| 1 | Supply, Installation, Testing & Commissioning of Inverter Ducted/ Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 7.0 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments.(Make: Mitshubishi/O-general/Daikin) |
| 2 | Supply, Installation, Testing & Commissioning of Inverter Ducted/Concealed split AC machine (a set of full metal body indoor and outdoor unit) having cooling capacity not less then 5.0 kw with veriable speed rotary/ scroll compressor, refrigerant gas R32/R410 or better , both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments.(Make: Mitshubishi/O-general/Daikin) |
| 3 | S&F of Copper Refrigeration pipe line for liquid and suction line with hard/soft drawn copper piping with supports & brackets (Rajco/Ryoku/Nippon) |
| 4 | Liquid Line ( 3/8\\" dia 1.2 mm thick) with 19mm thick nitrile insulation) |
| 5 | Suction Line (5/8\\" dia 1.2 mm thick) with 19mm thick nitrile insulation) |
| 6 | Supply & Laying of 4 Core 2.5sq. mm. XLPE Insulated & unarmoured stranded Copper Conductor control cables having following numbers of core for Working Voltage up to 1100 Volts of following sizes] (As Control Cable from ODU to IDU) (Make : Havells/Gloster/KEI/Polycab) |
| 7 | SITC of Drain piping with 25 MM PVC (Sch-40) pipes with fittings duly insulated with 9MM thick Nitrile rubber section, Vapour barrier with necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc (Make : Supreme/Finolex/Approved make) |
| 8 | Supply & fixing of milky while powder coated Aluminium extruded return air diffusers/grilles without VCD(As per direction of E.I.C) (Make: SYSTEMAIR/DYNACRAFT/AIR ENT/RUSKIN) |
| 9 | Supplying, fitting & fixing in position suspended boxing for return /supply air arrangement for ducting with frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm ,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent including suitable arrangement for grill fixing complete in all respect as per direction of EIC. |
| 10 | a) Drop Celing |
| 11 | b) Trap door |
| 12 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the[100x50x1.25mm (18SWG)With 25x25x3mm angle iron support]. Incl. Al painting of MS support. |
| 13 | Supply, design, fabrication, installation of MS structural work for supports as per site requirement as per direction of E.I.C. |
| 14 | Fire redundant Flexible double canvas connection for package air conditioners as per direction of E.I.C. |
| 15 | Labour charges for dismantling of OLD Split Type AC Machines. |
| 16 | Less Cost for old dismantled 09 nos of Split AC Machines with ancillary componets like copper pipes etc. Rs. 45,000.00 |
| 17 | The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules |
| 18 | Defect Liability Period - 1 (One) year after completion of work |
| 19 | Make & model of each and every material to be approved by EIC Please Enable Macros to View BoQ information |