supply & fix in repair Capacitor for ceiling fan 2.5/4.0MFD copper wired |
| 49 | S & F LED bulb 9 watt all as specified and directed . |
| 50 | Disconnecting ‘U’ assembly brass type of 25 Ltr cap any description and in any position from Geyser and supply and fixing new ‘U” assembly to match with the existing system complete all as specified and directed. |
| 51 | S & F Recess mounting LED 300x300 mm luminaire,18 W, 230v, suitable for Recessed mounting ,with powder coated CRCA housing with LEDs, seamless front frame complete with driver and all accessories internally pre-wired and including necessary cutting as required in panel and connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 52 | S & F Recess mounting LED luminaire 600mm x 600 mm ,36 W, 220v, with high efficiency PMMA diffuser soft glare free light suitable for recessed mounting ,with powder coated CRCA housing with LEDs, seamless front frame complete with driver and all accessories internally pre-wired and including necessary cutting as required in panel and connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed. |
| 53 | S & F in replacement bldg security light luminaires of 25 watt LED suitable for 220-230 V, 50 Hz with IP 65 protection including bracket for fixing fitting made of 32mm bore light grade GI pipe connecting up with three core twisted flexible copper conductor cable complete all as specified and directed. |
| 54 | Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed |
| 55 | S & F LED bulk head fitting, 1 x 10 watt with PDC aluminium housing and milky diffuser complete with all accessories and including LED light driver holder connecting up with three core twisted flexible copper conductor cable with suitable size of 230 Volts, 50 Hz complete all as specified and directed. |
| 56 | S & F LED bollard fitting 09 Watt LED in cylindrical shape design IP66 protection, with opal PC diffuser, ensuring excellent distribution and high system lumen efficacy as per Cat Part No BGBOL6059WLEDWW of makeBajaj or equivalent of other make as approved by Engineer in charge, complete with all accessories and including PCC work (1:3:6 ) for fixing the light fitting and connecting up with twin core twisted flexible copper conductor cable with suitable size of 230 Volts, 50 Hz complete all as specified and directed. |
| 57 | Taking out old U/S Sub main wiring for replacement including S&F sub main wiring with two single core FRLS PVC insulated and sheathed 1100 Volts grade, 2.5 Sqmm size cables, PVC insulated stranded copper conductor fixed in PVC conduite pipe 25mm dia with all accessories and one continuous run of 2.5 Sqmm copper conductor PVC (Note :- Two single core cables along with earth wire and conduit shall be measured as one unit length). |
| 58 | Supply and fix High quality LED smart batten tubelight 20 W, aesthetically designed LED having extruded aluminum housing with Microwave motion technology for providing an energy efficient solution and with aluminum housing & integrated electronic driver, internaly pre wired of 1.5 sqmm twin twisted flexible cable all as specified & directed. |
| 59 | S&F LED Suspended architectural LED 20W luminaire provides soft-light and glare free symmetrical illumination (with continuous mounting end cap) complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size and suspended from ceiling comple all as directed. |
| 60 | Note :-Tenderers may be noted that amount of credit will be deducted from the total amount arrived, at the time of Acceptance of contract. Please Enable Macros to View BoQ information |