| 1 | Electrical Work |
| 2 | BOQ-AS/E of Terminal Gantry Structure of R.S. Joist - 175x85 mm. 19.5 Kg/Mtr. 6.1 Mtr. above the ground and 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75 mm. with 2 nos channel 175x85 mm suitable for Disc & Pin Insulator Including earth excavation back filling making plinth of required height and with required fabrication as per drawing. complete in all respects as per direction of E/I.(AOR) |
| 3 | Supply, Errection, Testing & Commissioning of 33 KV Outdoor VCB with required str, 1250A, 1500MVA, 25KA, Motorized 750MVA/1250Amp/ with transformer control & relay pannel including CT, PT with structure. complete in all respects Make: Crompton/ABB/Schneider as per specification and direction of E/I. (AOR) |
| 4 | S/E of Busbar Gantry Structure of 105 Lbs/Yard Rail pole 6.50 M long 5.2 Mtr. above the ground level and 1.30 Mtr. Below in 1:3:6 cement concrete foundation mounted on a stone pad of 300x300x75 mm. With M.S. angle 100x100x8mm (12.1Kg/M) mm suitable for Disc insulator including earth excavation, back filling, making plinth of required height and with required fabrication as per drawing complete in all respects as per direction of E/I.(AOR) |
| 5 | S/E of 33 KV, 1250A Bus Isolator with Structure made of 125x65 mm. 13.1 Kg/M Channel at a height of 2.5 Mtr. above ground and 1 Mtr. below ground on a cement concrete pad of 75 mm. Thick with 1:3:6 cement concrete foundation including excavation back filling, making plinth of required height & with required fabrication for bracing of M.S. Flat 50x6 mm. 2.4 Kg/M and top of M.S. Angle 75x75x8 mm., 8.9 Kg/M as per drawing (for structure) Complete in all respects Make: Jaipuria/Rama as per direction of the E/I. (AOR) |
| 6 | S/F of 33 KV fuse set out door type of Relco/Rama make complete including structure as per drawing. Complete in all respects.(AOR) |
| 7 | S/E of 33 KV Lightning Arrestors with Structure made of M.S. Channel 125x65 mm. 13.1Kg/M top of M.S. Angle 50x50x6 mm. 4.5 Kg/M Lightning Arrestors/Post Insulator are to be mounted on M.S. Plate of 200x150x8 mm. Height of structure is to be 3.5 Mtr. above ground and 1 Mtr. below ground on a 75 mm. thick cement concrete pad with 1:4:8 cement concrete foundation, making plinth of required height including all fabrication as per drawing complete in all respects Make: Elpro/Oblum/ W/S as per direction of E/I. (AOR) |
| 8 | Supply & fixing of 33 KV with 11KV 4 Nos Set B&S type strain Disc insulators 120KN E&M strength. as per drawing complete in all respects Make : Jaishree/BHEL/WS/RR as per direction of E/I.(AOR) |
| 9 | Supply & fixing of 33 KV tension fitting suitable for panther conductor and 120KN E&M 11KV disc insulator set of 4 complete in all respects as per direction of E/I. (AOR) |
| 10 | Construction of 33 KV transformer plinth as per drawing. with all material, labour and T&P etc. required for proper completion of the work as per specifications of UPPCL as per direction of E/I.(AOR) |
| 11 | Providing and fixing of G.I. Chain Link fabric fencing of required width size50x50mm including strengthening with 2mm dia wire or nuts, bolts and washers as required Complete as per the direction of Engineer-in-charge. Made of G.I. Wire of dia 4mm PVC Coated to achieve outer dia not less 5mm in required colour and shade. Complete in all respect as per direction of E/I.(AOR) |
| 12 | Construction of boundary wall in brick work with cement mortar 1:6 (1 Cement : 6 Coarse Sand) for chain link including plaster in cement mortar 1:4 (1 Cement : 4 Coarse Sand) and finishing with water proofing cement paint complete as per attached drawing & complete in all respects as per direction of E/I.(AOR) |
| 13 | S/Fixing of 33 KV Post insulator 2x22KV of approved quality and make with all necessary material required for proper fixing including structure made of 125x65mm MS Channel (2.5Mtr above ground of 1 mtr below with ground with grouting 1:3:6 cement concrete including all labour, material, T&P etc. required for proper completion of the work. as per drawing. complete in all respects Make: Jai shree / BHEL as per direction of E/I (AOR) |
| 14 | 1 nos 1250 A VCB of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally enclosed, air insulated metal clad housing floor mounting horizontal isolation, vermin proof. Fully interlocked horizontal draqout type having isolation features and control devices complete with following 8 nos single phase double core current transformer 300/5, 5/5 Amp epoxy cast resin isulated class of isulation E as per SLD. Core 1-15 VA burden class 1.0 for metering Core 2-15 VA burden class 5P10 for protection One no. numerical microprossor based three phase over current (IDMT element) with earth fault relay with instantaeous elements 1 no Anti Pumping device 1 no Circuit breaker control switch for eletrical (T/N/C) 1 No. limit switch for test & service 1 no Ammeter (0-300AMP & 0-5 Amp) with selector switch. (96 mm square). 1 No Electronic type digital energy analyser having 30 days memory and parameters of KW KWH, Power factor, frequency etc Suitable for BMS compatible with all accessories. 1 No Tri vector meter, 1 set of following indicating lamps, Red, Yellow & blue for phase indication, Amber for trip indication, Red \\"On\\" Green \\"Off\\", Spring charge indiacation, Auto trip Indication, 1 No Hooter with hooter acceptance and reset push button. 1 No master trip relay. ( Eletromechanical type), 1 set of fuses ferrules wiring etc as required. Note : All spare contacts of breaker or any other equipment inside the breaker shall be wired upto the outgoing terminal strip with appropriate terrules / coding. The terminal strip rating shall be suitable for connecting two wires of 2.5 sqmm subjected to providing minimum size suitable for 4/6 sqmm, Incommer & Buscoupler shall be electrically interlocked.11 KV H.T. Panel should have 02 Nos Incomer, 01 No. Buscoupler & 8 Nos Outgoing panel as per approved by specification of UPPCL describe as above (Make-ABB, Schiender, CG Power, Seimens) |
| 15 | Construction of control cable trench of required size 0.30x0.45 Mtr. bricks class designated-100 work including plastering etc. and covered with R.C.C. Slab (0.50x0.60 M) size complete with all material, labour and T&P etc. required for proper completion of work. complete in all respects. As per direction of E/I.(AOR) |
| 16 | S/Filling of 20 mm. stone grit in yard of size26x36mtr 75 mm. thick complete in all respects. (AOR) |
| 17 | Supply & laying of earth mat in the switch yard of the Sub-Station for all Electrical Equipments and structure by laying of M.S. Round bar of 32 mm. dia. in 750 mm. deep trenches and earth electrode 3.0 M. long of M.S. round bar 32 mm. dia 0.5 M below ground level. The work include welding/bending/flooring of M.S. round bar and connection all steel structure in switch yard with earth mat by means of M.S. Strip of size 50x6 mm. including all labour, materials, T&P etc. required for proper completion of the work as per details specification of UPPCL Complete in all respects as per direction of E/I. (AOR) |
| 18 | Painting of (Complete sub-station) Terminal Gantry, Lighting arrestor, Busbar Gantry, Line Isolator & Bus Isolator Structures, Post insulator, Fencing, Poles and other structure complete with two coats of Al. paint over red oxide. (AOR) |
| 19 | S/F of out door type 11KV fuse set Relco/Rama/Rastriya make with insulator Jai shree/BHEL make complete in all respects as per direction of E/I.(AOR) |
| 20 | Supply and laying of Control Cable for metering as per direction of E/I. (Gloster/Universal/Polycab/Havells/Diacab/KEI make) (AOR) (a) 2.5 Sq. mm. 2 Core Copper |
| 21 | (b) 2.5 Sq. mm. 4 Core Copper |
| 22 | (c) 2.5 Sq. mm. 10 Core Copper |
| 23 | Supply of Top MS Channel 100x50x2240mm as per design complete in all respects UPERC P-48 |
| 24 | S/E of 125x65 mm. MS Channel (13.10 Kg/M) 1.5 M long fixing in control room for OCB/VCB pannel complete in all respects as per direction of E/I.(AOR) |
| 25 | Supply/Fixing of MS ladder of size 5 mtr long and 0.4m width with MS angle 40x40x6mm incl painting etc . complete in all respect as per direction of E/I.(AOR) |
| 26 | Supply, Installation, Commissioning & Testing of Battery charger 24V 24V/40Amp float cum Boost battery charger with dropping diodes suitable for I/P 230V±10%, 1 Phase, 50Hz Type FCBC as per PVVNL Specification, maximum continuous output ratings (outpur voltage in float mode 25.80 Volts and in Boost mode upto 33.0 Volts), output current 40A, Plus trickle charging current of battery floatmode 20A(Max), Boostmode 20A Load terminal, 20A, Battery terminal 20A, Starting rate 10A upto 2.35 V per cell, Finishing rate 10 A upto 2.75 V Per cell, Output ripple 1% PP at full load and 25.8V DC, output regulation (floatmode) ±1% for ±10% supply voltage fluctuation and ±10% to 100% load variation, Automatic/manual mode of operation, Automatic and manual terminal charging, control configuration 1-phase full wave controlled, thyristor bridge feed through 1-phase transformer and controlled by constant current/protential controller with load liminting feature and integrated non compartmentalized DCDB with 01 No 60A MCCB incomer, 5 Nos 16AMCB, sheet thickness 2mm, protection as per detail specification enclosed. IS: 13947) IP-42/ maximum Permissible input volage ±10% of 230V AC, Electronic protection with auto reset against short circuit and overload , DC over voltage short circuit at charger output terminals, thyristor by fuseing with protection against over charging, efficiency of rectified >65% at rated load, Power factor 0.7 lag at D.C. Current 230V Input with ANC cooling type and Class F type insulation. For Battery : 240V/200AH Tubular type Battery Bank consisting 12 Cells of each 2V/200 AH dry & uncharged along with wooden stand & accessories (AOR) |
| 27 | S/Installation, testing & commissioning of out door type 10 MVA with on load tap changer Power Transformer as per ISI specification including loading, unloading, local carriage & erection of the same on existing plinth & making all necessary connection etc. Complete in all respects Make: Crompton/ Alstom/BHEL/ABB/Schneider or approved GTP from UPPCL/PVVNL cable termination box with disconnecting facility for 33 KV XLPE cable at 33 KV side.cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side.On load tap changer +/- 7.5@ 2.5% Bi directional roller, Conservator with drain valve, Earthing terminals, Double diaphragm explosion vent, Radiator with top & bottom shut off valve, First filling of oil including make up fill, Silica gel breather with oil seal, Rating and diagram plate, Air Release plug, Buchholz relay with shut off valve, Winding temperature indicator (WTI), Oil Temperature indicator (OTI), Megenatic oil level guage, Pressure relief device, Marshalling box (AOR) |
| 28 | S/Laying of Aluminium conductor PVC insulated armoured, served, sheathed cable 1100 V grade at a depth of 75 cm. below ground level over a cushion of 75mm. Below ground level over a cushion of 75mm. thick snad alround and protected with burnt bicks on sides and on top. on surface the cable run shall be fixed on MS clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respected. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. P.S. No. 501 (Gloster/Grandly/Polycab/Daicab/Havell's/KEI make). a) 50 Sq.mm. 3½ Core |
| 29 | Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. P.S. No. 1131 |
| 30 | ii) 50 Sq.mm. |
| 31 | iii) 120 sq mm |
| 32 | S/F of brass nickle plated compression gland for PVC isulated & armoured served sheathed, underground cable incl. rubber ring etc. complete in all respects. The armouring of the cable shall be properly connected with the earth as per direction of E/I P.S. No 503. (a) Size 25 mmx 3.5 core |
| 33 | (b) Size 16 mmx4 core |
| 34 | S/F of fire bucket, round bottom made of GI sheet 9-11 liters capacity duly painted as per fire brigade design, supported on hanging bracket, chained & locked initially filled with fine river sand, water as per direction of E/I. P.S. No. 1133 |
| 35 | S/F of shock treatment chart (Prescribed under I.E. Rules) duly framed with glass & supported from back with hard board or soft board with supply of all material labour and T&P for proper completion of work. P.S. No. 1134 |
| 36 | S/L of 1800x900x12 mm. thick chequered rubber matting of testing quality. P.S. No. 1136 |
| 37 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :DSR 2018. 120 Sq.mm.I.No. 10.5.2 |
| 38 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.DSR-2018/Item No. 14.13.2. 80mm dia 14.13.2 |
| 39 | 100mm dia 14.13.3 |
| 40 | Supply and fixing Clamps, bolts, nuts etc.complete in all respects (DSR-2018/I.No. 2924) |
| 41 | ii) 120 Sq.mm. 3 Core (AOR) |
| 42 | S/F of 11 KV TPMO Relco/Rama make 9 nos insulator of Jai shree/BHEL make complete in all respects as per direction of E/I UPERC P-48 |
| 43 | S/E Testing & Commissioning of 63 KVA Al. wound outdoor type Transformer as per ISS. Complete in all respects Make : P.M./Kanohar/LD Power/Paramix as per direction of E/I (UPERC 2019) |
| 44 | Supply of 300 sq. mm 3 core high conductivity aluminum strand compacted circular conductor XLPE armoured 33 KV(E) Cable neutral earthed system confirming to IS 7098-Part-II (1985) with latest amendment complete in all respects as per direction of E/I. (Make Gloster/Universal/Polycab/Havells/Diacab/KEI). (AOR) |
| 45 | S/F of jointing of 300 sq. mm out door type type 33 KV jointing kit heat Shrinkable type for 33 KV Cable including cost of all material, labour, T&P etc. for proper completion Make : Raychem/ Denson as per direction of E/I. (UPERC P-47) |
| 46 | S/F of palm or pin type copper tin plated cable socket (lugs) to the cable leads insulating with tape and making connections etc. complete in all respects as pe direction of E/I PS No. 504. i) 300 Sqmm |
| 47 | S/Making of Straight through joint suitable for 185 sq.mm x 3 core 11 KV armoured cable as per ISS & complete as per the direction and satisfaction of E/I (Raychem, Denson, Cabseal Make) UPERC 2019 Pg-29 |
| 48 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. DSR 2018 13.4 |
| 49 | 11 KV RMU Panel (3 Way RMU):-Design manufacture testing at works supply, installation testing & commissioning of 3 panel Board 11KV, Indoor tree standing, floor mounting totally enclosed mela clad VCB insulated comprising of 1 Nos 11KV isolater load break switch and 2 Nos Vaccum circuit breaker as outgoing enclosed in robotically laser weided non-extensible type stainless steel SF6 VCB enclosre with Self Powered relay (IDMTL O/C +E/F) as HT switchgear including suitable transformer protection relays, metering, indicators push buttons, copper busbars, etc as per the requirement complete as required The fault with stand capacity shall be minimum 20KA for 1 second including four cable entries for two incoming cable and two outgoning cable glands and lugs suitable for 2x 240/185 sqmm XLPE armoure cable. Incomer shall be provided with 630A Manual Load Bread / Fault Make switch, integral Earthing Switch with making switch, \\"Live Cable\\" Indicating LEDs energized thru Capacitive Voltage Deviders, Transparent Viewing window for verification of Earthing, Right Angle terminal protectors / Boots, Electrical & mechanical indications as required, Outgoing feeders: Two nos. Vaccum circuit breakers with the following |
| 50 | SF-6 insulated 630A Circuit Breaker, integral Earthing Switch with making switch, Emergency Trip Push Button, Electrical & mechanical indications as required, Shunt Trip coil for external trip signal, \\"Live Cable\\" Indicating LEDs energized thru Capacitive Voltage Dididers, Transparent Viewing window for verification of Earthing, Right Angle terminal protectors /Boots, IDMT relay for Circuit Breakers self powered, Merlin Gerin type VIP35 or equivalent with required protection CTs of suitable ratio, Cable box for incoming and outgoing shall be suitable for icrminating, 11KV, XLPE insulated Aluminium conductor armoured cables, One set inbuilt DC power pack , Transformer protection relays as required as per SLD. Complete in all respects (AOR) (Make-ABB, Schiender, CG Power, Seimens) |
| 51 | Laying of One number XLPE power cable of 33KV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required.(DSR elect 2018 Item.N. 8.7.2/P34) Above 120 Sqmm and upto 400 Sqmm |
| 52 | S/E of overhead line with ACSR (Painther/Dog) Conductor on pole/service bracket including binding etc. complete in all respects PS No 627 |
| 53 | S/L of Al. armoured cable PVC insulated served & sheathed cable 1100 V grade at 750 mm ground level protective with brick Complete in all respects as per direction of E/I 25 sq. mm 2 core. (Gloster/Universal/Polycab/Havells/Diatron/KEI make) P.S 501. a. 25 sq. mm 3.5 core |
| 54 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 33 KV grade as required : 120 Sq.mm. UPERC Pg-27 |
| 55 | S/F of jointing of following sizes outdoor/indoor type 11 KV jointing kit heat Shrinkable type for 11 KV Cable including cost of all material, labour, T&P etc. for proper completion of the E/I. (Raychem/Denson Make) uperc Pg-29. 185 Sq.mm. |
| 56 | S/Laying of heavy density poly ethylene pipes ISI marked anti rediant grade OD 160mm dia PN-8 PE 100 (PE 400) grade as per IS code 4984 with excavation at a depth of 1.20 Mtr below ground level i/c the cost of cutting of pipes for making up to length and making joints complete all respects as per direction of E/I. (Creator poly extrusion/duraline/rex/times/ narander plast/pioneer make). (AOR) |
| 57 | Supply of following type high conductivity aluminum strand compacted circular conductor XLPE armoured 11 KV Cable neutral earthed system confirming to IS 7098-Part-II (1985) with latest amendment at a depth of 900 mm. below ground level over a cushion of 100 mm. thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. Complete in all respects (Make: Gloster/Polycab/Havells/Diacab/KEI) as per direction of E/I. i) 185 Sq.mm. 3 Core (AOR) Please Enable Macros to View BoQ information |