| 1 | PART A: SITC OF UPS |
| 2 | 30 KVA |
| 3 | SITC of 30 KVA DSP Controlled, PWM Technology, IGBT based Rectifier & Inverter 3 Phase I/P & 3 Phase O/P with Built in Isolation Transformer (1:1) at Inverter OutPut , Double Conversion True Online UPS System, with following Key features: [Make: Power One/ APC/ Numeric/ Vertiv/ Powersafe/ Delta/ Bettter Power/ Prostarm] |
| 4 | (i) Wide input voltage range (340–460V) |
| 5 | (ii) VFI, Online Double Conversion Topology |
| 6 | (iii) DSP controlled IGBT Based |
| 7 | (iv) High efficiency (Min 90% at 100% load) |
| 8 | (v) High output PF (0.9) and less THDi (<3%) Active input Pf correction system to obtain 0.9 lag at 100 % Resistive Load |
| 9 | (vi) High Power density design, smaller footprint |
| 10 | (vii) Best in class Flexible DC Bus |
| 11 | (viii) Input Phase Sequence Protection |
| 12 | (ix) Output: Pure Sin Wave Crest Factor 3:1 |
| 13 | (x) Capable of operating at 50 degree centigrade ambient temperature |
| 14 | (xi) The UPS should have external automatic load transfer switch for parallel operation. |
| 15 | (xii) Ingress Protection (IP): IP21 |
| 16 | (xiii) The UPS should have Static Bypass Arrangement |
| 17 | (xiv) Certificate: ISO 9001:2015, ISO 14001:2015, ISO 18001, OHSAS 18001, CE Certification : IEC/EN 62040-1-1, IEC/EN 50091-1-1, IEC/EN 50091-1-2, IEC/EN 62040-2 (Electromagnetic Compatibility (EMC) emission and immunity requirements for UPS), IEC 62040-3 (International standard defining performance and test requirements for UPS), IEC/EN 61000-4 (EMC immunity testing) & IEC/EN 60146 (Design & Manufacture) |
| 18 | Batteries |
| 19 | 12V, SMF VRLA [Flame-retardant ABS (FR-ABS) body] battery bank. Total minimum VAH 28000 to provide 30 mints backup, along with suitable Rack & interconnection with suitable size of copper wire (45 AH to 125 AH). [Make: Exide Powersafe Plus/ Amara Raja Batteries Limited (ARBL)/ Amaron Quanta] , (Warranty- One Year on both UPS & Batteries on site against any manufacturing defects) |
| 20 | 15 KVA |
| 21 | SITC of 15 KVA DSP Controlled, PWM Technology, IGBT based Rectifier & Inverter 3 Phase I/P & 3 Phase O/P with Built in Isolation Transformer (1:1) at Inverter OutPut , Double Conversion True Online UPS System, with following Key features: [Make: Power One/ APC/ Numeric/ Vertiv/ Powersafe/ Delta/ Bettter Power/ Prostarm] |
| 22 | (i) Wide input voltage range (340–460V) |
| 23 | (ii) VFI, Online Double Conversion Topology |
| 24 | (iii) DSP controlled IGBT Based |
| 25 | (iv) High efficiency (Min 90% at 100% load) |
| 26 | (v) High output PF (0.9) and less THDi (<3%) Active input Pf correction system to obtain 0.9 lag at 100 % Resistive Load |
| 27 | (vi) High Power density design, smaller footprint |
| 28 | (vii) Best in class Flexible DC Bus |
| 29 | (viii) Input Phase Sequence Protection |
| 30 | (ix) Output: Pure Sin Wave Crest Factor 3:1 |
| 31 | (x) Capable of operating at 50 degree centigrade ambient temperature |
| 32 | (xi) The UPS should have external automatic load transfer switch for parallel operation. |
| 33 | (xii) Ingress Protection (IP): IP21 |
| 34 | (xiii) The UPS should have Static Bypass Arrangement |
| 35 | (xiv) Certificate: ISO 9001:2015, ISO 14001:2015, ISO 18001, OHSAS 18001, CE Certification : IEC/EN 62040-1-1, IEC/EN 50091-1-1, IEC/EN 50091-1-2, IEC/EN 62040-2 (Electromagnetic Compatibility (EMC) emission and immunity requirements for UPS), IEC 62040-3 (International standard defining performance and test requirements for UPS), IEC/EN 61000-4 (EMC immunity testing) & IEC/EN 60146 (Design & Manufacture) |
| 36 | Batteries |
| 37 | 12V, SMF VRLA [Flame-retardant ABS (FR-ABS) body] battery bank. Total minimum VAH 15000 to provide 30mints backup, along with suitable Rack & interconnection with suitable size of copper wire (45 AH to 125 AH). [Make: Exide Powersafe Plus/ Amara Raja Batteries Limited (ARBL)/ Amaron Quanta] , (Warranty- One Year on both UPS & Batteries on site against any manufacturing defects) |
| 38 | PART B: ALLIED ELECTRICAL WORKS |
| 39 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required [Make: Finolex/RR Kable/Polycab/Havells/ KEI/ Gloster] |
| 40 | 4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC |
| 41 | 4x84/0.3 (6 sqmm) + 2x56/0.3 (4 sqmm) as ECC |
| 42 | Supplying and fixing PVC Rigid Conduit 'FR' on wall, ceiling with saddles and other accessories as required and mending good damages to building works [Make: Precision / AKG / ATUL/ VIP /Universal /BEC /Polypack] |
| 43 | 25mm size |
| 44 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes |
| 45 | 4 sqmm |
| 46 | 6 sqmm |
| 47 | 10sqmm |
| 48 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection [Make: Legrand/ Schneider /Siemens/ABB] |
| 49 | 63 A FP |
| 50 | 25 A FP |
| 51 | 6-32 A SP |
| 52 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment [Make: Legrand/ Schneider /Siemens/ABB] |
| 53 | 4 way |
| 54 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [Make: Legrand/ Schneider /Siemens/ABB] |
| 55 | 4 way |
| 56 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection [Make: Legrand / Schneider /Siemens/ABB] |
| 57 | 63A FP |
| 58 | Notei) The agency must procure the materials from the manufacturer / OEM or from their authorized sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 59 | ii) Documents that authenticates such procurement form the manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-charge and hard copy of it to be submitted during execution of work / submission of bill. |
| 60 | iii) If any refurbished material is supplied and installed, penal action will be taken as per existing rules.(One year spare & maintenance warranty after commissioning of the UPS to be provided; security deposit will be released after one year of commissioning date, DLP period 1 (one) year, AGENCY / CONTRACTOR / OEM HAS TO ATTEND AND RECTIFY FAULT(S) WITHIN 24 HOURS OF RECEIPT OF COMPLAINT. CERTIFICATE IN THIS REGARD IS TO BE UPLOADED.) Please Enable Macros to View BoQ information |