| 1 | Supply, Installation, Testing & Commissioning of Inverter Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 10.0 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments. (Make - Mitsubishi Electric/ Mitsubishi Heavy/ Daikin/ OGeneral) |
| 2 | Supply, Installation, Testing & Commissioning of Inverter Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 7.0 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments. (Make - Mitsubishi Electric/ Mitsubishi Heavy/ Daikin/ OGeneral) |
| 3 | Supply, Installation, Testing & Commissioning of Inverter cassete type split AC machine having cooling capacity not less then 14.1 kw with variable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments. (Make - Mitsubishi Electric/ Mitsubishi Heavy/ Daikin/ OGeneral) |
| 4 | Supply, Installation, Testing & Commissioning of Inverter Ducted/Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 5.0 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments. (Make - Mitsubishi Electric/ Mitsubishi Heavy/ Daikin/ OGeneral) |
| 5 | S&F of Copper Refrigeration pipe line for liquid and suction line with hard/soft drawn copper piping with supports & brackets (Royku/Totaline/Mandeep) |
| 6 | Liquid Line (9.5 mm dia) with 9mm thick nitrile insulation with having aluminium foil wrapping and coating over insulation. |
| 7 | Liquid Line (6.35 mm dia) with 9 mm thick nitrile insulation with having aluminium foil wrapping and coating over insulation. |
| 8 | Suction Line (15.9 mm dia) with 9mm thick nitrile insulation having aluminium foil wrapping and coating over insulation. |
| 9 | Suction Line (12.7 mm dia) with 9 mm thick nitrile insulation having aluminium foil wrapping and coating over insulation. |
| 10 | Supply & drawing of control cabling of 1.1kV grade PVC insulated, size 4 Core 1.5 Sqmm copper cable between ODU and IDU(Make-RR/KEI/ Polycab/Gloster/Havells) along with refrigerant pipe line. |
| 11 | Supply & drawing of power cabling of 1.1kV grade PVC insulated, size 3 Core 2.5 Sqmm copper cable (Make-RR/KEI/ Polycab/Gloster/Havells) along with refrigerant pipe line. |
| 12 | Supply & drawing of control cabling of 1.1kV grade PVC insulated, size 4 Core 2.5 Sqmm copper cable between ODU and IDU(Make-RR/KEI/ Polycab/Gloster/Havells) along with refrigerant pipe line. |
| 13 | Supply & drawing of power cabling of 1.1kV grade PVC insulated, size 3 Core 4 Sqmm copper cable (Make-RR/KEI/Polycab/Gloster/Havells) along with refrigerant pipe line. |
| 14 | Supply & drawing of power cabling of 1.1kV grade PVC insulated, size 5 Core 4 Sqmm copper cable (Make-RR/KEI/ Polycab/Gloster/Havells) |
| 15 | Supply of 4 Core 6 sqmm XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] |
| 16 | Laying of cable of size 4 core 6 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting |
| 17 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire.Up to 50 sqmm |
| 18 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.150x50x1.25mm (18SWG) With out angle iron support |
| 19 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :4 core 6 sqmm |
| 20 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :4 core 6 sqmm |
| 21 | Supply & laying of 25/32 mm dia.drain Water piping work out of UPVC/ HDPE hard pipes (Supreme, ISI Marked) incl. fitting , accessories bends, elbows, tees, flanges, tapings, etc. insulated with 9mm. Thick nitrile rubber tube insulation. |
| 22 | Supply and Laying of flexible 20 mm drain pipe |
| 23 | Supply and fixing of GI tray having size as suitable to the AC machines and a height of 25 mm with an arrangement to drain out water . It must be made with 22 Gauge GI sheet and to be suspended from the ceiling with sufficeint no of suspenders etc below the AC units .The tray must be removable in nature . |
| 24 | Supplying,fitting & fixing in position suspended false ceiling with frame work of aluminium hollow section of size 50mm X 25mm (2.0mm thickness) combined with aluminium corners of size 38mm X 25mm, suspended by aluminium hollow tube section of size 38mm X 25mm having size of 600mm X 600mm ceiling with aluminium composit panels (ACP) - Interior grade of thickness 3.0mm comprising of proctective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect including all incidental charges etc. as per direction of Engineer-in-charge. |
| 25 | Providing and fixing of false ceiling with powder coated exposed G.I. grid suspension system (E-Grid T 2430/1510 or equivalent load carrying capacity withmid span deflection not exceeding 1/360 span with hanger spacing of 1200mm c/c) consisting of Main Runner 3600 mm long, Cross Tee 1200 mm / 600 mm long and Wall Angle. The Wall Angle shall be fixed on PVC Dash Fasteners on the perimeter of the wall by steel screws with distance 300mm c/c. The Main Runners to be placed @ 1200 mm. The Cross Tee 1200mm will be inserted in the pre-cut slots of Main Runner at a regular interval of 600 mm to form a modular grid of 1200mm X 600mm. Additional Cross Tees of 600 mm shall be placed perpendicular to the Cross Tee 1200 mm long to finally form a grid of 600 mm X 600 mm. |
| 26 | Grid of module size 600 mm X 600 mm shall be supported by 6 mm dia G.I. wire from purlins / soffit. 4 mm thick High Pressure Steam Cured NonAsbestos pearl designer Fibre Cement Standard Ceiling Board (Density > 1500 Kg/m3) of size 595 mm X 595 mm, conforming IS 14862 & Type A Category IV ofISO 8336, tested as per AS-1530 part 3 & BS-476 Part 4,5,6,7 & 8, should be placed in the Grid module to form a False Ceiling. All complete as per thedrawing & directions of Engineer-in-charge.In ground floor.a) False Ceiling (with 4mm thick Pearl Designer Fibre Cement Board and E-GridT-2430/1510). |
| 27 | Insulation of drop ceiling by 10 mm Nitrile rubber sheet (Accoflex / A-flex / Approved make) with necssary pasting by best quality adhesive as per direction of EIC. |
| 28 | Making Trap door with aluminiun channel and ACP Board ( 3 mm thick) Make -Aludecor/Protap Bond / Approved make) complete with linkages ,levers,fitting,supports and all necessary accessories for maintenance of Indoor Unit with lockable gate. |
| 29 | Supply & Fixing of Fire retardant nonporous double layer Flexible Connection ( CANVAS ) between each Concealed IDU and grill as per Direction of E.I.C . |
| 30 | SITC of Powder Coated Al. Grill without VCD suitable size (Make:Systemair / Primier / Approved make) |
| 31 | Charges for cutting wall / floor for entry of different sizes duct & pipe lines including mending good the damages including painting with wall matching colour and removal of rubbish as per direction of EIC. |
| 32 | S&F 415V, 3Ph, 25A, AC timer controller in SS double door 14 way DB enclosure (Legrand Make) with S&F following electrical accessories & front door locking arrangement with all connection, earthing attachment on wall as per direction of EIC i) 32A 4pole MCB (LK make cat no BB40320B)----1no ii) 24 Hr programmable Digital dial timer (LK make Cat no J6118B304)--1No. iii) 4 pole power contactor (LK make cat no MNX22/230V)--1no iv) 6A SPMCB...1 nos (make Legrand/ Myrius)--1no. v) 25A Auto-Off-Bipass SPDT toggle switch (Appvd reputed make)-1no. vii) LED indication lamp(approved reputed make)--3no. viii) Outgoing connectror make ELMAX (approved reputed make) for 4 TR AC Unit. |
| 33 | Supply & fixing 240 V 25A Timer controller for AC machine in SS double door (2+10) way DB enclosure with IP-43 ( Make-L&T ) or equivalent with S&F following electrical accessories & front door key locking arrangement with all connection by finishing the ends of 2 x 4 & 1 x 2.5 copper wire dowels solder less socket by crimping method as to GS earthing attachment on wall Inc. Necessary connections as per direction of EIC:- i) 10kA C-curve,240V 25A DP MCB (L&T/Schindler/ABB)---1 no. ii) 24 Hr programmable digital time switch(L&K/Schindler/ABB)---1 no.iii) 2 pole power contractor (L&T make cat no MNX22/230) ----1 set iv) LED indicator( Red/Green) ---- 1 Set v) 3 Module plate with cover-----1 no. vi) 20A auto-off-bypass SPDT toggle switch(Approved make/reputed make)-----1 no. vii) 10 A Modular type switch-----1 no. viii) Outgoing connection make ELMAX(Approved make)-----1 noix) Modular starter 25A --- 1 No |
| 34 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Legrand/Schneider/ Approved make), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 35 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Legrand/Crabtree/Approved make) & necy. Connections. |
| 36 | Supply & Fixing 240 V, 25 A, Modular type starter (North-west/Crabtree/Approved make) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 37 | Distribution wiring in 1.1 KV single core stranded 'FRLSH' PVC insulated & unsheathed copper wire (Havells/Ploycab/Gloster/KEI) in 20/25/40 mm size PVC rigid conduit 'FR' (Precision/Polycab make, MMS/HMS type) incl. necy. fittings as required. |
| 38 | (c) 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC |
| 39 | Supplying and Drawing 1.1 KV single core stranded 'FRLSH' PVC insulated & unsheathed single core stranded copper wire (Havells/Ploycab/Gloster/KEI) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required |
| 40 | (c) 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC |
| 41 | Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works |
| 42 | Channel Size : 40 mm x 40 mm19 mm dia 3 mm thick polythene pipe without earthcontinuity wire |
| 43 | Supplying & Fixing of PVC water proof type Loop box (Make-Sintex GSJB2520 /Hensel / Approved make) of size [250X200X100]mm having hinged PVC top cover & 4 mm thick with rubber gasket lining,railway type mechanical locking arrangement, with DIN rail. incl. S&F one no 415V,32 A 4 pole MCB on wall as per direction of EIC |
| 44 | Finishing of the PVC insulated wire ends by socketing (Dowels make) with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 45 | 4 sq mm |
| 46 | 2.5 sqmm |
| 47 | 1.5 sqmm |
| 48 | Dismantling charge for existing split/window type air conditioner and handing it over to the store house /section office as per instruction of EIC |
| 49 | TERMS & CONDITIONS :-The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules |
| 50 | Defect Liabibility Period 1 (One) year |
| 51 | Make & model of each and every material to be approved by EIC Please Enable Macros to View BoQ information |