| 1 | SUB-HEAD 1--BDB,PDB,VTPN ETC |
| 2 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make:L&T/Legrand/ABB/SIEMENS/Schneider] |
| 3 | 2+12 way |
| 4 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [Make:L&T /LEGRND /ABB /SIEMENS] |
| 5 | 6 way |
| 6 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Make:L&T /LEGRND /ABB /SIEMENS] |
| 7 | 4 way (Up to 160A) |
| 8 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection |
| 9 | 100 A |
| 10 | 125 A |
| 11 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. [Make:Legrand /Schneider /Siemens /Crabtree/ L&T] |
| 12 | 32 A DP |
| 13 | 63 A FP |
| 14 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make:Legrand /Schneider /Siemens /Crabtree/ L&T] as per direction of EIC. ] |
| 15 | 6-32 SP MCB |
| 16 | 32 A TP MCB |
| 17 | 40 A FP MCB |
| 18 | 63 A TP MCB |
| 19 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal /SPNDB enclosure with IP-42/43 as per GS. |
| 20 | 8/12/16 Way |
| 21 | Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991) 4 bars, 415 V, 100/125 A, Dimension of Cu. bars [85mm long] 4 x 15x3mm, Dimension of Sheet Metal Box, 500x150mm |
| 22 | Supplying and fixing 4 Way MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting he wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment. |
| 23 | S & F 250V 25A Timer controller for single phase single control AC machine in SS double door 2+10-way DB enclosure (Make:- LK, encloser cat no DBSPN012DD) or equvalant) with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 2x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :-i) 10kA, C-Curve, 240V, 25A ,DPMCB (LT/Schnider/ABB Elegance) --- 1 Noii) 24 Hr programmable Digital/Analog Timer (LT make cat no 67DDT0) ---- 1 Noiii) 3 pole power contractor (LT make cat no MNX 22/230V) with 1 NO +1 NCadditional contact block ---- 1 setiv) 2 Moduler AC motor stater (Make:- Legrand/Myrius) ---- 1 No.v) 3 Module plate with cover (Make :- Legrand/Myrius) -- 1 Novi) 20A Auto-Off-Bipass SPDT toggle switch (Approved/reputed make) ---- 1 No.vii) 10A SPST Moduler type switch (Make :- Legrand/Myrius) - 1 No.viii) 70V-250V, LED Indicating Lamp (Make (Siemens) -------- 1 No.ix) Outgoing connector make ELMAX (Approved/reputed make) - 1 No.. |
| 24 | SUB-HEAD 2-- Supplying & Laying of Cable |
| 25 | Supplying and delivery of following size Armoured cablesXLPE/PVC insulated are designed for 1.1 kV StrandedAluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.) [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] |
| 26 | 4 core 95 Sq. mm |
| 27 | 4 core 70 Sq. mm |
| 28 | 4 core 50 Sq. mm |
| 29 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 30 | 4 core 95 Sq. mm |
| 31 | 4 core 70 Sq. mm |
| 32 | 4 core 50 Sq. mm |
| 33 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 34 | 4 core 95 Sq. mm |
| 35 | 4 core 70 Sq. mm |
| 36 | 4 core 50 Sq. mm |
| 37 | Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. |
| 38 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed |
| 39 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire. |
| 40 | From 70sqmm to 150sqmm |
| 41 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium)Protection with necessary fittings and jointing metarials asrequired |
| 42 | 65 mm dia |
| 43 | SUB-HEAD 3 --MISCELLANEOUS |
| 44 | Straigh through Jointing of cable of different size by compound jointing kit including S&F ferrul, tapes and jointing materials (Brand approved by EIC) |
| 45 | 3½ / 4 core 95 sqmm cable |
| 46 | SUB-HEAD-4 Cable Tray |
| 47 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. |
| 48 | 200x50x1.25mm (18SWG) With 25x25x3mm angle iron support |
| 49 | 150x50x1.25mm (18SWG) With out angle iron support |
| 50 | Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. 150x50x1.25mm (18SWG) |
| 51 | Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. 200x50x1.25mm (18SWG) |
| 52 | Supply & Fixing of perforated GI cable tray reducer with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the reducer incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. 200x50x1.25mm (18SWG) |
| 53 | SUB-HEAD 5-- Earthing Installation |
| 54 | Earthing with 50 mm dia GI pipe (TATA-Medium) 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level. By ISI-Medium GI pipe |
| 55 | Excavation of soil for installation of Earth Electrode and filling & ramming. (a) For Soft Soil. |
| 56 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode. |
| 57 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. |
| 58 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 59 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 60 | SUB-HEAD 6 --- SITC FEEDER PILLAR |
| 61 | Feeder Pillar Box : Design, Manufacture, testing, supply and commissioning of Double door outdoor type Distribution Feeder Pillar box of suitable size conforming to Indian Standard IS : 5039- 1969 with latest amendments,suitable for use on 3 phase 4 wire, 400/440 Volts 50 Cycles A.C. Supply and shall be suitable to be fabricated as per design & drawing to be approved by EIC. The Enclosure shall provide Degree of protection IP -66 respective Indian standard (IS). [Manufacturer/Fabricator having Test Certificates from CPRI] [The OEM must submit the test report and 5 years warranty certificate for all the items]. |
| 62 | The body will be fabricated with 3mm thick MS plate, MS angle (40X40X5) & MS Flat (50X6). The top of the box will be fitted with a sloping canopy made out of 3 mm thick sheet steel. It will have double hinged door at the front and back with suitable locking arrangement (Godrej Type) and provision for manual locking arrangement also. |
| 63 | Incoming Arrangement : |
| 64 | a) 415V 200 Amps TPN SFU units with HRC fuses (Make:- L&T/SIEMENS/ABB/ SCHNEIDER) in SS enclosure.---- 2 No. |
| 65 | b) 415V 200 Amps TPN fornt operated change over switch units (Make:- L&T/SIEMENS/ABB/ SCHNEIDER) in SS enclosure.---- 1 No. |
| 66 | Bus bar section : |
| 67 | 415 V, 315 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification- 1 set. |
| 68 | The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications. |
| 69 | Outgoing Arrangement : |
| 70 | a) 415V 125 Amps TPN SFU units with HRC fuses (Make:- L&T/SIEMENS/ABB/ SCHNEIDER) in SS enclosure.---- 1 No. b) 415V 100 Amps TPN SFU units with HRC fuses (Make:- L&T/SIEMENS/ABB/ SCHNEIDER) in SS enclosure.---- 2 No. c) 415V 63 Amps TPN SFU units with HRC fuses (Make:- L&T/SIEMENS/ABB/ SCHNEIDER) in SS enclosure.---- 4 No. |
| 71 | (b) E.I. Danger Board of suitable size ------- 1 no. |
| 72 | Metering Panel:- |
| 73 | a)Digital multifunction meter with selector push button switch (up/down) with Voltage, Current, Frequency, Total Harmonic Distortion, PF, KW, KVA, Kwh, KVAh and Preloaded Max & Min Demand with Date & Time Stamping display (Make-Schneider Electric/ Cat No- EM6400NG Class accuracy CIo.5S, POP of Accuracy Class 0.5S or equivalent model of Legrand/ Siemens/ L&T) - 1 No. |
| 74 | b) Indicating LED Lamp with colour glasses showing (Red/Yellow/Blue/Amber) (Siemens cat.no 3SB5285-6HC03, 3SB5285-6HD03, 3SB5285-6HF03 or equivalent cat of L&T/ABB/ SCHNEIDER) - 1 set. |
| 75 | c) 500/5 Amp ratio C.T (Kappa or equivalent) --- 3 nos. |
| 76 | d)S & F 2 Amp SPMCB for auxiliary supply to meters (Make- SIEMENS/L&T/Legrand) - 1 no. |
| 77 | Interconnection :- |
| 78 | All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads. |
| 79 | Earthing Arrangement :- |
| 80 | A separate continuous aluminum earth busbar of appropriate size is to be painted at the inside bottom of the panel and run across the full load of the Feeder Pillar Box. All electrical equipment are to be properly earthed with suitable size G.I. strip. |
| 81 | The complete Feeder Pillar Box is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating. |
| 82 | Installation :- |
| 83 | The complete feeder pillar box board is to be installed on suitable brick padestal as directed by the E.I.C. |
| 84 | Note: 1) All the above rates should be quoted inclusive of all taxes, duties and all ancilery charges with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees. Please Enable Macros to View BoQ information |