| 1 | Taking out of existing LT UG cable of size 3½/4 core, 35 sqmm to 70 sqmm including taking out protection bricks complete all as specified and directed. |
| 2 | Taking out of existing LT UG cable of size 3½/4 core, 120 sq.mm including taking out protection bricks complete all as specified and directed. |
| 3 | Supply and laying in trenches / ducts, passing through pipe / fixing on poles 1100 volts grade, ISI marked of size 120 Sq.mm 3.5 core, LT cable (heavy duty), XLPE insulated served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and over all PVC sheathed with stranded aluminium conductor cable including commissioning and testing complete all as specified and directed.Note: (i) Excavation & earth work ,sand and brick will be measured and paid separately. |
| 4 | All as per Item No. 3 herein before but cable of size 70 sqmm, 3.5 core complete all as specified and directed. |
| 5 | All as per Item No. 3 herein before but cable of size 35 sqmm, 3.5 core complete all as specified and directed. |
| 6 | M&L for LT cable straight through jointing kit heat shrinkable type suitable for XLPE/ PVC insulated cable of size 3.5/4 Core, 70 to 120 sqmm complete including testing the cable joint for healthiness, cutting & removing unserviceable joint, preparation of both ends of cable to be joined with necessary stretching, aligning, making joint complete all as specified and directed |
| 7 | All as per Item No 6 herein before but straight through of size 35 sqmm 3.5 core complete all as specified and directed. |
| 8 | M & L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 MPa working pressure complete all as specified and directed. |
| 9 | Excavation in trenches in any type of soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cables, RCC poles/stays and struts etc or /getting out cable cover and stacking for reuse/ credit , trimming sides and forming bottom surface all as specified and directed at site. |
| 10 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed. |
| 11 | Removing surplus excavated soil nexc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified and directed. |
| 12 | M&L for dry sand cushioning to underground cables with 8 cm thick before laying of cables and 15 cm thick after laying and stretching of Cable complete all as specified and directed.Note : Only punned thickness i.e. 18 cm shall be measured and paid. |
| 13 | M & L for sub class 'B' brick for covering to under ground cable laid flat transversally width equal to the length of the cable complete all as specified and directed. |
| 14 | M&L for Horizontal Boring under hard standing/ pavements or roads manually using suitable auger for insertion of GI pipes up to 100 mm bore and making good the disturbed surface complete all as specified and as directed.Note: GI pipe will be measured and paid separately. |
| 15 | S&F GI tubes 80 mm bore dia light grade with all fittings laid in trenches or inserting in horizontal boring complete all as specified and as directed. |
| 16 | M&L for precast RCC 1:2:4 type B-1 (using 20mm graded stone aggregate) route indicator suitable for mounting on route of LT cable of size 25cm (width) x10cm (depth) x 60 cm overall height including 4mm gauge iron bar @ 100mm spacing both way, embedded to the depth not less than 20 cm below ground level, complete all as specified and directed. Please Enable Macros to View BoQ information |