| Sl. No. | Item Description |
| 1 | SH-I : SITC of 22kV RMG with Metering Panel |
| 2 | Supply of outdoor 22 KV, 50 HZ, 630 Amps, 26.3 kA SC, outdoor type RMG panel with 2 Nos of LBS (Load Break switch) and one No. CT & PT metering compartment with sealing provision (HT Metering Compartment as per TANGEDCO / TNPDCL (DISCOM) requirements) including CT & PT for RMG as per M/s TANGEDCO / TNPDCL specifications and requirements.i) CT ratio : 100-50/5-5A , Metering : Class 0.2s, Burden : 5 VA & Protection : Class 5P20, Burden :15 VA including suitable class PT as per DISCOM / TNPDCL requirement.ii) Panel shall be Designed & tested in accordance with IEC 62271-200 & 100.iii) Supply and laying of 25x5mm copper flat connecting existing earth pit to RMG panel earthing systems. |
| 3 | Installation, Testing and Commissioning of 22kV HT Outdoor RMG panel with LBS and 1 No of metering compartment (HT Metering Compartment for TANGEDCO) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections , interconnections, suitable size RCC Foundation of minimum 500 mm height from ground level and panel positioning at site complete as per TANGEDCO/TNPDCL specifications/norms etc., including size (5 Mtr [L] X 4 Mtr [W] X 2 Mtr [H]) metal/chain link fencing with all four sides of RMG panel area with lockable gate (1 Mtr [W]) including suitable channel support foundation arragement complete as required. Note: SITC shall be carried out according to TANGEDCO/TNPDCL (DISCOM) norms/ specifications. |
| 4 | SH-II : SITC of 22kV HT VCB Panel |
| 5 | Supply of Indoor Type OEM Fctory Built, floor mounted metal clad, fabricated of 2 mm thick CRCA / Aluzinc sheet, 22 KV, VCB Switch Board panel with 03 Nos. VCBs, free standing extensible on both sides, totally enclosed and electrically interlocked, horizontal drawout on floor, horizontal isolation type confirming to IS / IEC: 62271-100 for breakers & IS / IEC: 62271-200 for panels / switch board, as amended upto date, as per specifications, having capacities as mentioned below, single break, trip free mechanism, electrical and manually charged and closing breaker suitable for use on 22 KV, 3 Phase, 50 Hz AC supply, complete with self contained, electrically interlocked, rack in and rack out mechanism, air insulated and encapsulated copper bus bars, breaker featured with mechanical ON/OFF indicator with hand trip device , spring release coil , shunt trip coil and auxiliary switch of 4 NO + 4 NC and equiped with following switch gears and accessories i/c connections suitable size cable as incomer as well as outgoing feeder inline with tender specifications complete etc. as required.STC 26.3 kA for 3 Sec., Internal ARC test for AFLR 26.3 kA for 1 Sec. as required.The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current as required. |
| 6 | INCOMERi) 01 No. of incomer VCB panel comprising of 22 kV, 630A, Vacuum Circuit Breaker (VCB) ii) Set of 03 Nos. of cast resin insulated dual core dual ratio CT, 22 kV, 75-30/5-5A Core 1: Class 5P10, 10VA, Core 2: Class 0.5, 10VA with digital Ammeter with RS port iii) Set of 03 Nos. Cast resin drawout type PTs 22 kV / 110 V, Class 0.5, 100 VA burden including HT HRC fuse on 22 kV side and MCBs on secondary side protection with digital Voltmeter (Acc. Class 0.5) having selector switches.iv) Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt / tripping coil / closing coil Lockable type, Trip / Neutral / Close (TNC) Switch, Set of ON / OFF / TRIP / Service position / Test position / spring charging indicating, Set of R / Y / B Phase indicating lamps, Clear lamp for trip circuit healthy supply & trip circuit fails, DC control supply healthy & fails, indicating lamps. LED Illumination lamp ON/ OFF with limit switch, space heater with switch 6/16 amps 5 pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti pumping & indication, electrically / Mechanically interlocking etc. as required, 8 window alarm annuciator with windows and buzzer, reset push button for electrical faults incomer panel, complete with FRLS wiring, Terminal Blocks cable-ducts, with protection fuses / MCBs. |
| 7 | v) 01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of max demand load, I; V; Hz; Active, Reactive, Apparent power & Energy; Power factor; % unbalance of current & voltage;, individual harmonics up to 15th level (complying with IEC 61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system. vi) Numerical protection relay, modular design, protection scheme for detecting, indicating and tripping the breaker on circuit faults like(a) Over current & short circuit 51, 51N & one earth fault element in the three phases,(b) residual and three-phase under-voltages / over-voltages,(c) circuit-breaker-failure alarm,(d) Master-Trip and Trip-circuit supervisionvii) ARC flash protection shall be provided: Sensing of any RC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from protection features, along with ARC sensors, fibre cables etc. long with other accessories to complete system. |
| 8 | OUTGOINGS02 Nos. of outgoing VCB panel comprising of 22 kV, 630A, Vacuum Circuit Breaker (VCB) as transformer feeder each comprising of following;i) Set of 03 Nos. of cast resin insulated dual core dual ratio CT, 22 kV, 75-30/5-5A Core 1: Class 5P10, 10VA, Core 2: Class 0.5, 10VA with digital Ammeter with RS port for each breaker.ii) Breaker control switch 240 V AC, spring charging motor 24 V, DC Shunt / tripping coil / closing coil Lockable type, Trip / Neutral / Close (TNC) Switch, Set of ON / OFF / TRIP / Service position / Test position / spring charging indicating, Set of R / Y / B Phase indicating lamps, Clear lamp for trip circuit healthy supply & trip circuit fails, DC control supply healthy & fails, indicating lamps. LED Illumination lamp ON/ OFF with limit switch, space heater with switch 6/16 amps 5 pin switch socket outlet, control terminal as required. Auxiliary contact for Aux. relays for Anti pumping & indication, electrically / Mechanically interlocking etc. as required, 8 window alarm annuciator with windows and buzzer, rest push button for electrical faults incomer panel, complete with FRLS wiring, Terminal Blocks cable-ducts, protection fuses / MCBs for each breaker.iii) 01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of max demand load, I; V; Hz; Active, Reactive, Apparent power & Energy; Power factor; % unbalance of current & voltage;, individual harmonics up to 15th level with RS 485 / Ethernet port and protection MCBs. and required accessories for each breaker. iv) Numerical protection relay, modular design, protection scheme for detecting, indicating and tripping the breaker on circuit faults like (for each breaker) |
| 9 | (a) Over current & short circuit 51, 51N & one earth fault element in the three phases,(b) Three phase under / over voltage protection,(c) Transformer auxciliary protection, OTI / WTI alarm,(d) Master-Trip and Trip-circuit supervisionv) ARC flash protection shall be provided: Sensing of any RC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from protection features, along with ARC sensors, fibre cables etc. long with other accessories to complete system.BUSBAR800 Amp TP, 22 kV Air insulated and encapsulated copper bus bar of suitable size as per panel configuration & 2 Nos. of 25 x 5 mm copper earth strip,BATTERY & BATTERY CHARGER230V, single phase AC system battery charger for 24V DC Batteries, charger with semiconductor / IGBT full wave rectifier with auto / manual float cum boost facility complete with suitable capacity 24V DC, 120 AH sealed maintenance free batteries as per OEM design including one no. distribution board having 32 Amps DP MCB as incomer and 6 Nos. 20/16A DP MCB's (D.C duty) as outgoing complete as required and as per technical specifications. |
| 10 | All The above from (2.01) to (2.05) |
| 11 | Installation, Testing and Commissioning of 22kV HT VCB panel of 1 I/C and 2 O/G's (for iem No. 2.06) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections , interconnections and adjustment in the chequered plate for cable termination and panel positioning at site etc., complete as required. (Shall be as per IS) |
| 12 | SH-III : SITC of 22kV / 0.433 kV, 800 kVA Oil filled type Transformer |
| 13 | Supply of 800 kVA, 22 /0.433 kV , 3 Phase, 50 Hz, Dy11, indoor ONAN type Oil filled transformer , copper wound core type with on load tap changer (OLTC) switch on HV side in steps of 1.25% (tap range +5% to -15%) and remote tap changer control panel(RTCC) with AVR complete, having cable end boxes on HV side suitable for 3X185 Sq.mm. XLPE cable of 22kV grade and provision for 1600A Sandwich bus trunking entry on LV side complete with all accessories i/c first filling of filtered dehydrated oil and conforming to IS 2026 (Part 1 to part 5) and fittings inline with tender specifications complete etc. as required. |
| 14 | Installation, Testing and Commissioning of 800kVA, 22/0.433 KV Oil filled indoor type transformer including provision of 150mm height RCC foundation from floor level for positioning of transformer , necessary \\"C\\" Channel arrangement of size 100x50x6 mm, railing, stopper, earthing connections, interconnections, and providing suitable size, core of control cable from transformer to HT panel, providing suitable size chequered plate at site for cabling and necessary modifications for sandwich bus trunk termination inline with tender specifications complete etc. as required. |
| 15 | SH-IV : SITC of LT Panels |
| 16 | Non Essential Panel: |
| 17 | Fabrication and supply of cubical type TTA LT Panel - designed as per IEC 61439-1 & 2 suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply, made out of 2 mm thick CRCA sheet steel / GI sheet for frame work, doors and covers, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed, the degree of protection of enclosures of IP42 rating in accordance with IEC 60529, Form 4b compartmentalised design or as per design based on IEC, floor mounting, free standing, extensible on both sides i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 1600 Amps capacity FP Aluminium bus bars of high conductivity or as per design based on IEC, DMC/SMC bus bar supports with short circuit withstand capacity of 50 kA for 1Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 50 mm x 5 mm at the rear with 2 nos earth stud, solid connections from main bus bars to switch gears with required size of Aluminium bus bars and control wiring with 1.5 Sq.mm. FRLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half and suitable for indoor operation, complete with all accessories, interconnection, earthing, alignment with the bus ducts etc., as required and comprising of following switch gears. |
| 18 | Incoming:- Two Nos. of 1600 A, 50kA (Ics=Icu), Four Pole, EDO type Moulded case design ACB as INCOMER conforming to IEC 60947-2:2003 as ammended up-to- date with LCD/LED display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases on LCD/LED display, with Microprocessor Based Releases and provided with separate suitable rated Cast Resin CTs with Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, Auxilary power unit, LED Phase Indication Lamps alongwith 2 Amps control MCBs as backup protection, Breaker ON/OFF/TRIP/Spring Charge LED indicating lights alongwith control MCBs as per standard practice, Mechanical/ Electrical Interlocking arrangement between the incomers & bus coupler alongwith interlocking relays, mechanical lock & keys etc. i/c Control MCBs, control terminals & wirings as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 19 | Two(2) Nos. of three phase 4 module Surge Protection Device (SPD) type I + II, having 100KA, 10/350 micro seconds neutral to earth, 50 KA 10/350 micro sec line to neutral, with limiting voltage less than 1.5 KV of modular type at Incomer side of incomer ACBs. |
| 20 | Outgoing:- (i) Two (2) Nos. of 1250 A, 50kA (Ics=Icu), Four Pole, EDO type moulded case design ACB as OUTGOING conforming to IEC 60947-2:2003 as ammended up-to- date with LED/LCD display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases with LED/LCD display, with Microprocessor Based Releases and provided with separate suitable rated Cast Resin CTs with Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, Auxilary power unit, Breaker ON/ OFF/ TRIP/ Spring Charge LED indicating lights alongwith control MCBs as per standard practice etc. i/c Control MCBs, control terminals & wirings etc. as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 21 | (ii) Two (2) Nos. of 630 A, 50 kA, Four Pole, EDO type moulded case design ACB as OUTGOING conforming to IEC 60947-2:2003 as ammended up-to- date with LED/LCD display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases with LED/LCD display, with Microprocessor Based Releases and provided with separate suitable rated Cast Resin CTs with Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, Auxilary power unit, Breaker ON/ OFF/ TRIP/ Spring Charge LED indicating lights alongwith control MCBs as per standard practice etc. i/c Control MCBs, control terminals & wirings etc. as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 22 | (ii) Six (6) Nos. of 400 A, 50 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 23 | (iii) Ten (10) Nos. of 250 A,36 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 24 | (iv) Two (2) Nos. of 100 A,36 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 25 | Bus Couplers:-01 No. 1600 Amps Four Pole horizontal drawout EDO type Modular Air circuit breaker of fault breaking capacity 50 kA (Ics=Icu) fitted with in built metering, interlocked door, automatic safety shutter, Mechanical ON/OFF and service/ test/ isolation position LED indicators and frame earthing contact, conforming to IEC 60947-2:2003 as ammended up-to- date, Breaker ON/ OFF/ TRIP/ Spring Charge LED indicating lights alongwith control MCBs as per standard practice including suitable size adopter chamber in one part to attach with the other part etc., as required. |
| 26 | Busbar:One Set of FP Aluminium Bus Bars of minimum of 1600 A Capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section supports & their spacing etc. for meeting fault level of 50 kA for 1 Sec with adequate size aluminium busbar for interconnection of incomer and outgoing switchgears and 50x5mm copper earth strip etc, as required.Interlocking: Electrical through advance contacts in ACB's (incommer & Bus coupler), PLC system / logic to be provided for operation & monitoring of incomer ACB as per site requirement and mechanical interlocking should be to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidently approaching two supply at one bus section. |
| 27 | All The above from (4.01) to (4.11) |
| 28 | Installation, Testing and Commissioning of LT Non Essential panel (for item no. 4.12) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections, interconnections and adjustment in the chequered plate for cable termination, panel positioning at site and necessary modifications for sandwich bus duct termination etc., complete as required. |
| 29 | Essential Panel : |
| 30 | Fabrication and supply of cubical type TTA LT Panel - designed as per IEC 61439-1 & 2 suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply, made out of 2 mm thick CRCA sheet steel / GI sheet for frame work and covers, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed the degree of protection of enclosures of IP42 rating in accordance with IEC 60529, Form 4b compartmentalised design or as per design based on IEC , floor mounting, free standing, extensible on both sides i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 1600 Amps capacity FP Aluminium bus bars of high conductivity or as per design based on IEC, DMC/SMC bus bar supports with short circuit withstand capacity of 50 kA for 1Sec., bottom base channel of MS section not less than 100 mm x50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 50 mm x 5 mm at the rear with 2 nos earth stud, solid connections from main bus bars to switch gears with required size of Aluminium bus bars and control wiring with 1.5 Sq.mm. FRLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half and suitable for indoor operation, complete with all accessories, interconnection, earthing, alignment with the bus ducts etc., as required and comprising of following switch gears. |
| 31 | Incoming: (TIE & DG Breaker) Two Nos. of (TIE breaker) 1250 A, and Two Nos. of (DG Incoming) 1000 A, 50kA (Ics=Icu), Four Pole, EDO type Moulded case design ACB as INCOMER conforming to IEC 60947-2:2003 as ammended up-to- date with LED/LCD display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases with LED/LCD display, with Microprocessor Based Releases and provided with separate suitable rated Cast Resin CTs with Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, auxilary power unit, LED Phase Indication Lamps, Circuit alongwith 2 Amps control MCBs as backup protection, breaker ON/OFF/TRIP/Spring Charge LED indicating lights alongwith control MCBs as per standard practice, Mechanical/ Electrical Interlocking arrangement between the incomers & bus coupler alongwith interlocking relays, mechanical lock & keys etc. i/c Control MCBs, control terminals & wirings as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 32 | Outgoing:- Four (4) Nos. of 630 A, 50 kA, Four Pole, EDO type moulded case design ACB as OUTGOING conforming to IEC 60947-2:2003 as ammended up-to- date with LED/LCD display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases with LED/LCD display, with Microprocessor Based Releases and provided with separate suitable rated Cast Resin CTs with Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, Auxilary power unit, Breaker ON/ OFF/ TRIP/ Spring Charge LED indicating lights alongwith control MCBs as per standard practice etc. i/c Control MCBs, control terminals & wirings etc. as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 33 | Six (6) Nos. of 400 A, 50 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 34 | Twelve (12) Nos. of 250 A, 36 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 35 | Eight (08) Nos. of 100 A,36 kA, Four Pole MCCB (Ics=Icu) as outgoing with O/L and S/C fault Protection with AdustableThermal and Adustable Magnetic Releases and provided with three nos. Cast resin of suitable rating CTs for digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamps alongwith control MCBs as per standard practice etc. as required. |
| 36 | Two (2) Nos. of Three Phase Surge Protection Device (SPD) having 100kA 10/350 micro seconds neutral to earth, 50 kA 10/350 micro sec line to neutral, with limiting voltage less than 1.5 KV shall be connected on the mains power entry point at the incomers & shall be of modular type. |
| 37 | Bus Couplers:One (1) No 1000 Amps, Four Pole horizontal drawout EDO type Modular Air circuit breaker of fault breaking capacity 50 kA (Ics=Icu) fitted with in built metering, interlocked door, automatic safety shutter, mechanical ON/OFF and service/ test/ isolation position indicators and frame earthing contact, conforming to IEC 60947-2:2003 as ammended up-to- date, Breaker ON/ OFF/ TRIP/ Spring Charge LED indicating lights alongwith control MCBs as per standard practice including suitable size adopter chamber in one part to attach with the other part etc., as required. |
| 38 | Busbar:One Set of FP Aluminium Bus Bars of minimum of 1600 A Capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section supports & their spacing etc. for meeting fault level of 50 kA for 1 Sec with adequate size aluminium busbar for interconnection of incomer and outgoing switchgears and 50x5mm copper earth strip etc, as required. Interlocking : Electrical through advance contacts in ACB's (incommer & Bus coupler), PLC system / logic to be provided for operation & monitoring of incomer ACB as per site requirement and mechanical interlocking should be to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accidently approaching two supply at one bus section. |
| 39 | All The above from (5.01) to (5.09) |
| 40 | Installing, Testing and Commissioning of LT Essential panel (for item no.5.10) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections, interconnections and adjustment in the chequered plate for cable termination, panel positioning at site and necessary modifications for sandwich bus duct termination etc., complete as required. |
| 41 | AMF LT Panel: |
| 42 | Fabrication and Supply of cubical type TTA LT Panel - designed as per IEC 61439-1 & 2 suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply, made out of 2 mm thick CRCA sheet steel/ GI Sheet for frame work and covers, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed the degree of protection of enclosures of IP42 rating in accordance with IEC 60529, Form 4b compartmentalised design or as per design based on IEC, floor mounting, free standing, extensible on both sides i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 1250 Amps capacity FP Aluminium bus bars of high conductivity or as per design based on IEC, DMC/SMC bus bar supports with short circuit withstand capacity of 50 kA for 1Sec., bottom base channel of MS section not less than 100 mm x50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 50mm x 5 mm at the rear with 2 nos earth stud, solid connections from main bus bars to switch gears with required size of Aluminium bus bars and control wiring with 1.5 Sq.mm. FRLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half and suitable for indoor operation, complete with all accessories, interconnection, earthing, alignment with the bus ducts etc., as required and comprising of following switch gears. |
| 43 | (i) One (1) No. 1000 A, 50kA (Ics=Icu), Four Pole, EDO type moulded case design ACB as DG breaker, conforming to IEC 60947-2:2003 as ammended up-to- date with LED/LCD display, inbuilt Metering, Overcurrent, Short circuit & Earth fault Protection with variable current & time delay setting, Instantaneous protection, current demand & phase to neutral voltage on display, % loading of each phases with LED/LCD display, with Microprocessor Based Releases and provided with suitable rated Cast Resin CTs and Digital Multifunction Meter having RS 485 port, shunt trip coil 220 V AC, LED Phase Indication Lamps alongwith 2 Amps control MCBs as backup protection, Breaker ON/OFF/TRIP/Spring Charge LED indicating lamps alongwith control MCBs as per standard practice, Electrical Interlocking arrangement between the EB & DG Incomers alongwith interlocking relays etc. i/c Control MCBs, control terminals & wirings as required. [ACB shall have communicating facility via RS485 port modbus protocol providing status of ACBs & shall also be capable of Monitoring the ACB]. |
| 44 | (ii) 24 V Battery Charger consisting of transformer, rectifier, DC Ammeter, DC Volt meter and charge rate selector switch with position ON / Trickle/ OFF/ Boost for charging capacity of 24 Volts SMF battery with suitable AH etc. complete as required. (iii) One No. Display Temperatue Scanner for BTD/RTD.(iv) One Set of Timers and contactors/AMF Relay / AMF controller/module for Start with condition to take the load with in 15 Sec. in 3 Attempts/ Stop/ Delay time of DG Set with Selector Switch for Time Delay, Contactors for Auto/ Manual/ Interlock/Time Delay and Engine protection PCB & accessories etc. as required.(v) One Set of Selector Switches for Auto/ Manual/ Test/ Off Operation and One set of push button for Start / Stop / Reset etc.(vi) PLC system for operation and monitoring of 2 nos. of DG set including interlinking with DG Controller, Programming, operation of II set in case of I set fails to start and vice versa etc., as required with mains supply feeder. (One Common PLC will be installed for both AMF panel)(vii) One Set of LED Display for Performance of DG Set(viii) One set of Multi Channel Annunciation with Hooter Alarm for the Abnormality of DG Set(ix) All accessories such as fuses, auxiliary contactors, auxiliary switches, LVMs, multi core armoured copper control cables from DG set to AMF panel, LT Essential panel etc. as required.Complete all as above |
| 45 | All The above from (6.01) to (6.03) |
| 46 | Installing, Testing and Commissioning of AMF panel (for item No. 6.04) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections, interconnections and adjustment in the chequered plate for cable termination, necessary modifications for sandwich bus trunk termination and panel positioning at site etc., complete as required. |
| 47 | HYBRID HARMONIC Cum AUTOMATIC POWER FACTOR CONTROL PANEL |
| 48 | Fabrication and Supply of HYBRID HARMONIC Cum AUTOMATIC POWER FACTOR CONTROL PANEL (100 A Plus 125 KVAR) to achieve PF > 0.99 Lag and TDDI / THDV Values within IEEE Recommended Limits suitable to operate on 415 V, 3 Phase, 4 wire 50 Hz AC supply, depth not less than 900 mm, made out of 2 mm thick CRCA sheet steel/GI sheet for frame work, doors and covers, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed with the degree of protection of enclosures of IP42 Rating in accordance with IEC 60529. The system shall be of design as per IS 16636. Compartmentalised design, floor mounting, free standing, i/c cleaning and finishing complete with 7 tank process for powder coating in approved shade, having 400 Amps capacity FP Aluminium bus bars of high conductivity, DMC/SMC bus bar supports with short circuit withstand capacity of 36 KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel with a common Copper earth bar of size 50 mm x 5 mm with 2 Nos. earth stud at rear, solid bus link connections from main bus bars to switch gears and from adopter box of busduct to respective Switch gears as applicable with required size of Aluminium bus bars and wiring with 1.5 Sq.mm. FRLSH PVC insulated copper conductor cable for potential sensing and wiring with 2.5 Sq.mm. FRLSH PVC insulated copper conductor Control Cable for current carrying, cable alleys, cable gland plates suitable for indoor operation, complete with all accessories, fabrication done in transportable sections, interconnection, earthing, alignment with the bus ducts etc., as required. DAPFC shall have Auto/Manual selection sheme with selector switch etc. The switching device of the active compensation system shall be IGBT based. The active compensation system should filter harmonics from 2nd to 51th individual harmonic order and shall be selectable for the entire range. The active compensation system should have feature to improve PF correction as well. The Panel is comprising of following switch gears as required. |
| 49 | Incomer: One No. 400 A, 36KA, Four Pole MCCB (Ics=Icu) as Incomer with inbuilt O/L, S/C and earth fault Protection with microprocessor based releases and provided with 400/5A, CL-1, 15VA, three nos.Cast Resin CTs with Digital Multifunction Meter having RS 485 port, LED Phase Indication Lamps along with suitable rating control MCBs as backup protection, MCCB ON/ OFF/ TRIP LED indicating lights along with control MCBs as per standard practice etc., i/c control terminals & wirings etc., as required. |
| 50 | Active Filter PartOne No. 200 A, 36 KA, Four Pole MCCB (Ics=Icu) as Outgoing with inbuilt O/L, S/C and Earth fault Protection with microprocessor based releases, provided with One No. 75A AHF Module of IGBT Type, ON/OFF/TRIP LED indication lamp along with control MCBs as per Standard practice etc., as required.One No. HMI Hybrid PQ Controller capable to integrate/isolate the active and passive Components, provided with 7 Inch LCD Touch Screen to display all Parameters like Currents, Fundamental Current, iTHD, iTDD, Aunb, Voltages, Vthd, kW, kVAr, kVA, PF, dPF, Filter Current, Filter Loading (%), Stack Temperature, Ambient Temperature, Filter Run time, System Runtime etc., provision of a proper exportable fault log, able to log > 2,00,000 time stamped events and faults in memory, Capable of displaying individual harmonics for currents and voltages upto 51st order, Capable of simultaneously displaying current and voltage waveforms etc., as required.Cooling Fans as per Design and suitable for 230 V, 1 Phase Operation as required. |
| 51 | Detuned Capacitor Bank (Passive) PartOne No. 8 Steps APFC Relay with three nos. VA Sensors of (600/300/5/5) Amps Dual Core Resin Cast CT at appropriate Transformer's Secondary Circuit i/c supply and laying of 7C X 2.5 Sq.mm. PVC insulated PVC sheathed armoured, copper conductor Control Cabling from LT Panel Incoming / Transformer Secondary to APFC Panel (for length up-to 25 Mtr), including providing Auto/Manual Facility as required. |
| 52 | Four No. 25 KVAR detuned APFC compartment consist of 63 A, 16 KA, TP MCCB (Ics=Icu) with inbuilt O/L and S/C fault Protection with TM Release, ON/OFF/TRIP LED indication lamp along with control MCBs, 25KVAR @ 415V (33.1KVAR @ 525V), TP, MPP type with Al. Round Enclosure, heavy duty Power Capacitor with suitable rating TP capacitor duty contactor, 25KVAR, 415V, TP, Copper Wound 7% Detuned Reactor, ON/OFF LED indication lamps, Start/Stop push buttons, 25 sqmm Interconnecting PVC Insulated FR Copper Flexi-Wires, control MCBs etc, as required. |
| 53 | Two No. 10 KVAR detuned APFC compartment consist of 32 A, 16 KA, TP MCCB (Ics=Icu) with inbuilt O/L and S/C fault Protection with TM Release, ON/OFF/TRIP LED indication lamp along with control MCBs, 10KVAR @ 415V (12.65KVAR @ 525V), TP, MPP type with Al. Round Enclosure, heavy duty Power Capacitor with suitable rating TP capacitor duty contactor, 10KVAR, 415V, TP, Copper Wound 7% Detuned Reactor, ON/OFF LED indication lamps, Start/Stop push buttons, 16 sqmm Interconnecting PVC Insulated FR Copper Flexi-Wires, control MCBs etc, as required. |
| 54 | One No. 5 KVAR detuned APFC compartment consist of 16 A, 16 KA, TP MCCB (Ics=Icu) with inbuilt O/L and S/C fault Protection with TM Release, ON/OFF/TRIP LED indication lamp along with control MCBs, 5KVAR @ 415V (6.28KVAR @ 525V), TP, MPP type with Al. Round Enclosure, heavy duty Power Capacitor with suitable rating TP capacitor duty contactor, 5KVAR, 415V, TP, Copper Wound 7% Detuned Reactor, ON/OFF LED indication lamps, Start/Stop push buttons, 10 sqmm Interconnecting PVC Insulated FR Copper Flexi-Wires, control MCBs etc, as required. |
| 55 | Bus Bar: One Set of FP Aluminium Bus Bars of minimum of 400 A Capacity with heat shrinkable coloured epoxy sleeves and i/c providing and fixing of DMC/SMC bus bar supports meeting fault level of 36 KA for 1 Sec with adequate size Aluminium busbars for interconnection of incomer and outgoing switchgears etc., as required. Each vertical compartment shall have Illumination Lamp, Door Limit switch, Exhaust Fan & Thermostat. (Note: Price inclusive of Frieght charges.All accessories such as 3 CT sensing APFC Relay, auxiliary contactors, auxiliary switches, Auto/Manual selector swithes, ON/OFF push buttons, Phase and ON, OFF & Trip Indication lamps, control MCBs, rotary handles, phase seperators, spreaders etc., as required. |
| 56 | All The above from (7.01) to (7.09) |
| 57 | Installing, Testing and Commissioning of HYBRID HARMONIC Cum AUTOMATIC POWER FACTOR CONTROL PANEL (100 A Plus 125 KVAR) capacity APFC panel (Item No. 7.09 ) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections, interconnections and adjustment in the chequered plate for cable termination, necessary modifications for sandwich bus trunk termination and panel positioning at site etc., complete as required. |
| 58 | UPS / CCR Supply Panel : |
| 59 | Fabrication and supply of cubical type TTA LT Panel - designed as per IEC 61439-1 & 2 suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply, made out of 2 mm thick CRCA sheet steel / GI sheet for frame work and covers, 3 mm thick for gland plates, dust tight, vermin proof, totally enclosed the degree of protection of enclosures of IP42 rating in accordance with IEC 60529, Form 4b compartmentalised design or as per design based on IEC , floor mounting, free standing, extensible on both sides i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 400 Amps capacity FP Aluminium bus bars of high conductivity or as per design based on IEC, DMC/SMC bus bar supports with short circuit withstand capacity of 50 kA for 1Sec., bottom base channel of MS section not less than 100 mm x50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 50 mm x 5 mm at the rear with 2 nos earth stud, solid connections from main bus bars to switch gears with required size of Aluminium bus bars and control wiring with 1.5 Sq.mm. FRLS PVC insulated copper conductor cable, cable alleys, cable gland plates in two half and suitable for indoor operation, complete with all accessories, interconnection, earthing, alignment with the bus ducts etc., as required and comprising of following switch gears. |
| 60 | Incoming: Two Nos. of 250 A, 50 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. Two Nos. of change over power contactors of suitable ratings on the incomer side for auto change over with Auto/Manual selector switch including accessories etc., complete as required. |
| 61 | Outgoing:- Four (04) Nos. of 125 A, 36 kA, Four Pole MCCB (Ics=Icu) as outgoing with inbuilt Overcurrent, Short Ciruit and Earth Fault Protection with microprocessor based release and provided with three nos. Cast resin CTs of suitable rating with digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamp along with control MCBs as per Strandard practice etc. as required. |
| 62 | Ten (10) Nos. of 100 A,36 kA, Four Pole MCCB (Ics=Icu) as outgoing with O/L and S/C fault Protection with AdustableThermal and Adustable Magnetic Releases and provided with three nos. Cast resin of suitable rating CTs for digital Multifunction Meter having RS 485 port, ON/OFF/TRIP LED indication lamps alongwith control MCBs as per standard practice etc. as required. |
| 63 | Busbar:One Set of FP Aluminium Bus Bars of minimum of 400 A Capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section supports & their spacing etc. for meeting fault level of 50 kA for 1 Sec with adequate size aluminium busbar for interconnection of incomer and outgoing switchgears and 50x5mm copper earth strip etc, as required. Interlocking : Electrical / Mechnical interlock for Incomer I & II to ensure that only one supply is available at a time on bus and to eliminate any possibility of accidently approaching two supply at bus section. |
| 64 | All The above from (8.01) to (8.05) |
| 65 | Installing, Testing and Commissioning of UPS / CCR panel (for item no. 8.06) including provision of necessary \\"C\\" Channel arrangement of size 100x50x6 mm, earthing connections, interconnections and adjustment in the chequered plate for cable termination, panel positioning at site and necessary modifications for sandwich bus duct termination etc., complete as required. |
| 66 | SH-V : SITC of DG Sets |
| 67 | Supply of 500kVA Prime Duty Diesel Generating set with acoustic, complying CPCB-IV +Emission Norms as amended upto date comprising of following requirements. (i) 01 No. alternator suitable for generating 500 kVA, 415 V, 3 Phase, 50 Hz, 0.8 PF, 1500 RPM, self ventilated, self regulated, self excited with brushless type conforming to IS 4722 / IS 15999, IS 8528, radiator cooled, class-H insulation for windings with suitable size termination box / Bus Duct entry etc. as required.(ii) 01 No. multi cylinder engine, 4 stroke, turbo charged diesel engine developing suitable BHP at 1500 RPM suitable for above alternator and complete with all accessories such as base frame, AVM Pads, battery [12/24 volts, 180 Ah], all types of filters, coupling, starter, residential silencer, exhaust piping (with Thermal insullation and aluminium cladding) automatic electronic speed governing mechanism, control panel, compact radiator etc. and conforming to relevant IS with up to date amendments as specified and as required. The engine will be fitted complete with all the required accessories. (iii) 1 No. Daily Service Fuel Tank of Capacity 990 Liters., fabricated out of 3 mm thick M.S sheet complete with all standard accessories, suitable height MS support structure and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. complete with valves, level indications and accessories as required as per specifications.(iv) Integrated Microprocessor based Generator Set Control System providing Digital Voltage Regulation, Engine Protection, Alternator Protection, Isochronous Governing, AMF Function, Battery Monitoring, Operator Interface, Communication Interface etc., as specified and as required. |
| 68 | (v) Customised Compact Modular Type Tested Acoustic Enclosure suitable for the above DG Set to limit the Noise Level to 75 dB (A) at a distance of 1 Mtr. from the Enclosure, made out of CRCA sheet of 1.6 mm thickness for the Outside Cover and Doors and for Inside Cover with 0.8 mm thick perforated GI Sheet, Louvers of thickness 1.6 mm CRCA Sheet for Fresh Air and Hot Air, Powder coated after Seven Tank Process, Neoprene Rubber Gasket and heavy duty SS locks with SS Hinges, Acoustic made up of high quality rock wool/glass wool/ mineral wool as per OEM design, Base Frame of suitable Size Channel, provision to accommodate Batteries, Support for Silencers, provided with 4 Nos. LED Tube light Fittings of 2 feet and Switches etc. as specified and as required.(vi) Supply of Exhaust gas piping for above DG of suitable dia. welded black MS, B class pipe confirming to IS:3589 cut to required lengths and with necessary bends, supports and clamps, bellows, residential silencer, providing and fixing of insulation of exhaust pipe / system with mineral wool/Rockwool 50 mm thick, wire mesh & aluminium cladding of minimum thickness of 0.6 mm etc., upto DG exhaust stack as required height meeting CPWD/PCB/AAI Specifications. |
| 69 | (vii) Supply of G.S.S square/rectangular duct for dissipation of hot air to outside for above DG set made out of GI sheet thichness as specified in technical specification complete with gaskets, elbows, splitters, vanes, MS angle iron supports with threaded rod hanging arrangement etc. as per specifications to meet site requirement etc. as required.(viii) Complaint to latest emission norms of MoEF/CPCB (i.e., CPCB-IV & Emission Compliant) as specified and as required.(ix) Cost of supply of consumables, lubricant, 'B' check kit for one year DLP period is included. (x) Performing 13 Hrs Load test for the DG set at factory, arranged with suitable load equipmentat the time of predelivery inspection along with other routine tests as mentioned in the DG set specifications. |
| 70 | All The above from (9.01) to (9.03) |
| 71 | Installation, Testing and Commissioning of 500 kVA DG set (as mentined in 9.04) including positioning of DG set, including laying of fuel pipe lines, fixing of exhaust piping with required supporting arrangement upto DG exhaust stack, fixing of hot air duct with proper supports as per Technical specifications, supply and laying of control cable, earthing connections, interconnections and adjustment in the chequered plate for cable termination, necessary modifications for sandwich bus trunk termination and panel positioning at site etc., performing 06 Hrs Load test for the DG set at site with available load, laying and termination of control cables for engine control panel, batteries, alternator Sensor scanner to AMF LT panel, LT main panel etc. complete as required. inline with tender specifications complete as required. (Note: Civil foundation works for DG set will be done by AAI) |
| 72 | Providing & Installation of Lattice type MS support structure with suitable RCC foundation with foundation bolts & Nuts as per template for fixing of DG exhaust fume pipes of above 2 Nos DG sets (300mm dia 'B' Class MS pipe or as recommended by OEM (cost of exhaust pipe for 2 Dg set is included in Item No. 5.01) with necessary accessories like flanges, gaskets, bolts, nuts and washers including fixing of thermal Cladding with Mineral wool Wrapping 50mm Thickness with Chicken Mesh and 24 SWG Aluminium Sheet Including Bends and Supply & Installation of SS expanison bellow 8\\" dia with matching flanges, gaskets and Bolt nuts) for bottom support along horizontal and vertical runs upto the height supports with required platforms and ladder arrangement for all erection works like Exhaust Piping, Silencers, lattice supports etc., with MS Angles / Channels, Anchor fasteners, etc., including cutting, welding, painting (applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by E-I-C/as per CPCB norms) etc., Supply and fixing of lightning protection (LA Earthing strip will be paid seperately) and obstruction light with connections also included in the scope of work. Design of DG exhaust stack supporting system shall be suitable to the exhaust pipe height as per CPCB norms and duly vetted by OEM/reputed Govt. Institute/Charted Engineer shall be submitted inline with tender specifications, also to get the approval from the E-I-C before execution etc. as required. Work include all necessary civil works including RCC foundation. (Note: Height of lattice tower is 15 Mtrs is considered for 1 JOB) |
| 73 | SH-VI : SITC of Sandwich Bus duct |
| 74 | Supplying, installing by suspension on ceiling/along the wall, testing and commissioning of following capacity Sandwich Type Bus duct for use on 3 phase 4 wire 415 V, 50Hz A.C. supply with metal clad enclosure having IP- rating as per followings and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos. aluminium bus bars having current density as per standards at nominal current rating, necessary joints, elbow joints & expansion joints and bends, adopter box and copper flexible (Braided wire type) for joints, continuous earthing with 2 Nos. aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.Note: The bus trunking shall be measured along the length of enclosure. The Aluminium strips which will go inside L.T. panels & end termination boxes of transformers shall not be taken into measurement of bus trunking quantity. |
| 75 | 800 Amp. Indoor (IP-54) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip. |
| 76 | 1000 Amp. Indoor (IP-54) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip. |
| 77 | 1250 Amp. Indoor (IP-54) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip. |
| 78 | 1600 Amp. Indoor (IP-54) (4P) Aluminium bus trunking having Neutral =100% + 2 nos. of 50x6 mm external Aluminium earth strip. |
| 79 | SH-VII : Supply and Laying of HT Cables |
| 80 | Supply of 3C x 120 Sq.mm compact circular stranded Al conductor provided with conductor screening of semi-conducting compound XLPE insulated provided with insulation screening over individual cores, consisting of extruded semi-conducting compound followed by lapped semi-conducting copper tapes, cores laid together with suitable filters, in the interscripes covered with inner sheath by extrusion, galvanized flat steel strip armoured and overall PVC sheathed cable, suitable for 22 kV (E) System conforming to IS 7098 (Part-II) 2011 as amended upto date etc., as required. |
| 81 | Supply of 3C x 185 Sq.mm compact circular stranded Al conductor provided with conductor screening of semi-conducting compound XLPE insulated provided with insulation screening over individual cores, consisting of extruded semi-conducting compound followed by lapped semi-conducting copper tapes, cores laid together with suitable filters, in the interscripes covered with inner sheath by extrusion, galvanized flat steel strip armoured and overall PVC sheathed cable, suitable for 22 kV (E) System conforming to IS 7098 (Part-II) 2011 as amended upto date etc., as required. |
| 82 | Laying of one number XLPE insulated and PVC sheathed power cable of 22 KV grade of upto 120 Sq.mm size in the existing masonry open duct as required. |
| 83 | Laying of one number XLPE insulated and PVC sheathed power cable of 22 KV grade of size exceeding 120 sqmm but not exceeding 400 sqmm in the existing masonry open duct as required. |
| 84 | Laying of one number XLPE insulated and PVC sheathed power cable of 22 KV grade of upto 120 sqmm size in the existing RCC/HUME/METAL pipe/HDPE pipe as required. |
| 85 | Laying of one number XLPE insulated and PVC sheathed power cable of 22 KV grade of size exceeding 120 sqmm but not exceeding 400 sqmm in the existing RCC/HUME/METAL pipe/HDPE pipe as required. |
| 86 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 3C x 120 Sq.mm size of XLPE aluminium conductor cable of 22 KV grade as required. |
| 87 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 3C x 120 Sq.mm size of XLPE aluminium conductor cable of 22 KV grade as required. |
| 88 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 3C x 185 Sq.mm size of XLPE aluminium conductor cable of 22 KV grade as required. |
| 89 | SH-VIII : Supply of LT Cables, Light fixtures and Fans |
| 90 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required.3C x 10 Sq.mm |
| 91 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required.4C x 25 Sq.mm |
| 92 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required.4C x 50 Sq.mm |
| 93 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required.3.5C x 185 Sq.mm |
| 94 | Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-I) with upto date amendments as required.3.5C x 240 Sq.mm |
| 95 | Supply of 61 core 2.5 sqmm copper conductor cable of 1.1 KV grade, PVC/XLPE insulated PVC sheathed armoured cable confirming to IS:1554 I & IS: 7098-I with up to date amendments complete as required. |
| 96 | Supply of 6 core 2.5 sqmm copper conductor cable of 1.1 KV grade, PVC/XLPE insulated PVC sheathed armoured cable confirming to IS:1554 I & IS: 7098-I with up to date amendments complete as required. |
| 97 | Supply of Airfield Lighting (AFL) 5 KV grade, Single Core, Copper Conductor, Copper shielded, XLPE insulated, Unarmoured Underground Cable for airfield lighting cable, confirming to specification as specified in technical specification of the following sizes as required. 16 sq. mm. |
| 98 | Supply of Airfield Lighting (AFL) 5 KV grade, Single Core, Copper Conductor, Copper shielded, XLPE insulated, Unarmoured Underground Cable for airfield lighting cable, confirming to specification as specified in technical specification of the following sizes as required. 6 sq.mm. |
| 99 | Supply of 10 pair, 0.50 mm size, XLPE insulated PE outer sheathed armoured copper conductor Tele-communication cable, twised pairs stranded together in concetric layer so as to minimize cross talk and warpped with melinex / PVC tape, as per relevant IS with upto date amendment and generally conforming to ITD and ITI specifications. |
| 100 | Supply of 40 W surface/ ceilling / wall mounted 4 feet LED Tube Light Fixture with aluminium housing and integrated electronic driver complete with all accesories having minimum lumen output of 2000lm, CCT 5700 k ± 355 k suitable to operate on 230 V single phase, 50Hz AC supply in line with tender specifications with 5 years warrenty complete as required. |
| 101 | Supply of 45 W Street Light luminaries having, minimum lumen output of 7700lm , system efficacy not less than 110 lumen/watt, suitable optics for uniform light distribution, integral control driver with minimum 4kV surge suppressor, fitting made up of high pressure die cast aluminium/ standard alloy suitable thermal management arrangement, toughened glass with IP65 protection, suitable to operate on 230V, 50 Hz, single phase AC supply, hook/eye bolt for mounting the fixture inline with technical specifications attached with 5 years warrenty complete as required. |
| 102 | Supply of 1200 mm sweep, BEE 5 star rated ceiling fans suitable for 230 volt 50 HZ Supply, with standard down rod and other accessories with out regulator etc. as required. |
| 103 | Supply of 450 mm dia single phase 1400 RPM heavy duty Exhaust fan (ISI marked) with louver including all accessories etc as required. |
| 104 | SH-IX : Internal and External Electrification |
| 105 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed steel conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 106 | Wiring for twin control light point with 1.5sq.mm FRLS PVC insulated copper conductor single core cable in recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 107 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required.Group C |
| 108 | Supplying and fixing of following sizes of steel conduit along with accessories in recess, or cutting the wall and making good the same in case of recessed conduit complete as required.32 mm |
| 109 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in recessed steel conduit as required.2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 110 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in recessed steel conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 111 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in recessed steel conduit as required.2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 112 | Supplying and fixing following size/modules, Gl box along with modular base & cover plate for modular switches in recess etc., as required.3 Module |
| 113 | Supplying and fixing following size/modules, Gl box along with modular base & cover plate for modular switches in recess etc., as required.6 Module |
| 114 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 115 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 A switch |
| 116 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 117 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 5/15 A socket outlet |
| 118 | Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone Socket |
| 119 | Supplying and fixing of 8 way (8 + 24), Double door, horizontal type three pole and neutral, IP43, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc., as required. (Horizontal TPN DB) |
| 120 | Supply and fixing of 12 way, Double door, single pole and neutral, sheet steel, MCB distribution board, 240 volts on recessed complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc., as required. (SPN DB) |
| 121 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for 8 Way Double door, triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 122 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following Way Double door, SPN, sheet steel, MCB distribution board,240 V on recessed, complete with testing and commissioning etc.as required.12 way, Double door |
| 123 | Supplying and fixing 5 A to 32 A rating, 240 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc., as required.Single pole |
| 124 | Supplying and fixing 5 A to 32 A rating, 240 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc., as required.Double Pole |
| 125 | Supplying and fixing following rating, four pole, 415 V, MCB in the existing MCB DB complete with connections, testing and commissioning etc., as required.63A |
| 126 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc., as required.63 A |
| 127 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 128 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per drawing attached in technical specification for circular box type fan clamp. |
| 129 | Installation, testing and commissioning of pre-wired LED fittings of all types, complete with all accessories and tube etc., directly on ceiling/wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable through a flexible hose and earthing etc., as required. |
| 130 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable through a flexible hose etc. as required. |
| 131 | Installation, testing & commisioning of 45W LED street light fixtures on wall by providing suitable GI arm bracket of 1.5 Mtr length and minimum thickness of 3 mm, including connection with 1.5/2.5 sq. mm FRLS PVC insulated, copper conductor, single core cable through a flexible hose suitable for outdoor applications and earthing etc., complete as required. |
| 132 | Installation of 450mm dia exhaust fan with louver in the existing opening, including making good the damage, connection, testing, commissioning with 1.5 sqmm flexible FRLS cable through a flexible hose etc., as required. (Upto 450 mm Sweep) |
| 133 | Supplying and laying of \\"B\\" Class G.I pipe of following dia, i/c excavation of bituminous/ concrete road/ pavement, excavation of Soil to maximum depth of 1.2 Mtrs from ground refilling the Soil and with CC of ratio 1:3:6 on top for 0.15 Mtrs after laying Pipe and plastering, making good the same etc., as required.80 mm |
| 134 | Supplying and laying of \\"B\\" Class G.I pipe of following dia, i/c excavation of bituminous/ concrete road/ pavement, excavation of Soil to maximum depth of 1.2 Mtrs from ground refilling the Soil and with CC of ratio 1:3:6 on top for 0.15 Mtrs after laying Pipe and plastering, making good the same etc., as required.150 mm |
| 135 | Supplying and laying of following size OD HDPE Pipe of PE 80 PN 6 ISI Marked along with all accessories conforming to IS 4984:2016 complete with fitting and cutting, jointing etc., direct in ground (0.75 Mtr below the ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., as required.40 mm |
| 136 | Supplying and laying of following size OD HDPE Pipe of PE 80 PN 6 ISI Marked along with all accessories conforming to IS 4984:2016 complete with fitting and cutting, jointing etc., direct in ground (0.75 Mtr below the ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., as required.50 mm |
| 137 | Supplying and laying of following size OD HDPE Pipe of PE 80 PN 6 ISI Marked along with all accessories conforming to IS 4984:2016 complete with fitting and cutting, jointing etc., direct in ground (0.75 Mtr below the ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., as required.75 mm |
| 138 | Supplying and laying of following size OD HDPE Pipe of PE 80 PN 6 ISI Marked along with all accessories conforming to IS 4984:2016 complete with fitting and cutting, jointing etc., direct in ground (0.75 Mtr below the ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., as required.110 mm |
| 139 | Supply of following sizes 5 KV grade dry type Plug and Receptacle of type I, class 'B' primary connector kit with field attachment and suitable for 5 KV grade single core copper conductor, copper braided, XLPE insulated PE outer sheathed shielded cable, complete as required confirming to the technical specification.16 sq. mm. |
| 140 | Supply of following sizes 5 KV grade dry type Plug and Receptacle of type I, class 'B' primary connector kit with field attachment and suitable for 5 KV grade single core copper conductor, copper braided, XLPE insulated PE outer sheathed shielded cable, complete as required confirming to the technical specification.6 sq.mm |
| 141 | Making field connections by crimping of following sizes Plug and Receptacle with suitable existing size single core PVC cu. Conductor cable of 5 KV grade Airfield cable including filling the gap with water sealent material applying PVC insulation tape etc. complete as required.6 sqmm |
| 142 | Making field connections by crimping of following sizes Plug and Receptacle with suitable existing size single core PVC cu. Conductor cable of 5 KV grade Airfield cable including filling the gap with water sealent material applying PVC insulation tape etc. complete as required.16 sqmm |
| 143 | Constructing Masonry Chamber 180 cm x 180 cm x 100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand), with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :18.33.1 with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 complete as required. |
| 144 | Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars / spigot jointed with stiff mixture of cement morter in the proportion of 1:2 (1 cement : 2 sand) including testing of joints etc. complete as required.450 mm dia RCC pipes |
| 145 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL / HDPE pipe as required.Upto 35 Sq.mm |
| 146 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL / HDPE pipe as required.Above 35 sq. mm and upto 95 sq. mm |
| 147 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL / HDPE pipe as required.Above 95 sq. mm and upto 185 sq. mm |
| 148 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL / HDPE pipe as required.Above 185 sq. mm and upto 400 sq. mm |
| 149 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 Sq.mm |
| 150 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 35 sq. mm and upto 95 sq. mm |
| 151 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 95 sq. mm and upto 185 sq. mm |
| 152 | Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mm |
| 153 | Laying of one number Single core PVC /XLPE insulated and PVC/PE sheathed cable of 5 KV grade of following size in the existing RCC/HUME/ METAL / HDPE pipe as required.Upto 16 Sq.mm |
| 154 | Laying of one number Single core PVC /XLPE insulated and PVC/PE sheathed cable of 5 KV grade of following size in the existing masonry open duct as required.Upto 16 Sq.mm |
| 155 | Laying of one number control cables / Telephone cables, PVC /XLPE insulated and PVC/PE sheathed copper upto 100 core / 10 pair twisted cable in the existing RCC/HUME/ METAL / HDPE pipe as required. |
| 156 | Laying of one number control cables / Telephone cables, PVC /XLPE insulated and PVC/PE sheathed copper upto 100 core / 10 pair twisted cable in the existing masonry open duct as required. |
| 157 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays including necessary bends, accessories with perrforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness |
| 158 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays including necessary bends, accessories with perrforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.450 mm width X 50 mm depth X 2.0 mm thickness |
| 159 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required.3C x 10 Sq.mm |
| 160 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required.3.5C x 185 Sq.mm |
| 161 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required.3.5C x 240 Sq.mm |
| 162 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required.4C x 25 Sq.mm |
| 163 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of XLPE insulated and PVC sheathed aluminium conductor cable of 1.1 KV grade as required.4C x 50 Sq.mm |
| 164 | Supply and fixing of nominal 2.5 mm thick (Width 1 Mtr) PVC synthetic, electric insulated mats conforming to IS 15652-2006 having Dielectric strength of 45 KV, no adverse effect of mineral oil, high insulation resistance (Minimum 1,00,000 M Ω on wet condition with 5 KV meggar) etc., as required. |
| 165 | Supply and fixing of nominal 2.0 mm thick (Width 1 Mtr) PVC synthetic, electric insulated mats conforming to IS 15652-2006 having Dielectric strength of 45 KV, no adverse effect of mineral oil, high insulation resistance (Minimum 1,00,000 M Ω on wet condition with 5 KV meggar) etc., as required. |
| 166 | Supply and Fixing of 10 mm thick SMC chequered plates including provision of 50 x 50 x 5mm thick MS angle in all side and diagonal of SMC plate for strengthening by Aluminium revtting and provision of MS lifting hook etc. complete as required. |
| 167 | SH X: Lightning Protection and substation earrthing |
| 168 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc., complete as required. |
| 169 | Jointing G.I. tape (with another G I tape, base of the finial or any other metallic object) by riveting/nut bolting/sweating and soldering etc as required. |
| 170 | Providing and fixing G.I. tape 25 mm X 5 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run) |
| 171 | Providing and fixing G.I. tape 25 mm X 5 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run) |
| 172 | Providing and fixing testing joint, made of 25 mm X 5 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, check nuts and spring washers etc., complete as required. |
| 173 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc., (but with charcoal/coke and salt) as required. |
| 174 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required. |
| 175 | Providing and fixing 25 mm X 5 mm GI strip in 40 mm dia G.l. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 176 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 177 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 178 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/submain wiring/cable as required. |
| 179 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 180 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 181 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 182 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 183 | Fabrication, Supply and Fixing of 6mm thick chequered plates including providing and fixing 40mmx40mmx6mm angle iron supports on cable trenches, 25mmx6mm MS flat around the chequered plate by welding, providing lifting hook etc., as required. |
| 184 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 185 | SH: XI Provision of Fire Alarm System & Supply of Fire Extinguishers |
| 186 | Supply of UL listed (latest version) Non Networkable Microprocessor based expandable intellegent Addressable Type Fire Alarm Control Panel of Single loop, with minimum 80 character graphics / LCD display with keypad and minimum 1100 events history log in the non volatile memory (EPROM) ,The panel should be equiped with loop capacity to take minimum 64 intellegent addressable detectors/ devices (In any combination ) in one loop. Four access levels, capable of taking Protocol Devices, Graphical Display, sufficient numbers of programmable relay controls for controlling ventilation fan, fire pump room, monitoring of fire sprinkler and fire hydrant pump, 230 volts, 50 Hz AC power supply, automatic battery charger, 24 volts sealed maintenance free lead acid batteries sufficient for 2 hours normal working and then be capable of operating the system for 30 minutes during an emergency / fault conditions along with battery stand as required. The panel shall have facility for seamless integration with PA system (For Giving triger Signal to Start pre-recorded Digital Voice Evacuation from PA system in case of fire ). Provision shall be made in the panel to be compatible for Building Management System etc. as per specification, complete as required. |
| 187 | Supply of GSM SIM Auto dialler along with suitable adaptor with GSM based Voice and SMS dialer, Micro-controller based, 2 Voice Messages, Separate Intrusion & Fire Message, 15 Telephone Numbers for Each Message, 20 Second Recording Time for Each Message, Alarm SMS with Alarm Type, Time and Date Information, necessary connections, etc complete as required. |
| 188 | ITC of fire alarm panel and GSM SIM auto dialler including programming of all devices complete etc as required (mentioned in item No. 118 & 119). |
| 189 | Supply, Installation, Testing & commissioning of UL listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } and with unique optical sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications ,complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors) |
| 190 | Supply, installation, testing and commissioning of UL listed (Latest Version) intelligent Addressable type Heat Detector (Fixed cum-rate of rise type) with max. triggering temperature programable from 53.9 degree C to 60.6 degree C complete with all fixing accessories like base, base box, self adhesive sticker indicating loop number and address etc. to be installed below / above false ceiling, roof and concealed space, etc. interconnecting to loop cable, etc. as per specification complete as required. |
| 191 | Supply, Installation, Testing & commissioning of UL listed (latest version) intelligent addressable Manual call station (Resetable pull / push type) suitable for semi flush mounting, IP 54 for indoor use with inbuilt fault isolator / isolator module with double gang outlet box, equipment for key operated test-reset lock, electronic or rotary switches for address setting. Manual pull station shall be connected with two wire to SLC loop of Fire Control Panel. Cover shall be made out of LEXAN (or poly carbonate equivalent) with clear operating instruction and the word Fire appearing on the front complete with connections etc. as required and as per enclosed specifications. |
| 192 | Supply, installation, testing and commissioning of UL listed (latest version) loop powered addressable Hooter-cum- strobe with adjustable sound level in the range of min. 90 db to Max. 120 db at 1M distance complete with termination etc. as required and as per enclosed specification. |
| 193 | Supply, installation, testing and commissioning of UL listed Fault Isolator Module with termination etc. complete as required and as per enclosed specifications. |
| 194 | Supplying & laying of 2 x 1.5 sqmm FRLSZH (fire retardent low smoke zero halogen) armoured cable, 600 / 1000V rated with annealed copper conductor as per applicable IS standared complete as required. |
| 195 | Provision of industrial type First Aid Box (suitable for min 10 persons) as approved by St. John Ambulance Brigade/ Indian Red Cross conforming to IS 2217-1963 as required. |
| 196 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of MS Sheet, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 197 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of MS Sheet, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 198 | Providing & fixing of 4.5 Kg fully charged Co2 Fire extinguisher cylinder confirming to IS 2878 : 1976 including discharge pipe, handle, wheel type Brass valve, wall hook, etc complete as required. |
| 199 | Supply & fixing of foam fire extinguishers, portable type 9 litre capacity hanged on wall with bracket complete as required. |
| 200 | Supply & Positioning of Galvanized steel Fire Sand bucket (4 Nos) with MS Stand painted in post box red color with prior red oxide paint and written with white paint 'FIRE' including filling sand as per IS 2546 specifications etc complete as required. |
| 201 | Supplying and fixing shock treatment chart (easily readable and duly framed) in Three (English, Hindi & Tamil) languages and first aid box containing material as prescribed by St. John Ambulance brigade OR Indian Red Cross complete as required and complying the CEA regulations etc., complete as required. |
| 202 | SH-XII : Dismantling and Shifting of Essential, Non-Essential, APFC, AMF, CCR Essential Panels, CCRs, UPS & Battery banks etc., |
| 203 | Shifting of Essential LT Panel from existing power house to new sub station / Terminal building / Switch room including dismantling, removel of power cables / control cables and reinstallation, testing, commissioning etc complete as required. (Note: Cable end terminations will be paid extra as applicable). |
| 204 | Shifting of 2 x 80 KVA UPS along with associated isolation transformers, battery banks, UPS output LT Panel from existing power house to new sub station including dismantling, removel of power cables / control cables and reinstallation, testing, commissioning etc including end termination of power/control cables complete as required. |
| 205 | Shifting of 30 kW CCRs from existing power house to new sub station including dismantling, removel of power cables / control cables and reinstallation, connections, testing, commissioning etc complete as required. |
| 206 | Shifting of 04 kW CCRs from existing power house to new sub station including dismantling, removel of power cables / control cables and reinstallation, connections, testing, commissioning etc complete as required. |
| 207 | Dismantaling of LT Non-Essential panel from existing power house to AAI store complete as required. |
| 208 | Dismantaling of AMF panel from existing power house to AAI store complete as required. |
| 209 | Dismantaling of 125 KVA DG Sets from existing power house to AAI store complete as required. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail