| 1 | 10-PASSENGER LIFT - WITHOUT MACHINE ROOMSITC of Automatic Lift ( as per manufacturer design & as per detailed specification below conforming to IS ) and putting into operation after final testing in the existing lift shaft complete with all accessories and repairing the damage wall / floor if any etc to complete as reqd. |
| 2 | Make : OTIS / KONE/SCHINDLER |
| 3 | Type: passenger Lift . |
| 4 | Load : 10Passenger/680Kg |
| 5 | Control : Microprocessor based with AC variable voltage & variable frequency ( VVVF) (Simplex Full Collective Control) |
| 6 | Machine -- Energy efficient machine, Gearless, with Out Machine Room. [ MRL] |
| 7 | Position of Machine Room - NA |
| 8 | Speed:- 1Mtrs/Sec |
| 9 | Floor served :- G+2 |
| 10 | Landing: 03 (Three), all on same side |
| 11 | Total Rise -9.8Mtr |
| 12 | Operation : Microprocessor based simplex full collective with or without attendant. (Simplex Full Collective Control) |
| 13 | Signals : Digital car position indicator,car travelsdirection indicator in car & at all landing with call registration indicator.Buttons: all buttons on car & landing shall be luminous & encoded with braille |
| 14 | Leveling accuracy : ±5mm Micro levelling arrangement |
| 15 | Car inside : -1300 mm wide x 1350 mm deep x 2200 mm high |
| 16 | Car Entrence : Clear opening 800mm (W) x 2000mm (H) protected with car door. |
| 17 | Car Encloser : Stainless Steel Sheet (20 SWG) with hairline finish with hand rail. (Stainless steel Hairline AISI441) |
| 18 | Car ceiling & Lighting : Stainless steel with hairline finish with LED lighting & fan |
| 19 | Car Ventilation- Pressure fan with anodized aluminium grill. |
| 20 | Car Flooring: Decorative granite flooring (As per direcion of EIC and according to this Department's Order). |
| 21 | Car Door : Stainless Steel centre opening automatic door (COPD) provided with V3F controlled door drive system |
| 22 | Landing Door- Stainless steel centre opening door operated synchronizing with car door. Two-panel centre opening Plain Panel. |
| 23 | Door Opening - Automatic power oprated door with full length PhotoceL assembly light curtain sensor |
| 24 | PROTECTIVE DEVICES & OTHER ACESSORIES |
| 25 | ARD- Automatic rescue device complete with dry maintenance free batteries as required. for automatic evacuation to the nearest floor in case of power failure / single phasing/others. |
| 26 | Overload Protection -Fully loaded with overload protection. On overloading the lift car will not start with door remaining open and give audio & display indication |
| 27 | Emergency lighting in car- Battery operated emergency lighting in the lift car. |
| 28 | Intercom system : Battery operated intercom system in Lift Car, Machine Room & Control Room |
| 29 | Emergency Alarm: Battery operated alarm bell system in lift car and control room |
| 30 | Fireman switch - Fireman switch at main landing terminal. |
| 31 | Voice Synthesizer: Voice announcement system (Voice Synthesizer) in the car to announce the position of the elevator in the hoist way as the car passes or stops at a floor served by the elevator. |
| 32 | Main rope/Belt - As per manufacturer's standard conforming to IS |
| 33 | DIMENSION OF SHAFT & POWER SUPPLY |
| 34 | Available Shaft Dimension 1900 mm (Wide) X 1680mm(Depth) |
| 35 | Pit Depth : 1600mm |
| 36 | Overhead : 4500 mm |
| 37 | Electric power supply AC 415 Volt 3phase, 50 Hz, terminated in machine room as per IS |
| 38 | N.B. i) The rate quoted by the manufacturer should be inclusive of cost for providing 2 years DLP after completion of 1 year of intial commissioning |
| 39 | ii) Rates should be quoted with minor Civil works. Wall cutting and mending good the damages to the original finish. |
| 40 | Terms and Conditionsi) The Agency must procure the materials from the Manufacturer / OEM or from their authorise sales channel so that the standard warranty / Supportof of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.ii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work /submission of bill iii) If any refurbished material is supplied and installed penal action will be taken as per existing rules. |
| 41 | [ Rates should be Quotated inclusive of all taxes & duities and L.W.C. @ 1% as applicable ] Please Enable Macros to View BoQ information |