| 1 | HVAC workSITC Microprocessr Controlled, DX Type ceiling suspended Ductable Air conditioner Unit with all necessary acessories for hanging Indoor& Outdoor unit as per site condition having following specification i) Refrigerent-R410A/R407C ii) Expansion Valve:Thermostatic/Electronics iii) Compressor :Single/Twin Scroll/Twin Rotary with Fixed speed v) ODU: Outdoor Unit Air cooled Condenser unit With Copper coil with Aluminium fins having single compact ODU or multiple ODU unit vi) IDU: Indoor Unit having synthetic Filter and wireless/Wire Remote Vii) CFM: 400/Tr viii)Protection: Single Phase Preventer, phase reversal preventer, HP/LP cut Out. ix)Power sypply: 415+/- 10%, 50Hz x)Ambient temperature: 48°C +/- 5°C (Tollerance) Make: (Make:Hitachi/Daikin/ Blue Star/Voltas/carrier/Mitsubishi Heavy/O-general) no extra shal be payable for refrigerant gas & transportation/shifting work. |
| 2 | Min BTU/Hr or KW:66000/19.34 (1 nos. compressor) |
| 3 | SITC of ceiling concealed ductable cooling Air conditioner having following specifications:Minimum Cooling Capacity:(Kcal/hr)-7500 K.cal/hr Or 8790WISEER Rating -3.34-4.39/2022-2023 as per BEE/BIS IS Compliance- IS 1391Refrigerant- R410A/R32Compressor - Tropical RotaryEvaporator & Condenser Coil: Copper LCD Remote and All other accessories Power supply -220 V,50Hz(+ Tolerrance as per applicable standard)Indoor PCB should be enclosed in metalic enclosureMake:- O-General/Mitsubishi Electric/ Mitsubishi Heavy/Hitachi. |
| 4 | Fire Damper:Supplying, Fixing, testing and commissioning of Fusible link type fire damper.. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire in indoor motor and temperature rise above 62 degree centrigate . (Make: Carryaire/ Dynacraft/ TSC/Ravistar/ Systemair/Jonson Control) |
| 5 | REFRIGERANT PIPING WITH INSULATION:Supply & Laying Hard / Soft drawn Copper Refrigeration pipe line for liquid and suction line suitable for R410A/R407C refrigerant & 19 mm thick Nitrile Rubber 'class O' Insulation tube with supports & brackets as per direction of EIC. |
| 6 | Liquid Line ( 5/8\\" dia) without rubber insulation (make: Rajco / Mandev / Royku) |
| 7 | Suction Line (7/8\\" dia) with 19 mm thick nitrile rubber insulation Al foil covered (make: Rajco / Mandev / Royku) |
| 8 | S & Installation of Extra Add-on- Items- HVAC grade 5/8\\"(for suction) & 3/8\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle,screw,insulation, tape,fastner etc. for above AC machine as per direction of EIC. |
| 9 | DRAIN PIPE:Supply and fixing of Drain piping by UPVC with 6mm thick nitrile rubber insulation and necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc: |
| 10 | 25 MM |
| 11 | S&F flexible 25 mm PVC drain pipe as per direction of EIC. |
| 12 | Duct Work:Fabrication , supply, Installation , testing & commissioning of following GSS(120 GSM) sheet conforming to IS:655 – 277 (SAIL/ TATA/ JINDAL or as per choice of EIC) rectangular duct complete with neoprene rubber gaskets, elbows, splitter supports, flanges, turning vanes for supply air / return air duct erected with supporting rods, fustners, nuts etc. |
| 13 | 22SWG |
| 14 | 24 SWG |
| 15 | Supply, Fixing, testing, commissioning of Supply air diffusers of linear type powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core. Make - Premire /Systemair / Air Enterprise / Caryaire /Airmaster |
| 16 | Supply & Fixing of IDU & Duct Covered with 3mm thick ACP Board (Make:Aludecor/Protap Bond) Complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C. (for tap door ) |
| 17 | DUCT THERMAL INSULATION:Supplying and fixing of 13mm thickness duly laminated aluminium foil of mat fininshedclosed cell Nitrile rubber (class ''O'') insulation ANTI MICROBIAL COATING type on duct after applying two coats of cold setting adhesive (The joints shall sealed with 50mm wide and 3 mm thick self afhesive nitrile rubber tape insulaton complete as per specifications and as required. for Duct (K-Flex / Amracell / Supreme / K-Flex) |
| 18 | DUCT ACOUSTIC INSULATION:Supplying & fixing of acoustic insulation inside ducting with 10mm thick open cell nitrile rubber(class O) of density 140Kg/cu.m-160 Kg/Cum insulation with bolts nuts GI washers etc as required. (Make - Armacell / K Flex / Supreme/ A-Flex) |
| 19 | Supplying, fabrication & fixing M.S. Angle Frame for installation of 1 nos Outdoor unit . the structure having 3 nos 50 x 50 x5 mm MS angle for main bottom support grouted on wall with total length 16' and in between main support 7 nos 25 x 5 mm ms strip . For railing vertical & horizontal support is made by 25 x 25 x 5 mm Angle for safety of maintenance , total length 25' ; including cutting holes , welding , painting and mending good damage as per EIC |
| 20 | Supply & laying 1.1KV grade 3 core 4 sqmm flexible copper Cable with screw, saddle,drill machine nut bolt etc all necessary items needed for connection. (from starter to AC outdoor Connection) (make: Havells/KEI/Polycab/Finolex/Gloster/RR as per approved by EIC) |
| 21 | Supply and fixing of necessary electrical arrangements of Air Conditioning Units, PVC insulated FRLS grade Copper cable for connection betweeen indoor and outdoor units, 1.1 KV grade. 7 core x 2.5 mm² (Make- Polycab/ Havells/Gloster/RR/KEI/Finolex). |
| 22 | Providing and fixing fire retardant nonporous double layer flexible connection between IDU(FR) Please Enable Macros to View BoQ information |