| 1 | WIRING |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Group C |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 6 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 8 | 3 x 2.5 sq. mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 20 mm |
| 11 | 25 mm |
| 12 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 13 | 5/6 A switch |
| 14 | 15/16 A switch |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | 15/16A modular socket Three module |
| 17 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 18 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 19 | 4 Module (125mmX75mm) |
| 20 | 6 Module (200mmX75mm) |
| 21 | 8 Module (125mmX125mm) |
| 22 | Supplying and making end termination with copper reducer/bottle lugs/terminal lugs for following size of PVC insulated copper stranded cable of 1.1 KV grade as required. |
| 23 | 4 x 16 sq.mm + 2 x 6 sq.mm |
| 24 | 4 x 10 sq.mm + 2 x 6 sq.mm |
| 25 | DLP PVC Trunking |
| 26 | Supply and fixing of DLP Pastic Trunking 105x50mm with cover including all accessories (flexible cover (85 mm),end cap, junctions, joints, wall crossing, VDI accessories etc. as per site condition) |
| 27 | Seperation Partition for DLP Pastic Trunking sutable for DLP of size 105X50 |
| 28 | Supplying and fixing following modular switch/socket on existing modular plate, including connections etc. as required on the existing DLP trunking. |
| 29 | 5/6 A switch |
| 30 | 5/6 A socket outlet |
| 31 | Supply and fixing following modular support for mounting wiring accessories suitable for DLP trunking with 85mm cover plate |
| 32 | 6 module |
| 33 | MCCB, MCB & DB'S |
| 34 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 35 | 4 way , Double door |
| 36 | 16 way, Double door |
| 37 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 38 | 6 way (4 + 18), Double door |
| 39 | 8 way (4 + 24), Double door |
| 40 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 41 | 4 way (4 + 12), Double door |
| 42 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 43 | Single pole |
| 44 | Double pole |
| 45 | Triple pole |
| 46 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 47 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 48 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 49 | Supplying and fixing the following rating, 415 V, 10 kA, 'C' curve miniature circuit breaker suitable for inductive load of Triple pole in the existing MCB DB, complete with connections, testing and commissioning etc. as required. |
| 50 | Supplying and fixing the following rating rating, 415 V, 10kA, 'C' curve miniature circuit breaker suitable for inductive load of Four Pole in the existing MCB DB, complete with connections, testing and commissioning etc. as required. |
| 51 | 6-32A |
| 52 | Supplying and fixing the following rating, breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in the spare space of existing cubicle panel board including drilling holes in cubicle panel, making connections, providing extended/direct rotary operating mechanism (ROM) for operation from panel door, spreading insulation reinforcement, industrial work on busbar and panel to accommodate the MCCB etc. complete with connections, testing and commissioning etc, as required as per the site condition and making good the damages and insulation. |
| 53 | 100 A, 16 kA, 4P |
| 54 | Supplying and fixing the following rating, breaking capacity and pole MCCB with thermomagnetic release in the existing MCCB vertical DB including making connections to accommodate the MCCB etc., complete with connections, testing and commissioning etc., as required as per the site condition and making good the damages and insulation. |
| 55 | 100 A, 16 kA, 4P |
| 56 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required. |
| 57 | 4 way Double door TPN MCCB DB |
| 58 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN distribution board with provision for fixing FP MCCB as incomer and TP MCB as out going, complete with 250 A tinned copper bus bar, common neutral link, earth link, din bar for mounting MCBs, detachable gland plate, interconnections, earthing, phosphatized and powder painted, fixing using bolt and nut, giving connections etc. as required. (But without MCCB, MCB) |
| 59 | 4 way (4 + 12), Double door |
| 60 | EARTHING |
| 61 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt ) as required. |
| 62 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 63 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 64 | Supplying and filling Earthing compound in the earth pit, not including excavation, but including mixing with excavated earth and water. Complying with IEC 62561-7:2018. |
| 65 | Supplying and fixing 12 SWG copper wire on surface or in recess for loop earthing as required. |
| 66 | Supplying and fixing 8 SWG copper wire on surface or in recess for loop earthing as required. |
| 67 | MV CABLE LAYING |
| 68 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 69 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 70 | Supply of 1.1 kV grade following rating, Aluminium conductor XLPE insulated PVC sheathed armoured power cable(as per IS ) as required. |
| 71 | 4C x 16 sq.mm |
| 72 | 2C x 10 sq.mm |
| 73 | 4C x 50 sq.mm |
| 74 | 4C x 10 sq.mm |
| 75 | MV CABLE JOINTING & END TERMINATION |
| 76 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 77 | 2 X 10 sq. mm (19mm) |
| 78 | 4 X 10 sq. mm (25mm) |
| 79 | 4 X 16 sq. mm (28mm) |
| 80 | 4 X 50 sq. mm (35mm) |
| 81 | Removal of Existing Electrical Fittings and Accessories |
| 82 | Removing the existing sub-main wiring including conduits, wires, clamps and all associated accessories, complete as required, and handing over the dismantled materials to the store/yard, as directed by the Engineer-in-Charge. Please Enable Macros to View BoQ information |