| 1 | Supply & Delivery of commercial Grade conceal Non inverter Split Air conditioner (IDU&ODU) with fully metal enclose IDU having following specification: Minimum Cooling Capacity: 6900WIS Compliance- IS 1391Refrigerant- R410A/R32Compressor - Rotary/scrollEvaporator & Condenser Coil: Copper (LCD (wireless / wired Remote) and All other accessories Operating outdoor Temperature - 50°C and above Power supply - 240 V,50Hz(+ Tolerrance as per applicable standard.Make:- Daikin / Hitachi / Voltas / Bluestar |
| 2 | Supply & Delivery of commercial Grade conceal Non inverter Split Air conditioner (IDU&ODU) with fully metal enclose IDU having following specification: Minimum Cooling Capacity (W) - 5000W IS Compliance- IS 1391Refrigerant- R410A/R32Compressor - Rotary/scrollEvaporator & Condenser Coil: Copper (LCD wireless / Wire Remote) and All other accessories Operating outdoor Temperature - 50°C and above Power supply - 240 V,50Hz(+ Tolerrance as per applicable standard.Make:- Daikin / Hitachi / Voltas / Bluestar |
| 3 | Installation Testing & commissioning of the above Said Split Acs incl. Supply & fixing required Angle iron structure on wall for placing outdoor unit and mending Good the damages as per direction of EIC |
| 4 | SITC of commercial Grade conceal Non inverter Split Air conditioner (IDU&ODU)with fully metal enclose IDU having following specification [all necessary accessories for hanging indoor & outdoor unit as per site condition & As per Direction of EIC]: Minimum Cooling Capacity: 14000W IS Compliance- IS 1391Refrigerant- R410A/R407C/R32Compressor - Rotary/ ScrollEvaporator & Condenser Coil: Copper CFM/Tr - 400 LCD wirless / wired Remote and All other accessories operating outdoor Temperature - 45°C and above Power supply - 415 V 3-Ph,50Hz (+ Tolerrance as per applicable standard)Safety Features: Overheating protection for compressor, LP HP cut out, single phase prevensionMake:- (Daikin / Mitshubishi Heavy / Voltas/Hitachi ) |
| 5 | REFRIGERANT PIPING WITH INSULATIONSupply & Laying Hard / Soft drawn Copper Refrigeration pipe line for liquid and suction line suitable for R410A/R407C refrigerant & 19 mm thick Nitrile Rubber 'class O' Insulation tube with supports & brackets as per direction of EIC. |
| 6 | Liquid Line (3/8\\" dia) without rubber insulation (make: Rajco / Mandev / Royku) |
| 7 | Suction Line (5/8\\" dia) with 19 mm thick nitrile rubber insulation Al foil covered (make: Rajco / Mandev / Royku) |
| 8 | Supply and fixing of necessary electrical arrangements of Air Conditioning Units, PVC insulated FRLS grade Copper cable for connection betweeen indoor and outdoor units, 1.1 KV grade. 3 core x 2.5 mm² (Make- RR Kable / Finloex / Polycab). |
| 9 | Supply and fixing of necessary electrical arrangements of Air Conditioning Units, PVC insulated FRLS grade Copper cable for connection betweeen indoor and outdoor units, 1.1 KV grade. 4 core x 2.5 mm² (Make- RR Kable / Finloex / Polycab). |
| 10 | S & Installation of Extra Add-on Items- HVAC grade 5/8\\"(for suction) & 1/4\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle, screws, insulation tape, fasner etc for above AC machines as per direction of EIC. |
| 11 | Supply & Laying 1.1KV grade 3 core 4 sqmm flexible copper cable with screw, saddle drill machine nut bolt etc all necy. items needed for connection.(from starter to AC outdoor connection)(Make: Havells/KEI/Polycab/Fenolex as per approved by EIC) |
| 12 | DRAIN PIPE Supply and fixing of Drain piping by UPVC with 6mm thick nitrile rubber insulation and necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc: |
| 13 | 25 MM |
| 14 | Supply & Laying 20 mm hard PVC pipe (heavy type) for water discharge |
| 15 | Supplying, fabrication & fixing M.S. Angle Frame for installation of 8 nos Outdoor unit . the structure having 50 x 50 x5 mm MS angle for main bottom support grouted on wall and in between main support 25 x 5 mm ms strip . For railing vertical & horizontal support is made by 25 x 25 x 5 mm Angle for safety of maintenance; including cutting holes , welding , painting and mending good damage as per EIC |
| 16 | Supply & Fixing Powder coated Linear type extruded aluminium Square Grill (Make: premire/systemair/Air enterprise / Airmaster) without VCD |
| 17 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. - With out angle iron support 150x50x1.25mm (18SWG) |
| 18 | S/F 3 mm thick ACP Board for covering the IDU complete with linkages, levers, fittings, angle iron supports, trap door incl. all accessories as per direction of EIC (Make : Aludecor / Pratap) Please Enable Macros to View BoQ information |