| 1 | Excavating in trenches not exc 1.50 mtr wide and not exc 1.50 mtr in depth for taking out/laying of under ground cable, pole or stay and getting out in soft/loose soil, complete all as specified and as directed. |
| 2 | Returning filling in soft/loose soil, including, spreading, levelling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed. NOTE : The top of filled trench shall be made proud by using the excavated soil to cater for subsequent settlement of soil. |
| 3 | Removing excavated materials (soils) not exc 50.00mtr and depositing where directed at a level not exc 1.50 mtr above the starting point in soil, complete all as specified and as directed. |
| 4 | Supply and filling for dry sand in cable protection trenches before and after the cables are laid, for sand cushioning to cables complete all as specified and directed. NOTE : thickness after punning of sand shall be (minimum as specified in SSR) measured and paid in this item. |
| 5 | Material and labour for brick protection for UG XLPE cable with burnt clay old size sub class 'B' bricks laid dry and flat abutting each other with gaps between adjacent brick not more than 10mm and width equal to length of brick in trenches across the cable complete all as directed by Engineer-In-Charge.Make: Best quality locally available which is duly approved by GE. |
| 6 | Taking down exixting old unserviceable LT cable of any size |
| 7 | Supply and laying, connecting, testing, commissioning LT UG cable XLPE Insulated,armoured, electric power cables (heavy duty) 1100 Volts grade conforming to IS 7098 with aluminium conductor multi-strand laid in trenches / ducts/ inside protection pipe including cable glands, lugs and suitable size of MS saddle clips etc complete all as directed by Engr-In-Charge of following sizes:-Note:-(a) Excavation, sand cushioning, bricks shall be measured and paid separately |
| 8 | 2 core 10 Sqmm |
| 9 | 2 core 16 Sqmm |
| 10 | 3.5 core 25 Sqmm |
| 11 | 3.5 core 35 Sqmm |
| 12 | 3.5 core 50 Sqmm |
| 13 | 3.5 core 70 Sqmm |
| 14 | 3.5 core 95 Sqmm |
| 15 | 3.5 core 120 Sqmm |
| 16 | 3.5 core 150 Sqmm |
| 17 | Material and labour as in replacement for indoor/ outdoor type heat shrinkable cable end termination jointing kit for LT 1100 Volts (Earthed) grade cable of 70 to 150 Sqmm 3.50 core size complete with jointing material and accessories complete all as directed by Engineer-In-Charge |
| 18 | Supply and fix in replacement for tubes \\"light grade\\" galvanised with all fittings laid in trenches of complete all as specified and directed by Engineer-In-Charge of following sizes:-Note :- Excavation & earth work shall be measured and paid separately under respective items of this schedule. |
| 19 | 50 mm bore |
| 20 | 100 mm bore |
| 21 | M&L for horizontal boring under road, manually suitable for inserting 50 mm & 100 mm bore pipe at a depth 0.6 mtr to 1.5 mtr complete all as directed by Engineer-In-Charge.Note :- Excavation, earth work & GI pipe if any shall be measured and paid including this item |
| 22 | Welding work exc. 9 mm but n. exc. 20 mm running pipe line/ MS frame/ Feedar panel in any length and thickness not exceeding 20 mm in any position complete all as directed by Engineer-In-Charge |
| 23 | Supply and fix as in replacement following components/parts in existing LT panel boards/feeder pillar complete all as directed:- |
| 24 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 16 KA breaking capacity, rating 63 Amps including all fixing accessories with both ends spreader links |
| 25 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 16 KA breaking capacity, rating 100 Amps including all fixing accessories with both ends spreader links |
| 26 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 25 KA breaking capacity, rating 125 Amps including all fixing accessories with both ends spreader links |
| 27 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 36 KA breaking capacity, rating 160 Amps including all fixing accessories with both ends spreader links |
| 28 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 36 KA breaking capacity, rating 200 Amps including all fixing accessories with both ends spreader links |
| 29 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 36 KA breaking capacity, rating 250 Amps including all fixing accessories with both ends spreader links |
| 30 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 50 KA breaking capacity, rating 315 Amps including all fixing accessories with both ends spreader links |
| 31 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 50 KA breaking capacity, rating 400 Amps including all fixing accessories with both ends spreader links Please Enable Macros to View BoQ information |
| 32 | MCCB, adjustable type thermal magnetic release type,4 poles, 415 Volts, Adjustable overload setting 0.8-1.0 x in and adjustable short circuit setting 5-10 x in, Lcu = 50 KA breaking capacity, rating 400 Amps including all fixing accessories with both ends spreader links Please Enable Macros to View BoQ information |