| 1 | Taking down old unserviceable ACSR conductor including channels, insulators etc complete all as specified and directed. |
| 2 | Material and labour for dismantling and taking down old UNSV concrete pole/Strut any size and removal from site including making good the disturbed surface complete all as specified and directed. |
| 3 | Supply & transporting and erecting of octagonal hot dipped galvanised mild steel pole with grey powder finish 9 meter long complete with top dia of size 70 mm and bottom dia of sie 130 mm including base plate of size 200X200X12 mm, foundation nuts bolts including RCC foundation of suitable size to withstand the said pole and Galvanised mild steel bracket for mounting on top of the pole for fixing of 04 Nos of Flood light complete all as specified and directed by Engr-in-Charge. |
| 4 | Supply and fixing LED flood light 250 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including taking down old UNSV light fitting complete all as specified and as directed by engr-in-charge. |
| 5 | Supply & Laying jointing, testing and commissioning LT XLPE cable, PVC insulated, PVC sheathed armoured LT 1100 volt grades heavy duty with aluminium stranded conductor through pipes, induct, on poles, in trenches etc including taking down complete of following sizes :- |
| 6 | (a) 50 Sqmm, 3.5 core. |
| 7 | (b) 25 Sqmm, 3.5 core |
| 8 | (c) 16 Sqmm, 4 core. |
| 9 | Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in hard/dence soil getting out and levelling of bottom surface to required level all as specified. |
| 10 | Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed. |
| 11 | Removing excavated soil not exc 50 mtr ant depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed. |
| 12 | Supply and lay Double walled corrugated pipe (DWC ), heavy duty 77/63 mm bore for cable protection as a guard pipe including required accessories etc. including taking down PVC pipe any type complete as specified and directed. |
| 13 | M & L for Earthing complete with Gl earth plate, electrode, 600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt, charcoal, garden soil and bentonite powder of adequate quantity and connected to Gl earth strip 25 x 4 mm thick by means of Gl nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of Cl cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with Gl pipe light grade 40 mm dia upto 7.5 from the earth plate electrode & refilling of soil etcCONTD TO 10.01 |
| 14 | Including necessary excavation & earth work in any strata and PCC chamber, including removing old earthing and all as specified and directed by Engr-inCharge.(Note:-Earth strip and protection pipe upto board is included in the rate quoted) |
| 15 | Supply, installation, testing and commissioning of LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequate size for MCBs, housed in a separate bus bar chamber and control wiring adequate size and length CONTD TO 11.01 |
| 16 | outgoing MCCBs shall have extended bus bar links and Panel mounted on 50x50x5mm size MS angle iron frame duly painted including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation design subject to approval of GE as per site requirement. The minimum depth, height, width of panel is 900x 900x450 mm respectively, minimum clearance from ground level is 450mm complete all as specified and directed and comprising of following :- CONTD TO 11.02 |
| 17 | Incoming : - (a) MCCB 100 Amps, FP, 36 KA, Adjustable type, 415 Volts, 50Hz-01 No.Outgoing : - (b) MCCB 63 Amps, FP, 36 KA, Adjustable type, 415 Volts, 50Hz-01 No.(c) MCCB 40 Amps, FP, 16 KA, Adjustable type, 415 Volts, 50Hz-03 Nos. (d) Digital Voltmeter with VSS- 01 Set, Digital Ammeter with CTs & ASS- 01 No. (e) LED phase indication lamps RYB - 01 Set.(f) Aluminium bus bar TPN 100 Amps rating - 01 Set.(g) 3 Phase street light timer - 01 No.Note :- (i) contractor shall provide CPRI certification of the panel. (ii) All items incorporated in panel shall be ISI marked or as per IS specification |
| 18 | Supply ,installatin ,testing and commisioning of 3.15 mmthick CRCA sheet , hutted type cubical factory made outdoor (kiosk) type feeder piller box weather proof outdoor mounting of suitable size , 415 volts ,4 wire AC 50 Hz ,with approved paint with powder coated with front oppening having degee of protection as per IP-52 class protection ,complete factory lock two earth terminal suitable cable gland for all incomming and outgoing and removable nuetral link ,connecting strip /solid conductor brought out to cable chamber brass /copper nut,bolt /washers etc including grouting of feeder piller boc 60 cm above the ground level bt providing 90 cm long angle iron of size 50x50x6 mm welded on the all four corner embedded in PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) up to 30 cm including excavation and earth work and taking down olld existing feeder piller box complete with following accessories .CONTD TO 12.01 |
| 19 | INCOMMING:- (a) MCCB 63 Amps 4 pole breaking capacity 36 ka -01 no OUTGOING :-(b) MCB TPN 32 Amps 4P 16 KA - 04 Nos(c) 3 Phase street light timer - 01 No. Please Enable Macros to View BoQ information |