| 1 | Total of Schedule-A OEM-2223 APPENDIX- 3A PROFORMA FOR STATEMENT OF MINOR DEVIATIONS (Refer Clause C 2.2(d) and C 15.1 of ITT) 1. The following are the particulars of minor deviations from the requirements of the Tender Document: Sr. No Clause Deviations Price reduction for each deviation/s Note : 1. The Tenderer shall indicate price reduction against each deviation in Appendix-3A of BOQ. This price is the price which the tenderer shall reduce from this tender price if deviation(s) is/are accepted by the Employer. 2. Where there is no deviation, the statement should be returned duly signed with an endorsement indicating ‘No Deviations’. In case, Performa of deviations is not submitted or submitted as blank, it will be construed that the tenderer has not proposed any deviations from tender documents. 3. It shall be noted that in case Nil/Zero/NA Price quoted by Tenderer in Appendix-3A then it shall mean that contractor has quoted same price for deviation and undeviation bid. 4. If the tenderer proposes deviations in tender documents, and/or any other terms and conditions of the tender, other than in this Appendix, it will have no effect. Signature of authorized signatory On behalf of Tenderer OEM-2223 S. No. Preamble |
| 2 | The Bill of Quantities shall be read in conjunction with Notice Inviting Tenders, Instructions to Tenderers, General and Special Conditions of Contract, Employer's Requirement and other relevant documents. |
| 3 | BoQ consists of one schedules i.e. Schedule-A |
| 4 | Tenderers shall quote their offer in Indian Rupees (₹) only. Tenderers are required to quote percentage (%) (Excess/Less) in figures in the appropriate highlighted cells in Excel sheet namely 'BoQ1' against given schedules. |
| 5 | The rates and prices to be tendered in the unit Priced Bill of Quantities are for completed and finished items of works and complete in all respect. It will be deemed to include Duties, Taxes, Octroi, Royalty etc., cost of all plants, labour, supervision, materials, transport, all temporary works, erection, maintenance, utility identification, contractor’s profit and establishment/overheads, together with preparation of design and drawings, all general risks, insurance liabilities, compliance of labour laws and obligations set out or implied in the contracts. For taxes and duties refer clause C2.4 & C2.5 of ITT & clause 10 of SCC. |
| 6 | The price offer in the BOQ shall be given without considering any deviation mentioned in Appendix-3 of FOT i.e. price in the box shall be quoted as per tender conditions without any deviation. |
| 7 | If the tenderer fails to quote rates against any item, the tender may be treated as incomplete and non-responsive and shall be rejected. |
| 8 | Errors will be corrected by the employer for any arithmetical errors in computation or summation as per contract conditions. |
| 9 | The Financial Proposal (as per BOQ) shall be uploaded online on the website http://etenders.gov.in/eprocure/app. The rates shall be quoted in the excel file provided in the bid documents. The tenderer shall download the excel file and quote the rates against each highlighted cells in BoQ1. After quoting their rates the excel file shall be uploaded accordingly. The rates shall not be offered/quoted elsewhere in the technical submission/ tender submission. |
| 10 | The actual work executed against all the BOQ as detailed in tender document would be paid as per relevant clause of Employer's Requirement (ER). DELHI METRO RAIL CORPORATION LIMITED BOQ Name of work - Contract No.: OEM-2223 - “POH (Periodic Overhaul) of Power Transformers and other miscellaneous work in Power Transformers of DMRC.” Schedule-A S. No. Description Unit Qty Unit Rate (₹)(excluding GST) Amount (₹)(excluding GST) |
| 11 | Periodic Servicing and Overhauling of EMCO make 220/33KV, 35/50MVA, 3 Phase Auxiliary Transformer. |
| 12 | Periodic Servicing and Overhauling of EMCO make 66/25KV, 30 MVA, Single Phase Traction Transformer. The Work also include Heath Assessment of Aircell and POH of conservator and Thermosyphone filter(including supply of activated alumina). |
| 13 | Periodic Servicing and Overhauling of T&R make 66 KV/33KV, 30/45 MVA, 3 Phase Auxilary Transformer.The work also include POH of Thermosuphone filter(including supply of activated alumina) |
| 14 | Health Assessment of Aircell and POH of Conservator a) Checking of healthiness of Air Cell (Bladder) of transformer conservator without opening the conservator, including isolation of air side system, carrying out air/gas pressure holding test, monitoring of pressure drop and oil level behavior, checking for oil ingress in air line/breather, functional verification through Magnetic Oil Level Gauge response, recording of observations and submission of Air Cell health status report, complete in all respects. Nos 32.0 22000.0 704000.0 b) Periodic Overhauling (POH) of conservator of transformer, to be carried out when Air Cell is found defective under Item No 4(A), including draining of oil to required level through Oil Filtration Machine (OFM) and temporary oil storage tank of requisite capacity, opening and thorough cleaning of conservator, replacement of Air Cell, replacement of gaskets, O-rings, nuts and bolts, checking of air side piping and sealing arrangement, refixing of conservator, oil filling/topping-up, air bleeding, leak testing and restoration to normal operating condition, complete in all respects. Nos 12.0 80000.0 960000.0 c) Supply of Air Cell suitable for transformer conservator complete with all accessories, suitable for specified transformer rating and conservator size, as per relevant standards. (i) For 66kV/33kV, 30/45 MVA 3Phase Transformer Nos 2.0 65000.0 130000.0 (ii) For 66kV/25kV, 30 MVA 1 Phase Transformer Nos 6.0 65000.0 390000.0 (iii) For 66kV/33kV, 40 MVA 3 Phase Transformer Nos 1.0 58000.0 58000.0 (iv) For 66kV/ 33kV, 15 MVA 3Phase Transformer Nos 1.0 50000.0 50000.0 (v) For 132KV/25KV, 30MVA 1 Phase Transformer Nos 1.0 65000.0 65000.0 (vi) For 220 KV/ 25KV, 30MVA 1 Phase Transformer Nos 1.0 65000.0 65000.0 d) Supply of Magnetic Oil Level Gauge (MOG) suitable for above rating transformer conservator, complete with dial, float, magnetic coupling, low oil level alarm contacts, fixing accessories, and mounting hardware, conforming to relevant IS/IEC standards. Nos 6.0 25000.0 150000.0 |
| 15 | Periodic Overhauling (POH) of Thermosyphon Filter Assembly of transformer (other than power transformer covered under Item No. 1 ,2&3) including isolation and draining of oil from filter through Oil Filtration Machine (OFM) and temporary oil storage tank of requisite capacity, opening and thorough cleaning of filter housing, removal of spent activated alumina and supply, loading and replacement with new activated alumina (including its supply), inspection of internals, checking of valves, piping and flanges, replacement of gaskets and fasteners as required, refixing, restoration of oil circulation, leak testing and commissioning, complete in all respects. Total of Schedule-A (excluding GST) 9888000.0 GST@18% 1779840.0 Total of Schedule-A (inclusive of all, GST@18%) 11667840.0 Please Enable Macros to View BoQ information |