| 1 | Taking down carefully aluminium point wiring (light, fan socket or power) complete including PVC Casing Capping/concealed conduit, fixture and fitting such as switches, ceiling roses, pendents, regulators, sockets , light fitting etc removing materials for taking credit and making good disturbed surface of walls, floors etc complete all as specified and directed by Engineer-in-charge. |
| 2 | Taking down the existing unserviceable main switch / cut out / DBs of any type / capacity / description alongwith MCB/MCCBs as existing at site including necessary making good the disturbed surfaces to match with the existing finishes complete all as specified and directed by Engineer-in-charge. |
| 3 | M & L for point wiring complete with and including single core PVC insulated unsheathed flexible bright annealed multi stranded copper conductor cables FRLSH 2.5 sqmm (22/0.30mm) 1100 volts grade drawn through and including ERW steel conduit 20 mm or higher dia as required at site, fixed on surface of walls/columns/beams/tie beam etc; by means of saddles and clips etc; including all conduits accessories / fittings / junction boxes/inspection covers etc.; of heavy grade, ISI marked and sunk terminal boxes factory made 16 SWG pressed steel housing, totally concelaed in walls with 3mm thick industrial laminated sheet top cover, fixed flush with wall surface by means of brass screws and sunk /cup washers, for mounting of switches, sockets fan regulators etc; including 2.5 sqmm (14/0.30mm) 1100V grade PVC insulated, unsheathed flexible multistranded copper conductor cable as continuous earthwire connected to metallic bodies of Iuminaires/fans etc; at one end and to common earth dolly at other end, all as specified, directed and shown on drgs, for :- |
| 4 | One light point controlled by one, one way switch |
| 5 | Two light points controlled by one, one way switch |
| 6 | Three light points controlled by one, one way switch |
| 7 | Four light points controlled by one, one way switch |
| 8 | S&F submain wiring with cable insulated single core multistranded copper conductor cable 1100 volts 2x 4 sqmm drawn through 20 mm dia Steel ERW Conduit (Concealed/Surface as per site requirement) alongwith 4.0 sqmm copper conductor cable for earth continuity including taking down old u/s sub-main wiring complete all as specified and directed by Engineer-in-charge.Note : 3 runs of 4.0 sqmm cable and one run of Steel ERW Conduit will be measured as one RM. |
| 9 | S&F submain wiring with cable insulated single core multistranded copper conductor cable 1100 volts 2x 6 sqmm drawn through 20 mm dia Steel ERW Conduit (Concealed/Surface as per site requirement) alongwith 6.0 sqmm copper conductor cable for earth continuity including taking down old u/s sub-main wiring complete all as specified and directed by Engineer-in-charge.Note : 3 runs of 6.0 sqmm cable and one run of Steel ERW Conduit will be measured as one RM. |
| 10 | S&F submain wiring with cable insulated single core multistranded copper conductor cable 1100 volts 4x 6 sqmm drawn through 25 mm dia Steel ERW Conduit (Concealed/Surface as per site requirement) alongwith 6.0 sqmm copper conductor cable for earth continuity including taking down old u/s sub-main wiring complete all as specified and directed by Engineer-in-charge. Note : 5 runs of 6.0 sqmm cable and one run of Steel ERW Conduit will be measured as one RM. |
| 11 | S&F submain wiring with cable insulated single core multistranded copper conductor cable 1100 volts 4x 10 sqmm drawn through 25 mm dia Steel ERW Conduit (Concealed/Surface as per site requirement) alongwith 10.0 sqmm copper conductor cable for earth continuity including taking down old u/s sub-main wiring complete all as specified and directed by Engineer-in-charge. Note : 5 runs of 10.0 sqmm cable and one run of Steel ERW Conduit will be measured as one RM. |
| 12 | Supply and fixing LED light fitting 150 Watt flame proof, CIMFR-BIS-PESO certified recommended for gas/ vapor group of IIC, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with driver connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable in flexible metalic conduit with suitable size complete all as specified and directed by Engineer-in-charge. |
| 13 | Supply and fixing LED light fitting 2x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable in flexible metalic conduit with suitable size complete all as specified and directed by Engineer-in-charge. |
| 14 | S&F in repair Flame proof and weather proof Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V SP, 50 Hz, complete all as specified and directed by Engineer-in-charge. |
| 15 | S&F in repair Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 25 A,250V, 2P+earth complete all as specified and directed by Engineer-in-charge. |
| 16 | Supply and fix in repair Flame Proof Weather Proof DB (Distribution Board) TPN 4 Way Having Incoming MCCB of 100 A 4Pole 16 Ka and outgoing total 12 MCB’s CBs as – 4 Nos. 6 Amps Single Pole Mcb , 4 Nos. 10 Amps Single Pole Mcb and 4 Nos. 16 Amps MCb Single Pole all including interconnections and Bus Bar of Suitable Size With Sufficient Entries for Mounting Cable Gland for incomer and outgoing Cables as Per Make – Sudhir or Equivalent in Flexpro / Baliga |
| 17 | Supply and fix in repairs Flame Proof Weather Proof DB (Distribution Board) SPN 8 Way Having Incoming MCB of 32 A 2 Pole and outgoing total 06 MCB’s MCBs as – 2 Nos. 6 Amps Single Pole Mcb , 2 Nos. 10 Amps Single Pole Mcb and 2 Nos. 16 Amps MCb Single Pole all including interconnections and Bus Bar of Suitable Size With Sufficient Entries for Mounting Cable Gland for incomer and outgoing Cables as Per Make – Sudhir or Equivalent in Flexpro / Baliga |
| 18 | Supply and fix in repairs LED street light fitting 40 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver,holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed by Engineer-in-charge. |
| 19 | Taking out carefully copper/GI earthing complete including GI pipe and removing materials for taking credit and making good disturbed surface complete all as specified and directed by Engineer-in-charge. |
| 20 | Taking down carefully copper/GI earthing Strip Copper/Aluminium /GI wire complete including and removing materials for taking credit and making good disturbed surface complete all as specified and directed by Engineer-in-charge. |
| 21 | M & L bore earthing not less than 250 mm dia 16 feet deep filled with black soil up to 7 feet from bottom complete with galvanized iron pipe 40 mm bore medium grade 3 meter long tapers at bottom & provided 12 mm holes (staggered) at 75 mm centre to centre up to 2.5 meter of length from bottom , burried directly in ground filled with 45 cm alternate layer of chemical magnisium sulphate, charcoal & salt up to ground level connected to galvanized iron strip 32x6 mm as earthing lead up to 7.5 mtr by means of bolt and nut, check nuts and washer of galvanized iron or steel including brazing work and 40mm dia light grade pipe for earth lead protection connected to electrical equipment and earthing test point , earth dolly and earth chamber as shown in elect plate No 2 of SSR Pt-I including all necessary earth work, excavation, earth chamber with PCC 1:3:6, Type C1 and RCC chamber cover of PCC 1:2:4 with handle , funnel and wire mesh etc and testing on complete all as specified and directed by Engineer-in-charge. Note : Testing of earthing of any type, after disconnecting from test point and other loops by using ISI marked digital/Analog earth tester of reputed make and test result shall be entered in a Earth Testing register and put up to the Engr-in-Charge after testing complete all as specified and directed. Test result for item No. 6 and all earthing in schedule to be provided to Engr-in-Charge before completion of work. Earth tester to be provided by the contractor himself. |
| 22 | M&L of bore earthing not less than 250 mm dia 16 feet deep filled with black soil up to 7 feet from bottom complete with Copper pipe 40 mm bore medium grade 3 meter long tapers at bottom & provided 12 mm holes (staggered) at 75 mm centre to centre up to 2.5 meter of length from bottom , burried directly in ground filled with 45 cm alternate layer of chemical magnisium sulphate, charcoal & salt up to ground level connected to copper strip 32x6mm as earthing lead up to 7.5 mtr by means of bolt and nut, check nuts and washer of galvanized iron or steel including brazing work and 40mm dia light grade pipe for earth lead protection connected to electrical equipment and earthing test point , earth dolly and earth chamber as shown in elect plate No 2 of SSR Pt-I including all necessary earth work, excavation, earth chamber with PCC 1:3:6, Type C1 and RCC chamber cover of PCC 1:2:4 with handle and 20 mm dia GI watering pipe with funnel and wire mesh etc and testing on complete all as specified and directed by Engineer-in-charge. |
| 23 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in pipe or fixed to DBs or any other indicated situation for loop earthing with copper strip of 32X6 mm size complete all as specified and directed by Engineer-in-charge. |
| 24 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit or fixed to DBs or any other indicated situation for loop earthing with 32X6 mm dia GI strip size complete all as specified and directed by Engineer-in-charge. |
| 25 | S&F in repairs GI Tubing light grade 40 mm dia.for cable protection complete all as specified and directed by Engineer-in-charge. |
| 26 | S&F in repairs Single pole and nuetral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amp complete all as specified and directed by Engineer-in-charge. |
| 27 | S&F in repairs Triple pole and earth enclosure with a three pin and earth plug and socket complete with one triple pole MCB 63 Amp complete all as specified and directed by Engineer-in-charge. |
| 28 | S&F in repairs Earthing Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos 8mm dia 25mm long hex. head screw.Material and labour for testing/termination point made out of 32 x 6 mm copper strip of length 150 mm duly housed in suitable MS box insulators etc for linking the down conductor and the earth terminals of the lightening arrester system complete all as specified and directed by Engineer-in-charge. Please Enable Macros to View BoQ information |