| 1 | Supplying, installing, testing and commissioning of 100 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (550 Wp X 182 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnecting wires / cables up to solar ON GRID inverter proper base plate canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB MCB etc. wiring up to solar Inverter in casing and capping display board sign board two distinct earthing lightning arrester liaisoning charges remote monitoring system with maintaining card / chip for 5 years including net charges for RMS System complete up to net meter Installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG.(4-5-7) |
| 2 | Providing and erecting 3 Pole MCCB 415V 200A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB(5-5-2) |
| 3 | Providing and erecting 3 Pole MCCB 415V 400A rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB(5-5-4) |
| 4 | Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes panel boards etc. including cutting bending drilling welding riveting treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.(6-1-1) |
| 5 | Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.(6-1-19) |
| 6 | Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose 500 V with require capacity 99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density0.8 A per sq. mm. with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB(6-2-11) |
| 7 | Supplying and erecting LT CT multifunction DLMS compliance energy meter of accuracy of class 0.5 3x240V 50 Hz with optical & RS 232 port backlit LCD measure & display trivector energy load survey TOD tamper detection & logging power ON /OFF events instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box and connected to CTs.(6-3-5) |
| 8 | Supplying and erecting AC three phase LT CT multifunction net meter DLMS compliance of accuracy class 0.5 3 x 240V 50Hz with backlit LCD display optical port & RS 232 port (measures import kWh kVAh export kWh kVAh Net kWh kVAh V I kW 6 months history of energy load survey TOD tamper detection & logging power ON/OFF events instantaneous parameters of rating 1/5A with display in absence of power) with wiring connections and mounting hardware on provided panels complete with calibration certificate from manufacturer.(6-3-14) |
| 9 | Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates.(6-5-2) |
| 10 | Supplying and erecting LED type indicating pilot lamp with LED colours red / yellow / green 230 / 250V on provided box / panel with necessary material wiring & connections etc.(6-5-5) |
| 11 | Supplying and erecting LED type indicating pilot lamp with LED colour blue 230 / 250 V on provided box / panel with necessary material wiring & connections etc.(6-5-6) |
| 12 | Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 185 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL(7-1-37) |
| 13 | Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100V 4 core 300 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL(7-1-39) |
| 14 | Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface to required depth complete.(7-6-11) |
| 15 | Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing &recording the results as per specification no. EA-EP(9-1-1) |
| 16 | Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP.(9-2-2) |
| 17 | Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.(9-2-3) |
| 18 | Supplying and erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation complete.(9-3-1) |
| 19 | Making cement concrete foundation including excavation (60 x 60 x 150) cm deep in 1 3 6 cement concrete (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay).(16-3-6) |
| 20 | Supplying and installing of Solar PV Module cleaning unit consisting of nozzles spray necessary pipes valves post electronic panel board concealed with weather proof cabinet spreading water periodically for removal of dust related motor pump controller timer and nozzles set suitable for covering 5 KW Solar PV Module. (Approx. 35 Sq. Mtr. PV Module area). ( 22541 + 39*4000 =178541 * 5% =187468.05)(4-8-8) |
| 21 | Supplying, installtion & marking of surge arrestor/ surge protection device at the sub main distribution board after the incoming breaker of type 2 tested for Imax 40 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD(6-6-6) |
| 22 | Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface to required depth complete.(7-6-12) |
| 23 | Providing earthing with copper earth plate size 30 x 30 x0.315 cm complete with all materials testing & recording the results as per specification no. EA-EP(9-1-2) Please Enable Macros to View BoQ information |