| 1 | Requirement of electrical wiring in new proposed signature lab (ECED) and Basic electronics lab (ECED). |
| 2 | Wiring for light point/ fan point/ exaust fan point/ call bell point with 1.5 sq mm FRLS PVC insulated copper condutor single core cable in surface/ recessed medium class PVC conduit with modular swtich, modu;lar plate, suitable GI box and earthing the point with 1.5 sq mm FRLS PVC insulated copper conductor single core etc. are required. complete in all respect.Make- Anchor Roma, Havells crabtree, C&S. Wire Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells. |
| 3 | Supplying and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Complete in all respect.Make- Anchor Roma, Havells crabtree,C&S. |
| 4 | Supplying and fixing of suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. Complete in all respect.Make- Anchor Roma, Havells crabtree,C&S. |
| 5 | Wiring for following circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | Wiring for following circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 2 X 4.0 sq. mm + 1 X 4.0 sq. mm earth wire |
| 7 | Wiring for following circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 4 X 6.0 sq. mm + 2 X 6.0 sq. mm earth wire |
| 8 | Wiring for following circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 4 X 10.0 sq. mm + 2 X 6.0 sq. mm earth wire |
| 9 | Wiring for following circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Complete in all respect.Make- KEI,R.R Kable, Kalinga Premium. HPL, Havells, Rallison, V-Marc 4 X 16.0 sq. mm + 2 X 10.0 sq. mm earth wire |
| 10 | Supplying and fixing 20 amps, 240 V, SPN industrial type ,socket outlet,with 2 pole and earth metal enclosed plug top along with 20 amps 'C' series SP MCB, in sheet steel enclouser, on surface or in recess with chained matel cover for the socket outlet and complete with connections, testing and commissiong etc. as required.complete in all respect. Make- L&T, Simens, Legrand, HPL, Havells, C&S. |
| 11 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. Triple pole and neutral |
| 12 | Supplying and fixing following way, single pole and neutral sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. Complete in all respect. (But without MCB/ RCCB/ Isolator). Make- L&T, Havells , Legrand, HPL,C&S,ABB, Schnieder, Simens. 6 way , Double door |
| 13 | Supplying and fixing 63 Amp. FP MCB (10 KA) miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. CAT-B |
| 14 | Supply & fixing of 36 watt to 46 watt above 3300 leumin indoor recess mounting LED Square Fitting for Armstrong Ceiling having Powder coated die cast aluminium housing body with extended heat sink and diffuser of Special Polycarbonate material and driver set complete in all respect.Make- Bajaj, Philips, Havells,C.G. (CAT- A) |
| 15 | Supplying and fixing following ways on surfce/ reces mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCB/ Incomer/ RCCB/Isolator/ MCCB) as required (Note- Vertical type MCB TPDB is normally used where 3 phase outlets are required) .complete in all respect as per site requirement. Make- L&T, Havells , Legrand, HPL,C&S. 4 WAY (4+12), Double Door |
| 16 | Supply, installation, testing and commissioning of ceiling fan, including wiring the down rods of 90 cm with 1.5 sq mm FRLS PVC, insulated, copper condutor, single core cable, etc. as required. Complete in all respect |
| 17 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. Complete in all respect. Make- Anchor Roma, Havells crabtree, Philips, C&S. |
| 18 | Providing and fixing M.S. Fan clamp type I or II of 16 mm dia M.S. Bar, bent to shap with hooked ends in R.C.C slabs or beam during laying, including painting the exposed portion of loop, all sa per standered design complete. Complete in all respect. |
| 19 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. complete in all respect. Make- Bajaj, orient PSPO, Crompton,Havells, C&S. |
| 20 | Supplying and fixing following ways on surfce/ reces mounting,vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCB/ Incomer/ RCCB/Isolator/ MCCB) as required (Note- Vertical type MCB TPDB is normally used where 3 phase outlets are required) .complete in all respect as per site requirement. Make- L&T, Havells , Legrand, HPL,C&S. 8 WAY (4+24), Double Door |
| 21 | Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.Make- L&T, Havells, Legrand, HPL, C&S. 200 Amp, 25 KA,TPMCCB |
| 22 | Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.Make- L&T, Havells, Legrand, HPL, C&S. 100 Amp, 16 KA,TPMCCB |
| 23 | Supplying, installation , testing & commissioning of following capacity End feed unit for the existing air insulated compact type bus trrunking/ rising main for on 3 phase 4 wire 415 volt, 50 Hz A.C. supply made with 1.6mm thick steel sheet enclouser (IP54) duly power coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets , angle iron bracket stell fastners, connecting to earth system etc. as required. complete in all respect. 200A to 250 A, Isc= 15kA for 1 sec. |
| 24 | Supply & laying of 35 sq mm x 4 core aluminium conductor XLPE armored served aseathed cable 1100 volts grade of following size at suitable depth below ground level over cushion of 75 mm thick sand alround and protected with well burnt bricks on & along the cable & back filling after digging the soil & it back filling/ on wall/ floor the cable run cancealed manner, with cutting and plastering, complete in all respect as per direction of engineering incharge. The armouring of cable shall be properly connected with the earth terminal of the pole panel and as required lugs,, gland etc. Make- Gloster, Kalinga Premium, Rallision, Havells, KEI, R.R.Kable. |
| 25 | Supplying and making end termination with aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 10 sq mm |
| 26 | Supplying and making end termination with aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 16 sq mm |
| 27 | Supplying and making end termination with aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 35 sq mm |
| 28 | Supplying and making end termination with aluminium lugs for following size of PVC insulated and PVC sheathed / XL.10 sq mmPE aluminium conductor cable of 1.1 KV grade as required. 50 sq mm |
| 29 | Supplying and making end termination with aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 95 sq mm |
| 30 | Supplying and making end termination with brass compression gland for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 95 sq mm. x 3-1/2 core |
| 31 | Supplying and making end termination with brass compression gland for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 35 sq mm. x 3-1/2 core |
| 32 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 33 | Supply and fixing of two number 8 SWG copper wire in 15 dia G.I. pipe for earthing, laid in ground or in wall duly concealed including the post of cement, sand, labour, T&P other material required for proper completion of the work with 2 Nos.8 SWG copper wire. complete in all respect. |
| 34 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, “C”curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBcomplete with connections,testing and commissioning etc. as required.complete in all respect.Make- L&T, Havells, Legrand, HPL, C&S. Single pole |
| 35 | Dismantaling and reconnection of old cables, wires, Panel, dismantaled portion including cost of material, labour, T&P for proper finishing of work. Complete in all respect. (Electicians charge) Please Enable Macros to View BoQ information |