| 1 | Supply and fixing or passing through pipe, stranded conductor 6 Sqmm, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers no more than 1 meter apart including 4 mm suspension wire, one twin core cable flat or circular etc complete all as specified and directed. |
| 2 | All as per item No. 1 here in before, but 10 Sqmm. |
| 3 | All as per item No. 1 here in before, but 16 Sqmm. |
| 4 | Supply , laying , connecting, testing and commissioning 300 Sqmm 3.5 core under ground LT cable XLPE insulated screened, PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor 1100 Volts laid in trenches, fixed to walls/ drawn through pipe and including the disturbence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc complete all as specified and directed.Note;-(Excavation, earthwork sand cushioning and cable protection shall be measured and paid for separately.) |
| 5 | All as per item No. 4 here in before, but 150 Sqmm 3.5 core |
| 6 | All as per item No. 4 here in before, but 70 Sqmm 3.5 core |
| 7 | All as per item No. 4 here in before, but 50 Sqmm 3.5 core |
| 8 | All as per item No. 4 here in before, but 35 Sqmm 3.5 core |
| 9 | All as per item No. 4 here in before, but 16 Sqmm 2 core |
| 10 | Supply, laying, connecting, testing and commissioning of 95 Sqmm 3 core earthed system underground HT XLPE insulated screened, PVC bedded, armoured heavy duty electric cable with stranded aluminium conductor 11000 Volts laid in trenches, fixed to walls/ drawn through pipe with suitable size glands, crimping type lugs and including the disturbed surface of road making good with using PCC etc all as specified including dismantling of old U/S cable.Note;-(Excavation, earthwork send cushioning and cable protection shall be measured and paid for separately.) |
| 11 | Excavation in trenches not exceeding 1.5 mtr wide, depth exceeding 1.5 mtr and getting out in hard/dense soil complete all as specified and directed by Engineer-in-charge |
| 12 | Returning, filling including spreading, levelling, watering and well ramming in layers not exc. 25 cm in hard/dense soil all as specified and directed. |
| 13 | Removing excavated material (soil) not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. |
| 14 | M&L for dry clean sand filling in trenches below and around underground cable cushioning complete all as specified and directed. Note: - Thickness of sand cushioning shall be measured after punning. |
| 15 | Supplying and laying un-reinforced precast concrete cable cover class LV type 1 flat size 250x150mmx40mm complete all as specified and directed. |
| 16 | Dismantling of Steel poles including demolition of coping and levelling of ground and making surface dressing as required or as per direction of Engr-in-Charge complete all as specified and directed. |
| 17 | Dismantling of cross arms/bracings of MS Sections channel or angle sections etc., complete all as specified and as per direction of Engr-in-Charge. |
| 18 | Dismantling of insulators any type, any size as required and as per direction of Engr-in-Charge complete all as specified and directed. |
| 19 | Dismantling/Taking Down old U/S lightning arresters any size as required and as per direction of Engr-in-Charge complete all as specified and directed. |
| 20 | Dismantling/Taking Down old U/S GI wire 4 mm dia on HT electric lines including binding, jointing and for guarding cradle or distributor span as per direction of Engr-in-Charge complete all as specified and directed. |
| 21 | Supply, fixing, transporting, erecting and fixing steel tubular swaged pole type 410 SP- 31 (11 metres long) complete with cast iron base plate, finial taper plug MS bolts, and washers including two coats of aluminium paint over a coat of red oxide primer to external surfaces of steel tubular pole and two coats of anti-corrosive bituminous paint internally and externally up to planting depth of pole and providing 3 bands/ straps with paint red post office colour and 2 bands with black synthetic enamel paint 300mm from plinth block and marking pole No. with black synthetic enamel paint and feeder location of Pole including dismantling of existing damaged steel pole/struts etc complete all as specified and directed. |
| 22 | M&L for mild steel work Fe-410-S grade in cross arms, bracing, support, clamps and back plate, fabricated from structural steel section including nuts bolts and washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and including two coats of aluminium paint over a coat of red oxide primer including dismantling cross arms of mild steel channel or angle section etc complete all as specified and directed. |
| 23 | Supply and fixing pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed by Engr-in-charge. |
| 24 | Supply and fixing shackle type, porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts in repair insulators suitable for working pressure in 11000 volts of height 150mm and max dia 150mm along with galvanised steel fittings section of straps in 38x5mm and dis of bolts 20mm complete all as specified and directed by Engr-in-charge. |
| 25 | M&L in repair of disc type insulator porcelain vitreous 145mm high and 255mm dia ball and socket type white brown or green single disc assembly for tension with tension clamps for conductors working pressure 11000 volts complete all as specified and directed by Engr-in-Charge. |
| 26 | M&L for stringing, drawing of GI wire 4 mm dia on HT electric lines including binding, jointing and for guarding cradle made to shape hexagonal/rectangular or any shape fabricated etc complete all as specified and directed. |
| 27 | M&L in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letter figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 25x20cm size etc complete all as specified and directed. |
| 28 | M&L for lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 Kilo amp, HT 11000 Volts grade complete all as specified and directed. |
| 29 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm all as specified and directed. |
| 30 | All as per item No. 29 here in before, but 120 sqmm to 185 sqmm. |
| 31 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm all as specified and directed. |
| 32 | All as per item No. 31 here in before, but 120 sqmm to 185 sqmm. |
| 33 | M&L for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm all as specified and directed. |
| 34 | All as per item No. 33 here in before, but 120 sqmm to 185 sqmm. |
| 35 | Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 KV for electrical purpose as per IS 15652-2006, (Superseding IS 5424) suitable for electrical shock safety of size 2m x 1 m complete all as specified and directed. |
| 36 | M&L for providing earthing with Copper earth plate electrode 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the earth plate not less than 1.5 M below ground level connected to Copper strip 32 x 6mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate No 3 of SSR-2009 part 1, including necessary excavation and earth work in any type of soil, comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh, PCC pit with CI cover and frame etc complete all as specified and directed by Engr-in-Charge.Note: -(i) All the joints shall be made with welding to get proper conductivity. (ii) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. (a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1. (c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm. (d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering. (f) Requisite quantity of common salt and charcoal. (g) Testing of earthing. Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. |
| 37 | M&L for earthing complete with galvanised steel, earth plate electrode 600x600mm x 6mm thick burried directly in ground verticaly (earth pit not less than 2.25 mtrs below ground level ) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanised strip 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electrical plate No 3 on page 497 of MES schedule 2009 part - I connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handle to cover, GI protection pipe 40mm dia light grade up to 7.5mtr from electrode GI pipe to be fixed with complete all as specified and directed. Note :- (i) Earth lead beyond 7.5 mtr from electrode to earth terminal point/main switch & GI pipe light grade 40mm dia for protection against mechanical damage to lead shall be measured separately. (ii) On testing after completion if desired earth resistance is not obtained, the earthing will be redone at no extra cost. |
| 38 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3mm copper strip complete all as specified and as directed. |
| 39 | M&L in repair to burnt transformer upto capacity 630 KVA indoor/outdoor type 11 KV / 440 volts removing HT & LT cable connection from transformer and taking into the workshop with the help of man power, crane, truck, TPT etc opening the top cover lifting the core removing sludge with oil pressure pump, repair of burnt/damage winding of suitable size including core limb, insulating material, applying two coats of insulation paper/varnish etc and put in the oven for 24 hrs and cleaning the tank sludge etc. After completion of the job, transformer tests to be carried out that is no load test short circuit test and oil colour test to be done at factory in the presence of Engineer -in- charge. Any damages of bushes and studs to be replaced. Shifting the transformer from workshop to substation etc complete all as specified and directed.Note: - (i) Spare parts measured and paid separately.(ii) Standby transformer suitable KVA should be provided by contractor at the site for uninterrupted supply and the cost/rent of standby deemed to be including in repairing cost and no extra payment shall be made on this account. |
| 40 | Supply and fixing in repair HT busing 11 KV upto capacity 630 KVA complete all as specified and directed. |
| 41 | Supply and fixing in repair LT busing 11 KV upto capacity 630 KVA complete all as specified and directed. |
| 42 | Supply and fixing in repair HT brass studs 11 KV capacity 315 KVA to 630 KVA complete all as specified and directed. |
| 43 | Supply and fixing in repair HT brass studs 11 KV upto capacity 250 KVA complete all as specified and directed. |
| 44 | Supply and fixing in repair LT brass studs 11 KV capacity 315 KVA to 630 KVA complete all as specified and directed. |
| 45 | Supply and fixing in repair LT brass studs 11 KV upto capacity 250 KVA complete all as specified and directed. |
| 46 | Supply and fixing new breathers upto capacity 630 KVA complete all as specified and directed. |
| 47 | Supply, fixing and commissioning of copper winding wire of transformer complete removing job/core inside of body and refixing same after rewinding of burn winding complete all as specified and directed. |
| 48 | Dehydration and filtration of transformer oil of distribution transformer any capacity indoor/outdoor type at various location to achieve di-electric strength not less than 60KV with dehydration machine including checking of electric strength of transformer oil before and after dehydration complete all as specified and directed. |
| 49 | Supply and topping up of transformer oil with die-electric strength not less than 60 KV in to conservator tank / Body tank of the transformer etc. complete all as specified and directed. Make- Power oil or equivalent as approved by GE. |
| 50 | Preventive maintenance of transformer 63 to 630 KVA indoor/outdoor type 11 KV / 440 volts following repairs complete all as specified and as directed.[a] Draining out transformer in the suitable capacity of container / drums and keeping it in safe custody for reuse.[b] Lifting, transporting & handling the transformer to the work shop and opening top cover of the transformer by unscrewing nuts / bolts / washers etc. including disconnecting core assembly from HT / LT bushing and lifting the same gently with the help of crane and taking out from the shell [Container / Body] of the transformer.[c] Visual inspection of entire Core Assembly, Transformer Tank, Core Limbs, OLTC etc., locating the fault / damages.[d] Cleaning the transformer body from inside, removing deposited dirt / sludge / foreign particles etc. from the bottom / body of the transformer, cleaning with CTC and drying up the shell from inside before refilling with the Transformer Oil.[e] Cleaning and washing thoroughly core and serviceable windings of the transformer by hosing down with clean dry oil conforming to IS – 336, removing deposited dirt / sludge / foreign particles from the windings / core through inspection of windings, providing insulations to leads and terminals complete and re-assembling the core including newly winded coils etc. |
| 51 | Item No. 50 (contd….) [f] Heating / drying / baking complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc all as per IS.[g] Lifting and refixing core assembly inside the transformer shell gently and carefully connecting Primary / Secondary / Neutral Terminal Connections to the bushings assembly, fixing of Tap changer including tightening of nuts, bolts, washers of the core to reduce humming noise.[h] Refilling the filtered transformer oil in the shell of transformer complete.[i] Refixing the top cover including replacement of Cork Sheet / Gasket 8 mm thick tightening of nuts / bolts / washers etc. and replacement of Breather with Silica Gel.[j] Lifting / Shifting to the place from where removed and re-installing the transformer including connecting Primary / Secondary / Neutral connections etc.[k] The inspection of transformer shall involve Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts, checking all brazing, joints, tap heads and connection joints, checking all jumpers, terminations / connections inside the transformer and Checking the Bucholtz Relay / Conservator MOG if any. Note: - Standby transformer suitable KVA should be provided by contractor at the site for uninterrupted supply |
| 52 | Taking down HT Switchgear [Vacuum Circuit Breaker] of capacity 630 KVA for carrying out following Repairs, Overhauling, Servicing, Preventive Maintenance and refixing the same after Repairs / Overhauling complete all as specified and as directed:[a] Tripping off the breaker, lowering the breaker with raising / lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing / inspection / overhauling.[b] Servicing / Inspecting / checking of Automatic Safety Shutter operation for serviceability and replacement of spares if required.[c] Servicing / Inspecting / checking of circuit spout and circuit spout connections for RYB Phases and replacement of spares if required.[d] Dismantling and checking of Crossbar Assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc.[e] Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism.[f] Servicing / Inspecting / checking of Secondary Sockets / Busbar Earthing Plugs / Earthing Sockets and replacement of spares if required.[g] Checking, setting and adjustment of lowering and raising operation of the Breaker Trolley.[h] Decarbonising of Busbar and connected items |
| 53 | Item no 51 (contd....) [i] Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly.[j] The inspection of HT switch gear shall involve Inspection of Truck & Hoist Assembly, Tank Assembly & Barriers, Assembly & components of Solenoid Assembly, Assembly & components of Dependent Mechanism, Assembly & components of Spring Box Mechanism, Motor Mechanism Spring Charge Assembly and Assembly of Trip Unit & related components in full satisfaction of Engr-in-charge and inclusive of one primer coat with red oxide one under coat , one finishing coat with aluminium paint complete all as specified and directed.(k) Certificate to be provided by OEM after completion of VCB Servicing.Notes:- [a] The rate quoted shall be deemed to be include for necessary T & P, nuts, bolts, washers, gasket, insulation tape, compound, all as per existing etc. to put in to the VCBs and Panels in serviceable condition, testing and commissioning all as specified and as directed.[c] Major spares will be measured and paid separately under relevant items of this BoQ. However, the rate quoted shall be deemed to be include for any other minor spares requires replacement.[d] The servicing shall be carried out by Authorised Service Centre as approved by GE. |
| 54 | S&F in repair voltmeter 500 volts squire type 96 mm including connecting and testing complete all as specified and directed. |
| 55 | S&F in repair amp meter 0-100 amp rotary selector switch all 3 way direct reading type complete all as specified and directed. |
| 56 | S&F in repair LED type indicating lamps with holder as per existing at site complete all as specified and directed |
| 57 | Supply, Install, Testing and commissioning of REF 615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 64R, 67, 67N, 27, 59, 59N, 25, 81U, 81O, df/dt, 95, Measurement for 3I, I0, 3U, U0, Kw, KVA, PF, Hz, KWH, 12 DI + 10 DO, One front RJ45 Port, One Rear RS485 Port for Modbus Protocol, Draw out Type with CT Shorting feature, Small LCD Display feature including taking down old relay of any description complete all as specified and as directed by Engr-in-Charge. |
| 58 | Supply and fixing in repair of CT's ratio 120/60/5A and any size/capacity as required on site, suitable for VCB under repair with number of poles including wiring upto indicator display board etc complete all as specified and directed. |
| 59 | Supply and fixing in replacement of Voltage Transformer (PT) for indoor type VCB ration -11000/110 volt as per existing model and capacity complete and any size/capacity as required on site, suitable for VCB with number of poles including wiring upto indicator display board etc complete all as specified and directed by Engr-in-Charge. |
| 60 | Supply and fixing Spring Chargin Motor with Gearbox Universal Motor with Gearbox 230AC/DC 110V AC/DC complete with all accessories complete all as specified and directed. |
| 61 | S & F in repairs Space Heater in HT VCB, 11KV Suitable for operation on 220 volts, AC Supply complete with necessary wiring and control cable with Toggle Switch complete all as specified and as directed. |
| 62 | M&L for scraping down the existing deteriorated old aluminium paint by iron brushing and painting of four pole structure with one coat of (metal primer) and two coat of aluminium paint over exposed portion including cross arms, angles, nuts bolts clamps & junction box of above PCC coping and painting to steel tubular HT poles with two coats of synthetic enamelled paint upto 1.5 m height above from ground level/plinth block (in yellow and black strips of 30 cm wide each) complete all as required on site and directed. |
| 63 | M&L for scraping down the existing deteriorated old aluminium paint by iron brushing and painting of two pole structure with one coat of (metal primer) and two coat of aluminium paint over exposed portion including cross arms, angles, nuts bolts clamps & junction box of above PCC coping and painting to steel tubular HT poles with two coats of synthetic enamelled paint upto 1.5 m height above from ground level/plinth block (in yellow and black strips of 30 cm wide each) complete all as required on site and directed. |
| 64 | M&L for Repair of Gang operated air break switch 11 KV , 400 Amps, each pole consisting of galvanised steel base HT insulator as per BSS/ ISS non- ferrous knife and spring loaded contacts, arching arms of adequate section to break magnetizing current \\" TILTING TYPE\\" complete with square shaft of GI, adequate length for phase separation , operating handle complete set conforming to IS : 1818 with suitable clamp , nuts, bolts complete for fixing on the existing channel, making all electric connections/ Jumpers with bottle lugs commissioning and testing complete all as directed. |
| 65 | M&L for old painted steel and iron surfaces and painting to steel tubular HT poles with two coats of synthetic enamelled paint upto 1.5 m height above from ground level/plinth block (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 m height of poles including painting on cross arms, bracing, clamps etc and writing pole Nos with thick black synthetic enamel paint complete all as specified and directed. |
| 66 | M&L in repair for HT underground cable Fault locating instrument suitable to locate and pin point fault in HT cables upto 11 KV and make the cable in operation condition including provision of jointing material which is required on site except cable joint kit, excavation in trenches upto depth of cable, returning filling and removing the extra material on site after completion of work complete all as specified and directed by Engr-in-Charge. |
| 67 | Tightening/restringing existing loose/broken conductor ACSR/ copper any type of size and GI wire including strengthening of HT overhead lines including binding with suitable binding wire and jointing jumpers as required at site and all as specified and directed. |
| 68 | Supply and replacement of silica-gel (dehydrating agent) in position on transformers installed at various location at Haldwani all as specified and directed. |
| 69 | Trimming of trees all as along the HT/LT line in such a way that there is clear distance of 3.00 mtr between tree and electric line including stringing stretching and strengthening of overhead loose conductor (ACSR) on existing HT steel tubular pole or RS joist HT electric pole including binding and jointing the conductor with and including 14 SWG winding wire etc. The work will be executed to the entire satisfaction of Engineer-in-charge irrespective of the size of the tree branches etc complete all as specified and directed.Note: - (1) Tree branches will be left as it is the wood belong to cantt board/DO. They will be responsible for the wood. (2) Contractor will deploy sufficient labour to complete the full one job within 15 days.(3). Contractor will be responsible for any type of accident while trimming the trees. (4) Contractor supervisor will take proper sit down for MES installation before starting the work and clear it before resuming power supply, however full assistant will be provided by MES staff. |
| 70 | M&L in replacement of Epoxy insulators in VCB 630Amps complete all as specified and directed by Engr-in-Charge. |
| 71 | Supply, installation, commissioning and testing of switch Air break, Gang operated with 12 insulator switch triple pole mechanically operated, mounted on insulator and steel frame, with mechanism worked from ground level, for current rating 400 Amps operating voltage 11 KV out door type vertical mounted type complete with locking arrangement , assembly with fuse mount carrier and fuse element of required capacity and isolate suitable for 11 KV including necessary electric connection and 11 KV fuse (drop out type) of capacity 10 Amp complete with DO fuses assembly operating Rod of 25 mm dia bore grade GI Pipe of suitable length worked out from ground level and handle complete with lock and two nos keys including flat iron clamp 50 mm x 6 mm MS Channel of suitable size & length for fixing GOD including nut, bolt, washers including taking down existing set all as directed by Engr-in-Charge. |
| 72 | M & L for providing PCC 1:4:8, type D-2 (using 40mm graded stone aggregate) in base of pole of size 1200mm X 600mm X 200mm complete all as specified and directed |
| 73 | M & L for providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) in foundation (1200mm x 600mm x 1800 mm (sub base as mass concrete) for concrete encasing the pole up to GL or struts, stay etc or other necessary form work all as directed and specified. |
| 74 | M & L for providing PCC 1:2:4, type B-1 for coping (using 20 mm graded stone aggregate) of Existing /New electric pole for plinth block/Collar above GL, 300 mm high and 450 mm x 450 mm square or as directed by Engr-in-Charge including Dismantling old coping in pole complete all as specified and directed. |
| 75 | M&L in replacement of Tripping Coil (24V DC) in VCB 630Amps complete all as specified and directed by Engr-in-Charge. |
| 76 | M&L in replacement of Closing Coil (24V DC) in VCB 630Amps complete all as specified and directed by Engr-in-Charge. |
| 77 | M&L in replacement of Power pack 110-volt AC to 24-volt DC in VCB 630Amps complete all as specified and directed by Engr-in-Charge. |
| 78 | M&L for GI tubing light grade 80 mm bore for cable protection laid in trenches/fixed to wall, poles including MS flat iron, clamps, nuts, bolts, etc complete all as specified and directed. |
| 79 | M&L for MCCB 4 pole 415V adjustable type 160 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge. |
| 80 | M&L for MCCB 4 pole 415V adjustable type 200 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge. |
| 81 | M&L for MCCB 4 pole 415V adjustable type 250 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge. |
| 82 | M&L for MCCB 4 pole 415V adjustable type 400 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge. |
| 83 | M&L for MCCB 4 pole 415V adjustable type 630 Amps with breaking capacity 50 KA complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 84 | M&L for MCCB 4 pole 415V adjustable type 630 Amps with breaking capacity 50 KA complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |