| 1 | Electrical works |
| 2 | 1.14.1 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 3 | 1.14.2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | 1.17.12 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x2.5 sq. mm |
| 5 | 1.17.3 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 6 | 1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 7 | 1.24.3 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 8 | 1.24.5 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 9 | 1.27.2 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 10 | 1.28.2 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module |
| 11 | 1.50.1 Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 12 | 2.10.1 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 13 | 19.1 Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no:s blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accesories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required: |
| 14 | 90.12.10.2 Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 15 | OD263174/2025-2026 Supply, installation, and commissioning of a 10 kVA Online Double Conversion UPS with an inbuilt isolation transformer, having 3-phase input and single-phase output, suitable for continuous and reliable power backup. The system includes 20 Nos of 12V, 60Ah tubular leadacid batteries configured to provide 1-hour backup . A durable battery stand is included for safe installation. The UPS features advanced protections (overload, short circuit, deep discharge), intelligent battery management, and a user- friendly display panel. Both the UPS and batteries come with a 3-year warranty, ensuring long-term performance and reliability. |
| 16 | OD263176/2025-2026 Supply, installation, testing, and commissioning of a 6-litre capacity RO + UV water purifier with dual purification technology, comprising sediment pre-filter, activated carbon filter, RO membrane, and UV sterilization chamber, complete with initial flushing and performance testing to ensure the treated water meets IS:10500 potable water standards, and handing over the system in fully operational condition with a minimum one-year warranty. |
| 17 | OD263211/2025-2026 Supply of 305 mm sweep, 1400 rpm Heavy Duty Exhaust Fan working on 230V A/C with all accessories complete as required |
| 18 | OD263212/2025-2026 Supply of 250 mm sweep Light Duty Exhaust fan in plastic body with self-opening lowers working on 230V single phase A/C with all accessories complete as required |
| 19 | OD263214/2025-2026 Dismantling of existing damaged fluorescent light fittings including connections and handed over to the officer in charge as required |
| 20 | OD263220/2025-2026 Supply, Installation, testing and commissioning of pre-wired, 12W recess/Surface mounting round LED down light fitting complete with all accessories directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. Make : Phillips, Crompton Greaves, Bajaj, Lucker or approved by engineer in charge |
| 21 | OD263221/2025-2026 Supply and fixing of 9W LED Bulb in the existing holder as required. (Make: Phillips, Crompton, Lucker or Approved by engineer in charge) |
| 22 | 90.12.1.12 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3 core 4 sq mm |
| 23 | OD263222/2025-2026 SKFDSROD: Supply and installation of pre-wired 20W LED batten fitting complete with all accessories and tube etc directly on ceiling/wall, including connection with PVC insulated,copper conductor single core cable and earthing etc as required.<br>(Make: Phillips, Crompton greaves, Bajaj, Lucker or Approved by engineering in charge) |
| 24 | 90.15.4.4 Supply Conveyance, installation, testing and commissioning of 100W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 25 | 90.15.4.3 Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 26 | OD263292/2025-2026 : Engaging Electricians Please Enable Macros to View BoQ information |