| 1 | Supplying and fixing of 20W LED Batten on surface of wall / ANG partition i/c connections with 1.5 sqmm copper conductor cable etc. Complete as reqd. (Make: Crompton / Philips / similar superior) |
| 2 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch,connections etc. as required. |
| 3 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.(6 module) |
| 4 | SITC of 3Phase, 415V, 0-50A, 50Hz Energy Meter (Digital Type) for Submetering i/c all accessories (L&T 4040 dual source meter ) in the existing panel/ surface complete as required. |
| 5 | Supplying and Fixing the following electrical accesories on the surface of wall/ inside DB including giving connections, testing and commissioning etc as reqd |
| 6 | 4 way (4 + 12), Double door AC Distribution Board |
| 7 | 63A Four Pole Isolator |
| 8 | 5 - 32 A 'C' Series Single Pole MCB |
| 9 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 10 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 11 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 12 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 13 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 14 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 15 | 1 x 1.5 sq. mm |
| 16 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 17 | 25 mm |
| 18 | Supply &Laying of following size of PVC insulated and PVC sheathed / XLPE Aluminium armoured power cable of 1.1 KV grade on surface/ in panel etc as reqd |
| 19 | 4x50Sqmm cable |
| 20 | Supply & Laying of following size of PVC insulated and PVC sheathed / XLPE Aluminium armoured power cable of 1.1 KV grade etc as reqd in the existing cable tray as required. |
| 21 | 4x50Sqmm cable |
| 22 | Providing and fixing 6SWG dia GI wire on surface or in recess for connections etc.as reqd |
| 23 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 24 | 4 X50 sq. mm |
| 25 | Supplying and fixing of Voltage stabilizer suitable for 1.5TR AC unit, operating on the input voltage range from 160 to 280V, 50Hz AC supply, Intelligent Time Delay System and Ac output terminal, digital LED indication, Making connection, testing and commissioning etc as required. (Make:V-Guard I4 Prima or SS Make) |
| 26 | SITC of seqential operation logc along with temparature control for 4 nos 1.5 TR Split AC units with following features. make Smart Electronics/SS make Model :- TIM 4HTAM - SPL |
| 27 | Auto / Manual ON Switch ; Prefixed Timing Cycle ; Digital Temperature Controller with 3 meters long Sensor wire ; 230 VAC Buzzer for ALARM ; |
| 28 | 12 way & 8 way Heavy Duty Connectors for wiring ; Size :- 12\\" x 8\\" x 4 \\" |
| 29 | Working of Customized 4 AC Timer :-Situation 1 :- Room Temp. RT ≤ LOW , 1 Working, 3 Standby ; Situation 2 :- Room Temp. RT ≤ SET , 2 Working, 2 Standby ; Situation 3 :- Room Temp. RT ≥ (SET + Differential) , 3 Working, 1 Standby ; Situation 4 :- Room Temp. RT ≥ HIGH , All 4 Working & Buzzer also ON . (Defence room ) |
| 30 | All the above |
| 31 | Supplying and fixing 32 mm 8kgf/cm² PVC pipe for draining the condensate water of 1.5TR S/T AC unit etc. as reqd. |
| 32 | S/F 38 x 38 x 5 mm MS Angle for Supporting the ID/OD units |
| 33 | S/F 38 x 5 mm MS Flat for Supporting the ID/OD units |
| 34 | S/L of 2x1.5 sqmm copper conductor FRLS armoured cable on surface of wall etc as required. |
| 35 | SITC of Micro-processor type fire alarm control panel of4 zones built in charging arrangement with battery backup as per specifications attached as reqd. |
| 36 | SITC of Photo electric type smoke detector with fixing the detector as per the environment amd specification attached including sign writing etc. as required |
| 37 | P/I Manual Call Point ABS Resettable Type mounted on a surface of wall as per specifications. |
| 38 | P/F of Response Indicator including interconnetion,sign writing etc.as reqd |
| 39 | S/F Electronic Hooter in suitable metallic box with wall mounting provision and as per specification attached. Please Enable Macros to View BoQ information |