| 1 | Disconnection of incoming/outgoing cable from HT switch gear VCBs/OCBs/RMUs ,11 KV/33 KV of any type, rating and make for carrying out necessary repair work all as directed and carrying of following phase of work including painting of complete inside and out side unit by two coat of first quality synthetic enamel painting over a redoxide primer painting after scrubing and removing the paint suface and remove the old paint.(a) Taking out trolley unit from metal clad housing and dismantling complete, carrying out inspection cleaning and repair of worn out part, gasket, bushes etc all as directed.(b) Opening of bus bar chambers, carrying out inspection, cleaning and testing of complete unit, repair of worn-out parts, insulators(including low IR value) etc.(c) Carrying out testing of all metering instruments repair of worn out spares, meter, wiring cable etc and testing complete.(d) Inspection and checking of all protection devices, relays carrying out proper adjustment and calibration as per existing load, repair of spares/components complete and testing all as directed.(e) Carrying out inspection and testing of auxiliary power system, repair of all worn out spares / wire and make functional the complete system all as directed.(f) Assembling of complete HT switch gear unit, proper greasing oiling / for easy operation and connection of incoming and outgoing cable and make all necessary adjustment and testing complete .(g) The spare parts to be replaced shall be of reputed brand/make and shall be of same type,design,specifications etc to match with the existing and as per the recommendation of OEM.(h) Complete Servicing and Calibration work shall be carried out by Qualified and reputed Service Engineer only.Note : Replacement of all spares will measured and paid separately under relevant item. All the spareparts are tentative and may vary in specification and quantity during execution. |
| 2 | Supply and Fixing in Replacement of following items for overhauling/maintainance of OCBs/ VCBs of 11 KV, 400 amps/630 Amps of any capacity and make. |
| 3 | (a) S & F 30/C+1E/F Relay CGI14N 18 to 52 V DC , SAP Code No- 4602411501,Make Crompton / Ashida |
| 4 | (b) S & F Master Trip Realy, Model-CGLXH1, SAP Code No- 460254819, Make Crompton / Ashida |
| 5 | (c) S & F Digital Volt Meter,Type-Elmeasure ,ALPHA 3V,VTSEC:-110V,3PH,4W Supply AC, VTR Programmable AUX Voltage-230V AC ACC CL : 0.5 , SAP Code No- 45025073E, Make Crompton./ Ashida |
| 6 | (d) S & F Digital Ammeter with Built in Selector Switch, SAP Code No- 460262360, Make Crompton ./ Ashida |
| 7 | (e) S & F Digital Volt Meter with Built in Selector Switch, SAP Code No- 460262359, Make Crompton / Ashida. |
| 8 | (f) S & F Trivector Meter, Model-ER-300P, SAP Code No- 4602523543F, Make Crompton / Ashida |
| 9 | (g) S & F 8 Window Annuciator, SAP Code No- 4602241740, Make Crompton/ Ashida |
| 10 | (h) S & F 33KV,30V DC Single Trip Coil, SAP Code No- 190232581ASLY, Make Crompton/ Ashida. |
| 11 | (j) S & F 33KV,30V DC Single Closing Coil, SAP Code No- 190232581ASLY, Make Crompton ./ Ashida |
| 12 | (k) S & F Worm Wheel (BIG) Full Teeth,Worm Shaft for Full Teeth (BIG) ncluding Worm Shaft Support With Bracket (JV7496Q) -For 9 Teeth and Full Teeth, SAP Code No- 490021001,490041015,4500513144-01 No,450041153- 02 No, Make Crompton./ Ashida |
| 13 | (l) S & F Big & Small Gear Assly with Motor Shaft, SAP Code No- 543/SP1, Make Crompton./ Ashida |
| 14 | (m) S & F Motor & Gear Assly, 220V AC/DC UMG 14 type (DELCO Make PMR-5) , SAP Code No- 450237377, Make Crompton / Ashida |
| 15 | (n) S & F Motor Charged Mechanism Assly UMG Motor & Operating Coils ( For Double Trip & Spring Charging handle) Upto 26.3 kA SAP Code No- 190261050, Make Crompton ./ Ashida |
| 16 | (o) S & F Spout Bushing Upto 1250 Amps (Without cc Part) ( 1Set of 06 Nos) ( For NX CALIX Panel) SAP Code No- 450088184, Make Crompton / Ashida |
| 17 | (p) S & F Master Trip Relay Model-CGXHT -30V DC-04NO+1NC, SAP Code No- 460254819, Make Crompton / Ashida. |
| 18 | (q) S & F Vaccum Bottle CG:- WL- 34599 M3+PV4730Q , SAP Code No- 190241725N Make Crompton ./ Ashida |
| 19 | (r) S & F Big Cam with Main Shaft with Bearing & Cover 74200007 , SAP Code No- 568/SP1 Make Crompton ./ Ashida |
| 20 | (s) S & F Set of Isolating Contact Assly 800 A ( Set of 06 Nos ) Tulip contact Assembly , SAP Code No- 74200073,Make Crompton ./ Ashida |
| 21 | (t) S & F Bus Support Insulator with Gasket and Hardware 61mm Dia , 450088029,450162005,450141176,450043001, SAP Code No-590/SP,Make Crompton ./ Ashida |
| 22 | (u) S & F Epoxy Moulded Frame for NX/JV CALIX Type - 25 KA, SAP Code No-450088040,Make Crompton ./ Ashida |
| 23 | (v) S & F TNC Switch with Bell Alarm Contact SAP Code No-460232141S,Make Crompton ./ Ashida |
| 24 | (w) S & F Local Remote Switch , SAP Code No-190232508, Make Crompton ./ Ashida |
| 25 | (x) S & F Anti Pumping Device SAP Code No-4602321174E,Make Crompton / Ashida. |
| 26 | Supply and Fixing in Replacement of following items for overhauling/maintainance of VCBs of 33 KV, 400 amps/630 Amps of any capacity and make as mentioned- |
| 27 | (a) S & F Coil ,Single Close,30V DC , 33KV , SAP Code No- 190232536ASLY,Make Crompton / Ashida |
| 28 | (b) S & F Coil ,Single Trip,30V DC , 33KV , SAP Code No- 190232559ASLY,Make Crompton / Ashida |
| 29 | (c) S & F Tulip Contact Assembly 1250A (1Set Consisting of 06 Nos) , SAP Code No-36V0127EASLY, Make Crompton./ Ashida |
| 30 | (d) S & F Support Insulator Single Hole, SAP Code No- 450088500, Make Crompton ./ Ashida |
| 31 | (e) S & F Support Insulator Four Holes, SAP Code No- 450088556, Make Crompton . |
| 32 | (f) S & F Complete Pole unit Assembly with embeded VI ,(Witrhout Connector and without Tulip Contact) For 1250 Amps SAP Code No- 4500241067, Make Crompton / Ashida |
| 33 | (g) S & F 33KV DELCO Make (B/M) Motor 230 V AC/DC with Gear Box (UMG-8 ), SAP Code No- 4602412105, Make Crompton / Ashida |
| 34 | (h) S & F Worm Wheel (BIG) Full Teeth,Worm Shaft for Full Teeth (BIG) , SAP Code No- 490021001,490041015, Make Crompton./ Ashida |
| 35 | (j) S & F TNC Switch with Bell Alarm, SAP Code No-460232042, Make Crompton ./ Ashida |
| 36 | (k) S & F Local Remote Switcht, SAP Code No- 460232144, Make Crompton./ Ashida |
| 37 | (l) S & F 3 Pin Plug Socket , SAP Code No- 4602322042, Make Crompton./ Ashida |
| 38 | (m) S & F DC MCB DP,Rating-16 A, 30 VDC , SAP Code No- 450232382, Make Crompton / Ashida |
| 39 | (n) S & F AC MCB DP,Rating-16 A, 230 VAC , SAP Code No- 450232609, Make Crompton / Ashida |
| 40 | (o) S & F Ammeter Selector Switch, SAP Code No- 460232238, Make Crompton ./ Ashida |
| 41 | (p) S & F Volt Meter Selector Switch, SAP Code No- 460232239, Make Crompto / Ashida |
| 42 | (q) S & F 33KV Epoxy Cast Indoor Current Transformer , CTR-50-25/5+5A, STR- 25kA/1Sec, Burden/ACC Class--15VA/CL 1.0+15VA/5P10,CT Sec-ON P1 Side BIL: 33KV/70KVrm/170KVpp , 33KV VT Fusees With Fuse Clip Fuse Rating-3.1 Amps , SAP Code No- 3V833CT1 & 460257666 Make Crompton ./ Ashida |
| 43 | (r) S & F Voltage Transformer, 1ph, 3Nos Fixed type Feeder ,Ratio-33000/RT3//110/RT 3V WDG1: 100VA , Classs- 1.0, Voltage Factor - 1.2 Continuous & 1.5 For 30 Sec ,BIL: 33KV/70KVrms//170KVpp , SAP Code No- 460257657 Make Crompton ./ Ashida |
| 44 | (s) S & F Digital Ammeter ,Make- Elmeasure , Type- Allpha 3A ,CTR-100/1A, Aux Voltage-230 VC, ACC CL: 0.5, Case Size- 96X96 SQMM, SAP Code No- 450252407E |
| 45 | (t) S & F Digital Volt Meter ,Make- Elmeasure , Type- Allpha 3V ,VTSEC-110V,3PH, 4W Supply AC, VTR Programmable , Aux Voltage-230 VC, ACC CL: 0.5, SAP Code No- 450252407E |
| 46 | (u) S & F Digital Multifunction Meter type EM 6400(TVM), SAP Code No-4602523648,Make Crompton ./ Ashida |
| 47 | (v) S & F 8 Way Annuciator SAP Code No-460241740,Make Crompton ./ Ashida |
| 48 | (w) S & F Motor Charged Mechanism Assly with Delco Motor & Operating Coils (Suitable for 40 KA New VCB's Benchmark Mechanism ) , SAP Code No-4502411862, Make Crompton ./ Ashida |
| 49 | (x) S & F Pole Mould for 33KV Indoor (For without Embeded Pole) SAP Code No-450088150,Make Crompton ./ Ashida |
| 50 | (y) S & F 30/C+ 1E/F Relay- CGI 14N-18 to 52 V DC SAP Code No-4602411501,Make Crompton ./ Ashida |
| 51 | Supply and Fixing in Replacement of following items for overhauling/maintainance of RMUs of 11 KV, 400 amps/630 Amps of any capacity and make as mentioned- |
| 52 | (a) S & F Spring Charging Motor,24 VDC, SAP Code No- 4624101063,Make Crompton / Ashida |
| 53 | (b) S & F Big Gear and Hub Assembly , SAP Code No- D1208Q,Make Crompton/ Ashida |
| 54 | (c) S & F Small Gear Assembly ,SAP Code No-4502411387, Make Crompton./ Ashida |
| 55 | (d) S & F Closing Spring Assembly, SAP Code No- D0286Q, Make Crompton ./ Ashida |
| 56 | (e) S & F Battery Charger, Input -230VAC, Output- 24VDC, Battery-20AH (For 10 Open Close Operation, SAP Code No- 450088556, Make Crompton / Ashida. |
| 57 | (f) S & F 12 KV RMU LBS Mechanism ( Motorised ) SAP Code No- 46241013489, Make Crompton / Ashida |
| 58 | (g) S & F Battery , Battery Capacity - 12 V / 7AH , SAP Code No- 4602412105, Make Crompton/ Ashida |
| 59 | (h) S & F P.B.Actuator with Holder, SAP Code No- 4602321530, Make Crompton./ Ashida |
| 60 | (j) S & F T- Handle Welded Assembly, 12 RMU., SAP Code No-460411714, Make Crompton ./ Ashida |
| 61 | (k) S & F Shutter Assembly for Interlock, SAP Code No- D2949Q, Make Crompton./ Ashida |
| 62 | (l) S & F Axuxilary Switch 4NO+$nc-12Kv RMU 2 Position Aux Switch , SAP Code No- 190232601, Make Crompton./ Ashida |
| 63 | (m) S & F Axuxilary Switch for Disconnector, 9NO+7NC -12 KV RMU -3 Position Aux Switch. , SAP Code No- 46241010220, Make Crompton / Ashida |
| 64 | (n) S & F Charge Handdle Assembly,12 RMU , SAP Code No- 460411713, Make Crompton / Ashida |
| 65 | (o) S & F Tripper Coil, 24VDC, 74 OHM,Magnetic , SAP Code No- 46241013572, Make Crompton ./ Ashida |
| 66 | (p) S & F Closing Coil, SAP Code No- 190232582ASLY, Make Crompton/ Ashida |
| 67 | (q) S & F SF- Gas Cylinder 11 Kg. SAP Code No- 460088031 Make Crompton ./ Ashida |
| 68 | (r) S & F Capacitive Voltage Indication (VPIS) , SAP Code No-4602416197 Make Crompton ./ Ashida |
| 69 | (s) S & F Self Powered Overcurrent Relay & Earth Fault Relay, 30/C+ 1E/F CGI 14S Relay, SAP Code No- 4602411550M/ Ashida |
| 70 | Supply and Fixing in Replacement PVC unsheathed 650/1100 volt grade single core FRLS 2.5 sq mm copper conductor including replacement of all unserviceable PVC insulated connectors and complete function of fault protection system and functioning of voltmeter/ ammeter/ indicator lamp with Ferule number and cable lug of Panel complete. |
| 71 | Material and Labour for Painting of VCBs/OCB/ACBs & RMUs with 1 coat of Synthetic enamel paint inside and out side over a coat of redoxide primer red lead after scraping off the old Paint as directed by Engineer -in charge. |
| 72 | Supply and fixing of Bus Bar sleeve of size 60mm width and 10 mm thickness for HT 11KV complete all as specified and as directed. |
| 73 | . Supply and Using of CRC(2-26) of 500ml unit for cleaning of VCB/OCB parts |
| 74 | Supply and Fixing Dew Guard is a passive solution for Mitigation of conensation of Temperature between -30 deg C + 90 deg C , it is halogen free and silicon free , environment friendly and can be disposed of in regular trash of size 150X250X2mm including fixing arrangement with strong Adheishive double sided tap all as specified and directed by Engr-in-Charge. Cat Part No- HDG X 150 , Make- Dew Guard of Hensel |
| 75 | Supply and laying of Synthetic Rubber Insulating Mats of Sizes 2mX1mX3.0mm thick for Voltage upto HT 33KV for Electrical purposes as per IS-15652-2006, (Superceeding IS-1524) suitable for Electrical shock safety all as specified and directed. |
| 76 | Supply and replacement of Current transformer having CT ratio 50/5 A. 15 VA, 5P-10, class 1 Accuracy for metering and protection with taking down old/unserviceable CT all as specified and directed. . Make CG/Areva/southen switchgear |
| 77 | Supply and replacement of Current transformer having CT ratio 100/5 A. 15 VA, 5P-10, class 1 Accuracy for metering and protection with taking down old/unserviceable CT all as specified and directed. . Make CG/Areva/southen switchgear |
| 78 | Supply and fixing in repair of Power pack 230 V/110V DC 20A/30 Amps or any type and Suitable capacity contained with maintenance free battery and charger to provide Auxilliary power supply to the VCB all as per the OEM recommendation including taking down of old Unserviceable Power pack all as specified and directed by Engr-In - Charge |
| 79 | Supply and Fixing in Replacement of PT Bush male Female Set suitable for HT OCB/VCB , 11 KV all as specifeied and as direcetd. of Make Crompton/southen switchgear. |
| 80 | Supply and Fixing in Replacement of PT Housing Bush suitable for HT OCB/VCB , 11 KV complete all as specified and as directed of Make Crompton/southen switchgear. |
| 81 | Supply and fixing, testing and commissioning of Epoxy moulded / Dry type11 KV/, 3/110V/3 Potential transformer (PT) suitable for 11KV,3 phase,50Hz,Class-1 A complete suitable for VCB 11 KV including taking down of old existing PT switch all as specified and directed. Make Crompton Greaves/soutern switchgear. |
| 82 | Supply and Fixing in Replacement of HT HRC fuse link with fuse barrel capacity 63 Amps to 100 Amps for HT 11 KV all as specified and directed. |
| 83 | Calibration of IDMT relay corresponding to the existing load and fault current timing for outgoing feeder and incoming HT feeder of OCB / VCB for two Nos over current and one No. earth fault relay using pattern generator and other testing equipments all as directed. |
| 84 | Supply and fixing of IDMT relay 16 to 30 Amps with two Nos over current relay and one No earth fault relay 0including necessary connection initial calibration and testing complete all as directed. |
| 85 | Supply and fixing of AUTO relay with two Nos over current relay and one No earth fault relay including necessary connection initial calibration and testing complete all as directed. |
| 86 | Disconnection of PT( Set of three) from site and taken to workshop. Rewinding of PT 11 KV/ 110 volt with super enamel copper conductor of suitable size. Re-insulating the PT with proper insulating material with varnishing and heating. Reconnection to the panel and Top up with transformer oil after filtration/Dehydration. Make the Equipment functionable with testing, commissioning complete all as directed by Eng-in-charge. |
| 87 | Supply and fixing of 11 KV, 400 Amps drop out fuse two post insulator per pole complete channel type with FRP fuse barrel of complete set after taking down old one (Make : JAIPURIA/RASHTRIYA/Oblum) |
| 88 | Supply and fixing of 11 KV, 200 Amps drop out fuse two post insulator per pole complete channel type with FRP fuse barrel of complete set after taking down old one (Make : JAIPURIA/RASHTRIYA/Oblum) |
| 89 | M&L for disconnecting electrical connection from HT and LT side including transporting the transformer capcity 800 KVA to 2000 KVA to work shop within Goa area, dismantling the transformer, drain out transformer oil, lift the cover, coil assembly keep up the assembly in oven upto the preparation of inside chambers by cleaning inside, scraping complete all around old parts of the transformer, two coats of oil resistance painting internal (inside transformer) over a coat of red oxide primer, cleaning the core iron sheet laminations asssembly by oil complete,removing the carbon sediments, dust in the coil and core gently without making any damage to coil and core, re-assembling all dismantled parts including provision of new gasket , nut, bolts, refilling with transformer oil and transporting back to original location including electric conection testing and commissioning complete.Note:(i) Transportation of trnasformer shall be measured and paid seperately(ii) Oil filtration,supply of new oil will be measured separately.(ii) All petty parts including nut, bolts, gasket minor weldings shall be included the rate quoted (iv) Rewinding shall be measured and paid seperately. |
| 90 | M&L for disconnecting electrical connection from HT and LT side including transporting the transformer capcity 63 to 400 KVA to work shop within Goa area, dismantling the transformer, drain out transformer oil, lift the cover, coil assembly keep up the assembly in oven upto the preparation of inside chambers by cleaning inside, scraping complete all around old parts of the transformer, two coats of oil resistance painting internal (inside transformer) over a coat of red oxide primer, cleaning the core iron sheet laminations asssembly by oil complete,removing the carbon sediments, dust in the coil and core gently without making any damage to coil and core, re-assembling all dismantled parts including provision of new gasket , nut, bolts, refilling with transformer oil and transporting back to original location including electric conection testing and commissioning complete.Note:(i) Transportation of trnasformer shall be measured and paid seperately(ii) Oil filtration,supply of new oil will be measured separately.(ii) All petty parts including nut, bolts, gasket minor weldings shall be included the rate quoted (iv) Rewinding shall be measured and paid seperately. |
| 91 | M & L for transportation and lifting of transformer 33/11KV/433V of capacity upto 2000 KVA including loading and unloading by suitable capacity crane to workshop for repair as per SI Item Nos 24 in a load carrier vehicle from Electrical installations at GE PANAJI area to workshop and returning back to site at its existing installation place all as specified and as directed. |
| 92 | M & L for transportation and lifting of transformer 11KV/433V of capacity upto 800 KVA including loading and unloading by suitable capacity crane to workshop for repair as per SI Item Nos 24 in a load carrier vehicle from Electrical installations at GE PANAJI area to workshop and returning back to site at its existing installation place all as specified and as directed. |
| 93 | M & L for transportation and lifting of transformer 11KV/433V of capacity upto 200 to 400 KVA including loading and unloading by suitable capacity crane to workshop for repair as per SI Item Nos 24 in a load carrier vehicle from Electrical installations at GE PANAJI area to workshop and returning back to site at its existing installation place all as specified and as directed. |
| 94 | M & L for transportation and lifting of transformer 11KV/433V of capacity upto 63 to 150 KVA including loading and unloading by suitable capacity crane to workshop for repair as per SI Item Nos 24 in a load carrier vehicle from Electrical installations at GE PANAJI area to workshop and returning back to site at its existing installation place all as specified and as directed. |
| 95 | M & L for replacement of copper winding wire for HT/ LT side of distribution transformer of voltage rating 11 KV/ 440Volt of rating up to 2000 KVA including taking down existing widing wire from burned out transformer complete all as directed. |
| 96 | Disconnecting and checking of the Transformer of 33/11KV at site disconnecting carefully and removing primary and secondary terminals , top cover , conservator tank, neutral earth strips and draining out transformer oil to the required level and storing carefully in cleaned containers , cleaning of terminals inspection of core, supply and replacing 5mm thick rubberised cork sheet gasket for tank top cover and replacement of gaskets/ oil seal , HT side bushings with stud, brass terminals , brass nuts and washers with insulators to arrest the leakage of transformer oil complete reassembling the complete dismantled items,reconnecting the HT supply cable ends at the site for the following transformers of capacity 2000 KVA complete all as specified and directed. |
| 97 | Carrying out replacement of all gasket set of top cover suitable for 63 KVA to 250 KVA Transformer using rubber cork sheet of 6.0 mm thick including providing gasket synthetic adhesive complete all as directed and specified. |
| 98 | Supply and Fixing in Replacement of HT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 63 KVA to 100 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 99 | Supply and Fixing in Replacement of LT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 63 KVA to 100 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 100 | Supply and Carrying out in replacement of all gasket set of top cover suitable for 800 KVA to 2000KVA Transformer using rubber cork sheet of 6.0 mm thick including providing gasket synthetic adhesive complete all as directed and specified. |
| 101 | Supply and Fixing in Replacement of HT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 200 KVA to 250 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 102 | Supply and Fixing in Replacement of LT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 200 KVA to 250 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 103 | Supply and Carrying out in replacement of all gasket set of top cover suitable for 63 KVA to 100 KVA Transformer using rubber cork sheet of 6.0 mm thick including providing gasket synthetic adhesive complete all as directed and specified. |
| 104 | Supply and Fixing in Replacement of HT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 400 KVA to 630 KVA Transformercomplete in all respect & all specified. Make : Same as Existing. |
| 105 | Supply and Fixing in Replacement of LT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 400 KVA to 630 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 106 | Supply and Fixing in Replacement of HT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 800 KVA to 2000 KVA Transformercomplete in all respect & all specified. Make : Same as Existing. |
| 107 | Supply and Fixing in Replacement of LT bushing with stud, brass terminal 6 Nos brass nuts and washers, gaskets, insulator etc suitable for 800 KVA to 2000 KVA Transformer complete in all respect & all specified. Make : Same as Existing. |
| 108 | Supply and Carrying out in replacement of all gasket set of top cover suitable for 150 KVA to 200 KVA Transformer using rubber cork sheet of 6.0 mm thick including providing gasket synthetic adhesive complete all as directed and specified. |
| 109 | Supply and Carrying out in replacement of all gasket set of top cover suitable for 250 KVA to 400 KVA Transformer using rubber cork sheet of 6.0 mm thick including providing gasket synthetic adhesive complete all as specified.and directed . |
| 110 | M & L for Shifting of Transformer from one Area/Pocket to another Area/Pocket or One Substation to another Substation by lifting/loading through Crane and Placing in position including installation, testing and commissioning as per site requirements complete all as specified and directed. |
| 111 | S & F in repair fixed type Air circuit breakers microprocessor based 4 pole 1000Amps breaking capacity 50 KA including all accessories and connection all as specified and directed by engr-In-charge. (Make:L&T or as existing) |
| 112 | Supply and filling of fresh transformer oil after filteration and dehydration conforming to IS-335/BS dielectric strength not less than 60 kV at the electrode gap of 4 mm in 60 Sec and topping up to the entire satisfaction of Engineer-in-Charge complete. Make : Gulf Oil / Power Oil |
| 113 | Dehydration and filtration of transformer oil by mechanical plant to achieve to dielectric strength of 60 KV at gap of 4 mm and re-filling the same (oil drained out before opening the transformer) completeNote :- (a) Dehydration plant to be brought at site by the contractor. (b) Dehydration and filtration to be carried out when the transformer is on load at site and rate quoted shall deemed to be included the cost of arrangement of plant by the contractor and its transportation at site.(c) Before and after filtration the transformer oil Dielectric strength to be tested and recorded by the Contractor and to be submitted to department |
| 114 | M & L for Painting with Preparation of surfaces of transformer, scratching old paint and spray two coats of synthetic enamel paint smoke grey colour (1st quality) over a coat of redoxide primer and writing MES No in “BLOCK LETTERS” with computerized black heat resistance tape complete all as specified. |
| 115 | All as per item No-52 above here and before for Painting of 4-Pole Structure of Steel Tubular Poles including all Cross arms and channels with 2 Coats of Enamel Paint all as specified and directed |
| 116 | All as per item No-52 above here and before for Painting of 4-Pole Structure of Cement Pole with weather coated Cement paint including all Cross arms and channels with two coats of Synthetic enamel paints all as specified and directed |
| 117 | Supply & Filling in in repair/ replacement of Silica Gel in existing Breather assembly as per required quantity of Silica gel for any model/capacity of Transformer 63 KVA to 630 KVA.(Make : MB Supplier/Pooja industries/Goyal electric works) |
| 118 | S&F in repair breather assembly complete with silica gel for 63 KVA/100KVA/200KVA/250KVA Transformer complete all as specified and as directed (Make : MB Supplier/Pooja industries/Goyal electric works) |
| 119 | S&F in repair breather assembly complete with silica gel for complete all as specified and as directed .400KVA/500KVA/630KVA Transformer complete all as specified and as directed .(Make : MB Supplier/Pooja industries/Goyal electric works) |
| 120 | S&F in repair of Temperature Gauge suitable for Transformer of capacity 63 KVA and upto 200 KVA complete all as specified and directed.(Make : MB Supplier/Pooja industries/Goyal electric works) |
| 121 | S&F in repair of Temperature Gauge suitable for Transformer of capacity 250 KVA and upto 400 KVA complete all as specified and directed.(Make : MB Supplier/Pooja industries/Goyal electric works) |
| 122 | S&F in repair of Temperature Gauge suitable for Transformer of capacity 500 KVA and upto 630 KVA complete all as specified and directed.(Make : MB Supplier/Pooja industries/Goyal electric works) |
| 123 | Material, Fabrication and Labour for Cross Arms, bracing,V Arms, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat and two under coat of synthetic enamel paint and incl removing rusted cross arm complete all as specified. |
| 124 | Supply and fixing Jumper of two Pole/Four Pole Structure with Aluminium Conductor Steel reinforced of any size on existing HT two Pole/Four Pole Structure using new binding wire including reconnecting all connections by means of suitable size lugs /thimbles including taking down old U/S conductor Jumper all as specified and directed by Engineer-in-charge |
| 125 | Taking Down/ Dismantling of 11KV insulators from site of any type and size all as specified and directed |
| 126 | Supply and fixing of pin type, porceline , vitreous, brown insulator including one Galvanised mild steel spindle,two galvanised iron washers and one galvanised iron nut of 150 mm height, 150 mm dia for 11000 volt grade all as directed by Engineer-in-charge |
| 127 | Supply and Fixing of Disc type insulator, Porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white, brown or green Single disc assembly tension with tension clamps for conductor working pressure 11000 Volts and incl removing old us insulators. Make: Bengal portries or equitant. |
| 128 | Supply and Fixing in replacement of 3-Peticoat insulator, Porcelain, vitreous of adequete size suitable for Transformer of 63 KVA to 800 KVA complete with removing/taqking down of old U/S insulators. Make: Bengal portries or equitant. |
| 129 | Supply and Fixing in replacement of 5-Peticoat insulator, Porcelain, vitreous of adequete size suitable for Transformer of 63 KVA to 800 KVA complete with removing/taking down of old U/S insulators. Make: Bengal portries or equitant. |
| 130 | Supply and Fixing of Loop type insulator, Porcelain, vitreous of large size with overall diamensions 90X140mm with clearance of hole 25.5mm white, brown or green Single disc assembly complete with removing/taking down of old U/S insulators. Make: Bengal portries or equitant. |
| 131 | M & L for Anticlimbing devices, spike type fabricated out of MS bars ( round square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the HT pole. |
| 132 | Supply and Stringing ACSR (Aluminium Conductor Steel Rein - forced) Conductor and incl removing old ACSR conductor complete. |
| 133 | M & L Cradles, hexagonal/rectangular,fabricated with galvanised steel wire 3.15 or 4mm dia |
| 134 | M & L for Galvanised Stranded 7/ 4 mm Stay strand wire including taking down old stay wire. |
| 135 | Taking down/Dismantling stay assembly complete (demolition of concrete, etc. and excavation measured separately) |
| 136 | M & L for Stay assembly complete with accessories such as MS Stay plate of size 300mmX300mmX600mm thick ,stay rod of 20mm dia,stay bow,nuts,bolts and check nuts of GI including GI stay strand of size 7/4 mm all as shown in electricalplate No. 1 of SSRPart -I of 2009 or as directed by Engr-In-ChargeNote:- Earth work, PCC,stay clamp and loop type insulator will be measured and paid separately in revant schedule of items. |
| 137 | M & L for Danger Notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts, and nuts of approved size for HT 25 x 20 cm and inc! removing old rusted danger boards complete. |
| 138 | Dismantling of HT over head lines ACSR conductor & Restringing to the required tension incl. Replacement worn out ACSR conductor, binding wires, Cross arms, Insulators, Clamps, nuts, bolts and washer etc, Note: ACSR Conductor, Cross arms, insulators, clamps, nuts, bolts and washers aremeasured and paid in respective items incl trimming / chopping of trees upto 5 mtr either side from center of OH line :Note:- 3/4 wire span shall be measured as one length- |
| 139 | M & L for Laying/ Loose filling of 40mm to 80 mm graded stone aggregate of Broken Stone/Boulders/Gravels for protection of cable in out side transframer base upto inside Boundry of the Outdoor Substations including taking down of old stone aggregate all as specified and directed.. |
| 140 | Supply and fix in repair of 11 KV HT busbar panel of 11 KV busbar support cylinderical type insulator 600 Amps complete as per existing model all as specified and as directed |
| 141 | M&L for XLPE insulated,screented,PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor,11000 volts,(Earthed)grade cross sectional area 95 sq mm including taking down old cable and bricks. |
| 142 | Supply and laying HDPE DWC Pipes of sizes160mmx135mm,IS-16205 (Part-24), ISI Marked, UV with UV Stabilized Certified for protection of HT U/G Cables including all fittings and fixtures complete all as Specified and directed. |
| 143 | M&L GI pipe 80 mm dia light grade for cable protection including taking down old GI pipe.(Make:Tata/Jindal/Prakash) |
| 144 | Excavating in trenches in hard/dense soil n exc 1.5m wide and n exc 1.5m in depth, for foundation etc or shafts,walls,cesspits,manholes,pier holes,etc.n exc 10 sqm on plan and n exc 1.5m in depth and getting out all as specified and as directed. |
| 145 | Returning,filling in,including spreading,leveling,watering and well ramming in layers not exc 25cm. |
| 146 | Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the strarting point. |
| 147 | M&L for PCC 1:3:6 type C2, using 40mm graded stone aggregate for Pole foundation,filling and mass concrete of poles all as specified and directed |
| 148 | M&L for PCC 1:4:8 type D2, using 40mm graded stone aggregate for Base foundation,filling and mass concrete of poles all as specified and directed |
| 149 | M&Lfor PCC block massonry 1:3:6 type C1, using 20mm graded stone aggregate with solid blocks,exc.10 cm in width and setting in mortar,complete including Coping/formwork , finishing ,plastering complete all as specified and directed. Please Enable Macros to View BoQ information |
| 150 | M&Lfor PCC block massonry 1:3:6 type C1, using 20mm graded stone aggregate with solid blocks,exc.10 cm in width and setting in mortar,complete including Coping/formwork , finishing ,plastering complete all as specified and directed. Please Enable Macros to View BoQ information |