| 1 | Taking down carefully copper/aluminium point wiring (light/fan/socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc including making good the disturbed surfaces to match with the existing complete |
| 2 | M&L for point wiring with single core FRLS, PVC insulated, unsheathed multi stranded copper conductor of size 1.5 sqmm alongwith 1.5 sqmm earth wire of multi strand copper conductor (with same specification) casing caping/conduit pipe including replacement of sunk zinc coated pressed steel terminal box of 1.60mm thick with 3mm thick plastic laminated sheet top cover, brass screws, cup washers etc and including all cutting / chases etc in walls for sunken boxes and making good to the disturbed surfaces to match the existing complete all as specified and directed for the following :- |
| 3 | One light point controlled by one switch |
| 4 | One ceiling/exhaust fan point controlled by one switch |
| 5 | One socket outlet 5 Amps controlled by one switch on same board |
| 6 | One socket outlet 5 amps controlled by one switch on independent board |
| 7 | All as per the description of srl item No 02 above item but wiring with 2.5sqmm copper wire and 1.5sqmm earth wire for socket out let 16 Amps on independent board |
| 8 | M&L for point wiring concealed type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic suitable size PVC conduit complete with all PVC conduit accessories suitable for modular type switches/sockets/fan regulators with cover plates, blanking plates, brass screws, cup washers etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the followingsNote:- 1. Rates deemed to be included for GI metal flush box reqd modulars size, Modular cover inner and outer plates, blanking plates etc complete 2. Modular switch, sockets, Bell push measured and paid separately under relevant items. |
| 9 | One light point controlled by one switch |
| 10 | One ceiling/exhaust fan point controlled by one switch |
| 11 | One socket outlet 5 Amps controlled by one switch on same board |
| 12 | One socket outlet 5 amps controlled by one switch on independent board |
| 13 | One bell point controlled by one bell push switch |
| 14 | All as per the description of srl item No 04 above item but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 2.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire. |
| 15 | M&L for point wiring concealed type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic suitable size PVC conduit complete with all PVC conduit accessories suitable for normal/ flush type switches/sockets/fan regulators with brass screws, cup washers, hylam sheets etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the followings Note:- 1. Rates deemed to be included for GI metal flush sunken box reqd size 2. Flush type Switch, sockets, Bell push measured and paid separately under relevant items). |
| 16 | One light point controlled by one switch |
| 17 | One ceiling/exhaust fan point controlled by one switch |
| 18 | One socket outlet 5 Amps controlled by one switch on same board |
| 19 | One socket outlet 5 amps controlled by one switch on independent board |
| 20 | One bell point controlled by one bell push switch |
| 21 | All as per the description of srl item No 06 above item but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 2.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire. |
| 22 | S&F in repair Switch piano flush type 5/6 Amps single pole one way 230 Volts completeMake: Anchor/Havells/Legrand |
| 23 | S&F in repair Switch piano flush type 15/16 A single pole one way 230 Volts complete Make: Anchor/Havells/Legrand |
| 24 | S&F in repair Socket Outlet 2 in 1, 3 pin 5 Amps flush type 230 Volt complete Make: Anchor/Havells/Legrand |
| 25 | S&F in repair Socket Outlet 2 in 1, 3/6 pin 15 Amp flush type 230 Volts complete Make: Anchor/Havells/Legrand |
| 26 | S&F in repair Bell push, flush type 5 Amps 230 Volts completeMake: Anchor/Havells/Legrand |
| 27 | S&F in repair electronic dimmers flush type 120 watt, 230 Volt complete Make: Anchor/Havells/Legrand |
| 28 | S&F in repair ding dong bell, AC, 230 volts, single pole complete Make: Anchor/Havells/Legrand |
| 29 | S&F in repair lamp holder, 230 volt AC, PVC / Polycarbonate type of angular shape with back plate suitable for batten fittings complete Make: Anchor/Havells/Legrand |
| 30 | S&F in repair ceiling rose, 6 Amps, 250 volts, AC with three terminals and PVC / Polycarbonate insulated body of 50 x 25mm size complete. Make: Anchor/Havells/Legrand |
| 31 | S&F in repair modular switch 6 Amps, one way, one module 240 volts complete Make- Anchor/Havells/Legrand |
| 32 | S&F in repair modular socket, 3 pin 6 Amps,240 volts, 2 module complete Make- Anchor/Havells/Legrand |
| 33 | S&F in repair modular switch 16 A, 1 module,240 volts complete Make- Anchor/Havells/Legrand |
| 34 | S&F in repair modular socket 6/16 A, 5 pin, 2 module, 240 volts complete Make- Anchor/Havells/Legrand |
| 35 | S&F in repair modular Bell push 6 Amps, one module 240 volts complete Make- Anchor/Havells/Legrand |
| 36 | S&F in repair modular fan regulator, step type, 120 W, AC, 230 volts, 2 module complete Make- Anchor/Havells/Legrand |
| 37 | M&L in repair for two single core (submain) PVC insulated cable with 4 sqmm nominal cross sectional area 1100 V,stranded copper conductor, multistranded, and one single core green PVC insulated 2.5 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete |
| 38 | All as per the description of srl item No 23 above item herein before but with 6 sqmm two runs and 4 sqmm one run as earth wire |
| 39 | All as per the description of srl item No 23 above item herein before but with 10 sqmm two runs and 6 sqmm one run as earth wire |
| 40 | S&F in repair MCB DB, single pole and neutral with 200 Amps rated bus bar, 230 volts, glazed, double door type, 4 way IP-43, including connecting all connections of wire to MCBs with proper lugs & making good to the disturbed surface complete. Make- Havells/Indo asian/ Legrand |
| 41 | All as per the description of srl item No 26 way Make- Havells/Indo asian/ Legrand |
| 42 | All as per the description of srl item No 26 way Make- Havells/Indo asian/ Legrand |
| 43 | S&F in repair of factory made distribution box 4 way, AC, TP & neutral metal enclosure, Glazed double dooor, 415 V, AC, concealed type with suitable bus bar, neutral link, earth link suitable complete Make- Havells/Indo asian/ Legrand |
| 44 | S&F in repairs for MCB TPN, 240 Volts, AC, 32 to 63 amps, breaking capacity 10 KA, 'C' curve and connection by using suitable copper lugs complete Make- Havells/Indo asian/ Legrand |
| 45 | S&F in repairs for MCB, DP/SPN, 240 Volts, AC, 40/63 Amps of breaking capacity 10 KA, 'C' curve and connections by using suitable copper lugs complete.Make- Havells/Indo asian/ Legrand |
| 46 | S&F in repairs for MCB SP, 240 Volts, AC, 6 to 32 amps, breaking capacity 10 KA, 'C' curve and connection by using suitable copper lugs complete Make- Havells/Indo asian/ Legrand |
| 47 | Supply and fixing in repair of exhaust fan of strudy engineering plastic complete with louvers shutters, voltage 230V, 50 Hz RPM 1200, copper winding of sweep 250/200mm complete all as specified and directed. . Make: Bajaj/ Crompton Greaves /Havells |
| 48 | S&F in repair LED Batten type fitting for surface/wall mounted 20/22 W,230V,6500K integrated electronic driver completely pre wired, LED 4 feet fitting with polycarbonate housing & integrated electronic driver complete with connector blok, screws , gutties etc.and removing the UNSV fitting and all as specified and directed. Make: Philips/Polycab/Havells |
| 49 | S&F in repair LED Batten type fitting for surface/wall mounted 9/10W,230V,6500K integrated electronic driver completely pre wired, LED 2 feet fitting with polycarbonate housing & integrated electronic driver complete with connector blok, screws , gutties etc.and removing the UNSV fitting and all as specified and directed. Make: Philips/Polycab/Havells |
| 50 | S&F in repair indoor decorative wall light fixture suitable for 10 W LED lamp,230V for soft light ambiance, made up of polycarbonate, spiral B22 base lamp holder used,globe shape, incl LED lamp 10W(warm/CDL type) and remove the UNSV fittings and all as specified and directed. Make- Havells/Polycab/Philips |
| 51 | S&F lighting fixture wall mounted LED bulk head luminaire 9/10W,230V, made of die cast aluminium with opal diffuser IP 65, complete with mounting Brackets & accessories as required with connections and remove the UNSV fittings and all as specified and directed. Make: Philips/Polycab/Havells |
| 52 | S&F in repairs for building security light LED luminaries with low wattage with pressure die cast aluminium housing, with heat resistant thoughened glass & IP 66 protection and 30/45 Watt including taking down old unserviceable one all specified and directed Make: Philips/Polycab/Havells |
| 53 | Material & labour for earthing complete with galvanised mild steel earth plate electrode 60cmx60cmx6mm thick buried vertically in ground (earth pit not less than 2.25meter deep below ground level) with top edge of the plate not less than 1.5meter below normal ground level steel earth plate connected with GI wire 04mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150mm thick around GI earth plate, GI pipe medium grade 20mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6mm dia at the rate of 75mm center to center both way with 12mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40mmx40mmx3mm frame for pit cover including testing on completion complete all as specified and directed. |
| 54 | Supply and fixing of exhaust fan, steel body, AC, single phase, 230 V of size 300mm sweep with blades, frame & louver having 1400 RPM speed, 1600 CMH and including making of holes of suitable size and taking down old exhaust fan and depositing to MES store yard making good to the disturbed surfaces to match the existing complete all as specified and as directed.Make: Orients/Crompton/Havells |
| 55 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 220 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required including connecting up with twin core flat flexible copper conductor cable of suitable size with connector block to ceiling rose complete . and taking down old/unsv fan and deposit in E/M store yard complete all as specified and directedMake: Orients/Crompton/Havells |
| 56 | SSupply and fix electric water heater, storage type 25 ltrs capacity, BEE star rated, vertical type with suitable size of fastner and incl provision and connecting up of SS braided pipe with adapter for inlet and outlet water connection, copper element corrosion resistance antiscaling magnesium anode having adustable knobe for temperature control and inner tank material of superior glass lined tank and outer body material ABS with high pressure with standing capacity upto 8 bar pressure having heating element 2 KW and minium two year warranty on product, minimum three years on heating element complete all as specified and as directed Make: Philips/Polycab/HavellsNote:- Old unserviceable Geysers to be deposited in MES store. |
| 57 | Supply and fixing in repair of desert/Air cooler of body size 25\\"x25\\"x32\\", made out of corrosion resistant, 18 SWG GI sheet duly powder coated paint with 500mm sweep copper wound fan motor kit 180 watt with metallic blade, ISI marked, 1400 RPM, 230 volt AC, tank capacity not less than 100 ltr, incl plastic submersible pumps, electronis fan regulator with P/switch, desert cooler to be fitted with 6mm thick plywood to cover the gap as required size at existing window and old unsv desert cooler depositing in E/M Store yard complete all as directed (Make : JK Classic/Decool/Supreme/Kapsun) |
| 58 | Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete.Make: Philips/Polycab/Havells |
| 59 | Supply and installation of Decorative Ornamental pole as per Lustre item No.Li-8465. Total height of the pole is 4000 mm nominal above the ground. The pole is made out of mild steel tube and cast iron base . Mild steel tube shall pass through the Cast iron pedestal and joined with the mild steel base plate by means of welded joints at the bottom of the pole. Cast Aluminium embellishments are fitted with the help of grub screws . A built in service window is provided to accommodate a 6 amp SP MCB and 32 amp heavy duty connector for mains connections in the bottom part of the pole as shown in attached drawing. The Decorative Pole Shall be machined and Polished properly to give it a smooth Surface. The Decorative is duly pretreated by Shot Blasting Process and painted in U.V. ray resistant P.U. coating in approved color shade. The Coating on the pole Should have a minimum DFT of 90 microns & Should pass a minimum of 300 Salt Spray Hours as per IS or ASTM testing methods. Decorative pole shall be installed at desired location including foundation of the pole by making cement concrete foundation of 1:2:3( 1 cement: 3 course sand : 6 Raded stone aggregate 40mm nominal size) with the help of anchor bolts and 38mm G.I sleeve as required. Make:-Philips/Lustre/Neri/Ligman |
| 60 | Supply and installation of 15 W Tri Colour Led Garden Bollard as per Lustre item No.Li-8173(LIBLF-15). The Luminaire is made out of Cast and extruded aluminium. The Dimensions of the Garden bollard are 100 mm dia and 600mm height. A Translucent PMMA diffuser is Fitted in the Luminaire. Led shall be mounted on the PCB and fitted in the Luminaire .PCB shall be fitted on the suitable Heat Sink for proper Heat Dissipiation. Suitable Constant Current Led driver with power factor 0.95 or more and efficiency 85% or more Shall also be fitted inside the Luminaire. The Surface of the Luminaire Shall be machined and polished Properly to give it a Smooth Surface. The Luminaire shall be duly pretreated and Coated in U.V. ray resistant polyurethane/Polyester in approved color shade. A Two Way Connector Shall be Provided in the Luminaire for the mains Connections. Bollard shall be installed at desired location including foundation of the Same by making cement concrete foundation of 1:2:3( 1 cement: 3 course sand : 6 graded stone aggregate 40mm nominal size) with the help of anchor bolts and G.I sleeve as required. Make:-Philips/Lustre/Neri/Ligman |
| 61 | S&F in repairs of rigid non metalic 25mm dia PVC conduit with all ftgs (tees, bends, elbows, reducers, bell mouth, saddles, pipe hooks) complete. |
| 62 | S&F in repairs of GI flexible conduits 25 mm dia with check nuts and clamps and accessories complete |
| 63 | M&L for PCC (1:3:6) type C1, (using 20mm grade aggregate) as in foundation, for coping, filling andmass concrete with cement plastering fair finishing all as specified and as directed. |
| 64 | M&L in repair for two single core (submain) PVC insulated cable with 1.5 sqmm nominal cross sectional area 1100 V,stranded copper conductor, multistranded, and one single core green PVC insulated 1.5 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete |
| 65 | S&F in repairs for large area flood lighting system LED type IP 66, pressure die cast housing, with heat resistant tempered glass for protection with surge protection system, 100/120 Watt including taking down old unserviceable one all specified and directed. Make: L&T/Philips/Polycab/Havells |
| 66 | Supply and fix in repairs for electronic meters temper proof LCD display with polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH, including old unsv electric meters depositing in E/M Store yard complete all as directed. Make: L&T/Bentex/Schneider Electric |
| 67 | Supply and fix in repairs for electronic meters temper proof LCD display with polycarbonate cover 3 Phase, 415 volt, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH, including old unsv electric meters depositing in E/M Store yard complete all as directed. Make: L&T/Bentex/Schneider Electric |
| 68 | Supply and fix smart fan rod/ anti suicide fan rod 15'' (1.25 feet), load on fan exceeds 22 kg, the smart rod/ pipe opens from its centre and spring in the pipe expands, including existing fan down rod taking down and fixing with new one including old fan down rod depositing in E/M Store yard complete all as directed. Please Enable Macros to View BoQ information |