| 1 | Supply & Erection of M S lattice structure of height 12.8 mtr as per DISCOMs approved design & details in alignment, including painting of tower of approved make two coat of red oxide paint and one coat of aluminium paint before installation and one coat of Aluminium paint after erection work completed as per technical specifications & drawing of DISCOM. (Excavation of pit PCC and CC foundation as per Discom specs. to be Paid Extra). |
| 2 | Supply of Fabricated 33 KV of 'V' type cross arms made of MS angle(75x75x6 mm) with clamp etc as per Discom specifications on the existing poles complete including all necessary nut and bolt etc with clamps including two coats of Red oxide and two coats of Aluminium paint etc. as required. |
| 3 | Supply and fixing of top hamper as per Discom specifications on the existing pole complete including nut bolts etc as required. Vertical type 33 kV. 0.75mtr. IS 75x75x6mm as per tech specs. Of DISCOM (Steel weight 6.5Kg. Approx. per top hamper). |
| 4 | Supply and fixing of 33 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. |
| 5 | Supply and fixing of 33kV Disc insulator and Hot dipped galvanized Hardware confirming to IS:731:1971 with latest ammendment and as per latest Discom Specs. on existing bracket including all accessories etc. as required. |
| 6 | B & S type hardware 120KN |
| 7 | B & S disc insulator 120KN |
| 8 | Supply and fixing M.S. channel (cut point) 100x50mm ISMC (9.5Kg. Per Mtr.) 2x1.8mtr. long with pilot patti 50x6mm thick necessary nuts and bolts etc. as per technical specification & drawing of DISCOM. |
| 9 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM. |
| 10 | Supply and fixing of PG / T clamps on overhead lines/jumpers, made of aluminium alloy 4600 of IS 617-1994 (with latest amendment if any) with steel nut and bolts conforming to IS 1363-1992 & IS 1367/1979-80 (with latest amendments if any) all ferrous metal parts intended for outdoor use except those made of stainless steel shall be protected by hotdip galvanising in accordance with IS 2633-1986 complete in all respect as required. |
| 11 | PG Clamp for Panther Conductor |
| 12 | Supplying and drawing Aluminium conductor steel reinforced (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. |
| 13 | 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog) |
| 14 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required. |
| 15 | Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x 380 x 4.0 mm |
| 16 | Supply and fixing of 11 / 33. KV Stay insulator as per IS:5300/1969 and as per Discom's standard specifications etc. as required. |
| 17 | 140 x 85 x 25mm 33 KV Stay Insulator |
| 18 | Supplying and laying of Hot dip galvanized steel stay wire of 550-900 N/mm Quality confirming to IS-2141/2000 in all respect Including chemical composition (Heavily coated Hard quality) of dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as required. |
| 19 | Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 20 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 21 | 3 core 300.0 Sq.mm |
| 22 | Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 23 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 24 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 25 | 33 KV End Termination Kit Outdoor type |
| 26 | 3 core 240/300/400 Sq.mm |
| 27 | 33 KV Straight Through Joint Kit |
| 28 | 3 core 185/240/300 Sq.mm |
| 29 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 30 | 150 mm dia. |
| 31 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 32 | 3 core 185.0 Sq.mm |
| 33 | Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 34 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 35 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 36 | 11 KV End Termination Kit Indoor type |
| 37 | 3 core 120/150/185 Sq.mm |
| 38 | 11 KV End Termination Kit Outdoor type |
| 39 | 3 core 120/150/185 Sq.mm |
| 40 | 11 KV Straight Through Joint Kit |
| 41 | 3 core 120/150/185 Sq.mm |
| 42 | Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 43 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 44 | 80 mm dia. |
| 45 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated stainless steel Outdoor enclosure of thickness of 2 mm and tank of stainless steel Outdoor enclosure of thickness 3mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for both Cable chamber and gas tank as per IEC 62271-200 and LBS to be rated for class E3 as per IEC 62271 - 103. Vacum Interrupter should be same as used during type test of RMU. Each feeder of RMU should have voltage presence indicator. and VCB feeder should consist of 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder, 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.Load break switch feeder shall have Fault Passage indicator, Right angle boots for all the feeder Modules, Remote trip, Emergency Stop, Cable cover interlocking, Trasnformer protection tapo card etc. All the type test certificates as per IEC and CEA from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) |
| 46 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 47 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 48 | Coupling Assembly to connect two different RMUs. |
| 49 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 50 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing. |
| 51 | 200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer |
| 52 | S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 ( Correspnding level as per BIS amended upto date of receipt of tender) & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, undirectional rollers as required including carrying of pre-commission Testing & Charging of Transformer complete in all respect . Factory Tests : The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) in OEM's own lab and same shall be witnessed by Department engineer. Site Tests : Following tests shall be carried out on each transformer at site by OEM engineer in presence of department's site engineer:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor) |
| 53 | Note :Manufacturer's testing laboratory should be certified by NABL and have an in house core cutting facility to ensure proper control & monitoring of quality. This is crutial to prevent the mixing of prime core materials with Second grade or defective materials. The core should be constructed from high grade, non ageing, PRIME GRADE CRGO steel with M4 Grade or Better, using silicon steel laminations, and should be of boltless design. The core and coil assembly should be undergo drying process using a highly efficient vacuum drying autoclave to remove moisture through heating and drying. |
| 54 | 63 KVA with % impedance 4.5 |
| 55 | Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5 including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. |
| 56 | 9.0 Mtr long PCC pole of 200 Kg Working Load |
| 57 | Supply and erection of GI stay set confirming to pattern-1 of BS:16/1974 and as per latest Discom Specifications complete with stay rod with anchor plate fitted with cast iron cross head and steel bow, in cement concrete 1:3:6 including excavation of pit-re-filling etc complete as required. |
| 58 | Stay set of dia 16mm, 1.8m long stay rod and anchor plate 300 x 300 x 4.0 mm |
| 59 | Supplying and drawing Aluminium conductor steel reinforced (ACSR) ISI marked(IS 398 part II-1996) on existing cross arms through insulator with all necessary T&P required including binding and twisting etc. complete in all respect as required. |
| 60 | 50 Sqmm of (6+1) 3.35 mm (Rabbit) |
| 61 | Supply and fixing of Galvanised steel 'V' type cross arms with clamps as per latest Discom specifications made of Galvanised steel angle(65x65x6) on the existing poles complete including all necessary nut and bolt, clamps as required. |
| 62 | Supply and fixing of top hamper on the existing pole as per latest Discom specifications complete including nut bolts with two coats of Red oxide and two coats of Aluminium paint etc as required. |
| 63 | Vertical type |
| 64 | 11 kV (.7m long) (65 x 65 x6mm angle) |
| 65 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. |
| 66 | Supply and fixing of 11 kV pin insulator confirming to IS:731:1971 with latest ammendment on existing bracket including all accessories like MS forged hot dipped GI Pin confirming to IS 2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest amendment, and as per latest Discom specs. etc. as required. |
| 67 | T & C type hardware 45 KN |
| 68 | T & C disc insulator 45 KN |
| 69 | Labour charges for dismantling of existing Lattice tower including MS channel, V cross arm, 11KV/33 KV insulator, guard wires, stud/stay wire, one span of ACSR conductor and other electric items coming along and in the alignment of the road, then removal and re-rolling of Lattice tower as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from DISCOM/ concering authority complete as required. |
| 70 | Labour charges for dismantling of existing PCC/MS electrical Pole including MS channel, V cross arm, 11KV insulator, LT insulator, guard wires, stay wires, one span of ACSR conductors and other electric items, coming along and in the alignment of the road, then removal and re-rolling of the PCC /MS Pole as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge, clean the site good as per the requirement and dismantle material receipt duly signed by DISCOM Engineer submit the receipt to EIC as required. |
| 71 | Supply and fixing Substation structure for mounting 11/0.4 Kv Transformer on Double pole as per DISCOM specification complete in all respect as required including nuts and bolts etc (excluding the cost of poles) made of MS channel of 4 nos 100 x 50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as required. |
| 72 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. |
| 73 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required. |
| 74 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 75 | 120.0 Sq. mm |
| 76 | 3.5 core Please Enable Macros to View BoQ information |