| 1 | Installation of 250KVA,11/0.4KV Plinth mounted S/s -1No |
| 2 | 11mtrs long WPB Pole with Base plate (30.44Kg/m) |
| 3 | Earthing device Coil type |
| 4 | No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing |
| 5 | Pressure Channel (100X50X6) mm (9.2 Kg. / Mtr.)Rs.10.00 added for Galvanization |
| 6 | AB Switch mounting channel (100X50X6) mm(9.2 Kg. / Mtr.) |
| 7 | HG fuse mounting channel (75X40X6) mm(6.8 Kg. / Mtr.)Rs.10.00 added for Galvanization |
| 8 | Channel for cantilever arrangement (75X40X6) mm(6.8 Kg/mtr.)Rs.10.00 added for Galvanization |
| 9 | Angle for cantilever arrangement (50X50X6)mm(4.5 Kg./Mtr.)Rs.10.00 added for Galvanization |
| 10 | DP Bracing Channel (100x50X6)mm (9.2 Kg./Mtr.)RS.10.00 added for Galvanization(4 Nos.) |
| 11 | DP Bracing angle (50X50X6) mm 7Mtr. (4.45 Kg./Mtr.)RS.10.00 added for Galvanization |
| 12 | Angle for mounting LT distribution box (50X 50X 6)mm(4.5 Kg./Mtr.)Rs.10.00 added for Galvanization |
| 13 | 400 Amp 3 Pole AB Switch |
| 14 | 400 Amp 3 Pole HG Fuse |
| 15 | LA (9KV, 5KA Class) |
| 16 | 11 KV Pin Insulator polymer |
| 17 | HT Stay Set |
| 18 | Stay Wire (7/10 SWG) |
| 19 | Stay Insulator |
| 20 | Stay Clamp |
| 21 | GI pipe Earthing 40mm dia medium gauge- 2.5 Mtr long |
| 22 | 25 x 4mm GI Flat for Substation earthing |
| 23 | 50 x 6mm GI Flat for Neutral earthing of 250KVA |
| 24 | LT Distribution Box with MCCB, Aluminium Busbar for 3 Bay with kit kat fuse for 250 KVA S/S |
| 25 | 250 KVA.11/0.4 KV (AL)Transformer with tap changer, BIS Energy level-II |
| 26 | GI Nut, Bolt and Washer |
| 27 | 80sqmm AAA conductor for jumpering |
| 28 | 1Cx300mm2 LT XLPE cable(Armoured) |
| 29 | Anticlimbing Device(GI barbed wire 3kg per support) |
| 30 | Back Clamp for anticlimbing device 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 4 no's = (4x0.59x0.510) |
| 31 | Danger plate |
| 32 | Back Clamp for danger Plate 25X3 mm. flat, 0.59Kg/Mtr. Flat of 0.510mtr length 2 no's = (2x0.59x0.510) |
| 33 | Black Paint |
| 34 | Yellow colour paint for back ground |
| 35 | Sundries for tree cutting,Paint,Clamp,Connectors, Binding tape etc) |
| 36 | Erection of 11KV line by using 3Cx35mm2 XLPE Cable = 30 Mtr(DC)=2*30 mtr=60 mtr (1-Span) |
| 37 | 3Cx35mm² 11KV XLPE Cable (Armoured) |
| 38 | Heat shrinkable jointing kit suitale for 3Cx35 mm² 11KV XLPE Cable (out door type) |
| 39 | G.I pipe Earthing 40 mm dia medium gauge(3.25mm thick ness) 3 mtr long |
| 40 | Dead end clamp |
| 41 | Eye hook for (XLPE Cable) |
| 42 | Pole clamp Eye hook for (XLPE Cable) |
| 43 | XLPE Cable clamp to hold support wire |
| 44 | 7/12 GI Stay Wire for supporing Cable |
| 45 | 9 KV 5 KA 11 KV Lighting Arrestor |
| 46 | 25 x 4 mm GI Flat (For Lightning Arrestor) |
| 47 | 75x40x6mm GI channel for LA |
| 48 | GI nuts,bolts and washers |
| 49 | Sundries ( Clamp, Connectors, Binding tape etc |
| 50 | CIVIL WORK |
| 51 | Cement Concrete for Stay Anchor plate / stud CC foundation 1:3:6 size by using 4cm size HBG metal=(0.45 x0.45x1.5)mtr=0.3037Cum. @4158.84=1263.03 or 1270.00 |
| 52 | Concreting of poles in ratio 1:1.5:3 for 11Mtr WPB Poles |
| 53 | Couping of poles in ratio 1:1.5:3 for 11Mtr WPB Poles |
| 54 | Materials for Massionary work for Earth Pit,Charcoal, Salt etc including construction of earthing chamber (Size: 2\\"x2\\") and RCC slab cover |
| 55 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 Cement : 6 Coarse sand) as per TPSODL specifcation. Scope includes supply of all material with Locking arrangement ( for 14 Running meter) |
| 56 | Civil cost for makingTRF plinth from 250KVA of upto 1000KVA.BA has to provide necessary civil material,manpower,machinery for construction of plinth as per standard drawing |
| 57 | Survey of incremental/delta network and assets changes of 11 kV network and updation in GESW databas |
| 58 | Survey and digitization of New DSS and its internals including attrubutes |
| 59 | Survey and digitization of New MCCB/LTDB and its internals including attrubutes Please Enable Macros to View BoQ information |