| 1 | Supply,Installation,Testing & Commissioning of CPRI approved Manufacturer make floor mounted L.T. hooder type both side double door opening Feeder Pillar box of suitable size for accommodation of the bellow mentioned accessories duly approved by EIC with canopy with maple arrangement having rigid & self supporting structure of MS angle frame and fabricated with 3mm CRCA sheet for sides and bottom and 5mm thick CRCA sheet steel for canopy consisting of the following switches.Front Side: Incoming Section - 200 A TPN SFU with 3nos HRC Fuse Link -1 set; RYB,ON indication Lamp, 6A TP, 6A SP, MCBOutgoing - 32A TPN SFU and 3nos HRC Fuse Link-- 7NosBack side : Timer DB of to be fixed in this sideBus Bar Section: 500 V, 415A. electrolyte grade tin plated Copper bus bar with vertical/ horizontal section of size 20x 05 mm for Phase RYB, & neutral bars. Bus bar fixed with FRP chair & insulated with PVC heat Sinkable sleeve of suitable size & color should be enclosed by sheet metal (16 SWG) Iron Clad Busbar chambers inside feeder pillar, incl. earthing attachment and painting as required – ( As per Drawing no. 470 of PWD Specification Book – May 1991). Painting: Paint will be powder coated after cleaning the surface shall be given a phosphate coating, nine tank process system, SIEMENS GREY, RAL-7035 Shed |
| 2 | Constructural Details: All incoming & outgoing panel gasketted Door at front. All doors shall have Panel lock Arrangement. Degree of Protection will be IP-56 (Protected from high pressure water jets from any direction) .The panel shall be properly Gasketted to prevent ingress of dust & moisture & Remain. Busbar will be properly arranged & fixed by M.S. nuts & bolts On angle /flat iron frame base as per direction of E.I.C. The PANEL will be fabricated by 14 SWG. CRCA Sheet. The sheet steel thickness will be 2mm & Gland plate shall be 3mm thick. The work is inclusive of erection of Feeder Piller Box of above size on 10\\" brick padestal of appropriate size matching with the above Feeder Pillar and dimensions of the same approved be the EIC (minimum height 600mm bellow Goround level and 600mm above G.L) incl.sand cement plastering and neat cement finishing with brick padestal filled up by loose sand to accommodate the incoming & outgoing cable . (For power service Highmast Poles) |
| 3 | Supply & Erection of Latching Type 16 Mtr High Mast in two sections suitable for wind speed 50M/s made up from HTS as per BSEN 10025 , IS:2062 and T.R.-7 (Technical Report-7)with head frame luminaries carriage suitable to install minimum 6 nos luminaries in asymmetrical arrangement with latching centric system luminaries carriage, lightening final along with accessories required such as winch 6 mm dia ss wire rope, two continious rope without any intermediate joint, 5 core 2.5 sqmm ERP insulated pcp sheathed trailing cable, connector,integral power tool motor etc. as required , highmast shall be hot dip galvanized by single dipping method with single longitudinal welding , quality shall be as per ISO 3834-2:2005 (Top dia 150 mm ,Bottom dia min 410 mm,Section 2 nos,Thickness 3mm for top,4 mm for bottom.Base plate 570 mm x 570mm x 25 mm , Pcd -490 mm) with following acessories. (Make - Bajaj / Utkarsh / Valmont).(1) Baseplate ,Lantern carriage suitable to fix minimum 8 nos Lumineries .Suppy of Foundation bolt : M30 x 850 mm x 8 nos with template and Anchor plate .(2) Double drum winch (Gear ratio-50:1),Power tool motor ,Trailing cables(Make- as per OEM standerd) SS wire rope(Grade AISI 316) Make -as per OEM Standerd,Compensation Disc ,L stopper 2 nos Manual operating Handle Mounting Plates,Lighting Arrestor and Earthing Spikes (MS GI) (3) Supply & fixing of LED type aviation obstruction light. |
| 4 | (4) Supply & fixing of Stand mounted feeder pillar with 32 A TPN MCB incomer, single dial timmer, 25 A TP contactor for automatic switching of luminaries, power tool control with 2 nos 9A contactor and raise-lower push button etc. as required.(5) Supply & fixing of GI pipe earthing for High mast with2 nos. 2.5 M long 40 mm dia GI medium pipe incl. 25mm x 5mm GI strip connection with earth terminal as required.(6) High Mast feeder panel made of 3mm thick CRCA sheet for sides and bottom and 5mm thick for top including support structure made from 35mm x 5mm equal MS angle with powder coated painting as directed by EIC. (7) High Mast Should be made Galvanization as per BSEN ISO:1461(8) High Mast Should be made Fusion Welding as per ISO 3834 -2: 2005 Erection of the high mast has to be done with the help of suitable tools and plants with modern engineering practices with wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of 1.5 sq. mm suitable copper conductor. (Make- Valmont/Transrail/Bajaj) |
| 5 | Construction of shallow foundation with RCC with dimension (as per OEM standard) for the highmast considering the safe soil bearing capacity at site as 7.0 T/sqmtr at 2.2 metre depth with all materials and labour as per T.R.-7 (For 16 M High Mast) |
| 6 | Supplying, installation, Testing & Commissioning of Flood light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket forproper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with typeII/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevantBIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM- 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.System lumen efficacy shall be as below:System lumen efficacy ≥135 <135 lm/Watt250 Watt |
| 7 | Supply & Delivery of 8 Mtr. HDG Octagonal Poles in 3mm shaft thickness in MS Condition before Galvanization with Top A/F 70 mm, Bottom A/F 135 mm , Base Plate 225x225x16mm suitable for wind speed 180 Km/hr. as per IS:875 and 4 Nos. M20x700 “J” Type Foundation Bolts as per EN -8 (Min UTS -600) & Anti -theft locking doorarrangement for safety of MCBs, Terminal etc & 2000 mm HDG Double Arm Bracket made of (48.3ODx2.9 thik.) Mild Steel Pipe as per IS:1161 suitable to insert at Pole Top A/F 70 A) Material grade of shaft shall be of S355JO/JR as per BSEN 10025 or Equivalent IS: 2062 grade E350 (BR)B) Materials grade of Base Plate shall be E250(BR) as per IS:2062C) Galvanization as per BSEN ISO:1461D) Fusion Welding as per ISO 3824 -2:2021(Make–Valmont/Bajaj/Transrail) |
| 8 | Erection of upto 9 Mtr octagonal GI (Hot Dip Galvanised in single dip) pole 1.6 Km from the store to work-site with foundation of M20 grade concrete for 8.0/9.0 Mtr GI Octagonal Pole with all the materials like sand, cement, stone chips, reinforcement steel, binding wire etc as relavent IS Code. soil bearing capacity at site as 10 T/sqmtr., by PCC Base foundation having (L-1000mm x W-1000mm x H-100mm) & RCC foundation having dimention (L-500mm x W-500mm x H-1400mm) including neatly cemented finish (3mm thick) partly below and above ground level. There should be multiple alkathene pipes upto 1.2 mtrs of 50 mm dia of adequate length for distribution of incoming & outgoing cables for street light wiring as directed by EIC in the CC foundation of octagonal poles. |
| 9 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket forproper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 0o to 50o C and working RH 10% - 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with typeII/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevantBIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM- 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.System lumen efficacy shall be as below:System lumen efficacy ≥135 lm/Watt250 Watt |
| 10 | Fixing only Street Light Fitting with necessary fixing arrangements including GI reducer as required for mounting on existing arm brackets. |
| 11 | Supplying and Drawing 1.1 KV single core stranded 'FR'PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required3 x 22/0.3 (1.5 sqmm) |
| 12 | Supply and delivery of 4 core 70 sqmm of 1.1 KV grade alluminium XLPE armoured LT cable(Make: Havells/Polycab/Glostar/KEI/RR Kabel)(For connecting Service connection to Main feeder Pillar) |
| 13 | Supply and delivery of 4 core 25sqmm of 1.1 KV grade alluminium XLPE armoured LT cable(Make: Havells/Polycab/Glostar/KEI/RR Kabel) (For connecting Main Pillar to sub feeder pillar) |
| 14 | Supply and delivery of 4 core 16sqmm 1.1 KV grade alluminium XLPE armoured LT cable(Make: Havells/Polycab/Glostar/KEI/RR Kabel) |
| 15 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below as per G.S.(a) 4 core 70sqmm |
| 16 | Do----Do----Do(b) 4 core 25sqmm |
| 17 | Do----Do----Do(c) 4 core 16sqmm |
| 18 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials (a) 4 core 70sqmm |
| 19 | Do----Do----Do(b) 4 core 25sqmm |
| 20 | Do----Do----Do(c) 4 core 16sqmm |
| 21 | Making and adopting Micro Tunneling including supply of HDPE pipe 80 mm dia in single length for each individual tunnel to facilitate cable entry without disturbing and damaging as per requirement and as per direction of EIC (3 ft below the ground level). |
| 22 | Laying only Cable upto 50 sqmm through existing RCC/Hume/ GI Pipe/open masonary trench for 3, 3½ & 4 core as per G.S. |
| 23 | Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½ and 4 core |
| 24 | Supplying of 50 mm dia HDPE PIPES pe 63, 4kgf/cm2 type-SDR-21 (For laying different cables) Make- Supreme/Oriplast/Polycab |
| 25 | Excavation of soil and laying HDPE/GI Pipe for cable laying filling & ramming. (0.300x0.750xTotal Length of pipe laying (WxDxL) |
| 26 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 no 25 x 5mm GI (Hot Dip) flat (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers including S & F 32 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI-Medium GI pipe as per G.S. |
| 27 | Excavation of soil for installation of earth electrode and filling and ramming for soft soil as per G.S |
| 28 | Connecting the equipments to earth busbar including S & F GI (Hot Dip)solid wire of size No. 8 SWG on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages as per G.S. |
| 29 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl drilling holes, with bolts, nuts, washers etc as per G.S. |
| 30 | Dismantling all types of masonry excepting cement concrete plain or reinforced, stacking serviceable materials at site and removing rubbish as directed within a lead of 75 m. a) In ground floor including roof. |
| 31 | Earthwork in excavation for foundation of structures as per drawing and technical specification including setting out, removing, of spoils up to any lead as directed and including trimming the sides of the trenches, leveling, dressing and ramming the bottom, complete as per direction of the Engineer-in-Charge in marshy soil for depths not exceeding 3 m. by manual means: With pumping out water excluding shoring. |
| 32 | Removal of rubbish,earth etc. from the working site and disposal of the same beyond the compound, in conformity with the Municipal / Corporation Rules for such disposal, loading into truck and cleaning the site in all respect as per direction of Engineer in charge |
| 33 | Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. a) Pakur Variety. |
| 34 | Brick work with 1st class bricks in cement mortar (1:6) (a) In foundation and plinth |
| 35 | Note: 1) All the above rates should be quoted inclusive of all taxes & duties as applicable.Terms & Conditions: 1. Defect Liability period for the total work is 5 Years2. The warranty for the LED street light fittings of BOQ Item Sl. No. 6.00 and 9.00 has to be provided for 5 years by the manufacturer/OEM, the certificate/certificates (in case of more than one manufacturers/OEMs) in respect of which has to be uploaded with tender documents by the bidder.3.The bidder should upload Technical Data Sheet (TDS) of fittings and Driver, LM79 & LM80 Test Report for the offered LED street light fittings of BOQ Item Sl. No. 6.00 and 9.00 from the manufacturer’s NABL accredited Laboratory / any other NABL accredited Laboratory failing which the Bid may be rejected.4. The illumination design to fulfill the prescribed condition has to be certified by the Manufacturer/OEM within 07 (seven) working days from the date of layout. The minimum lux should be maintained as 40 lux with Uniformity factor ≥0.65. The Agency must procure the materials from the Manufacturer/OEM or from their authorized Sales channel so that the standard warranty/support of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.6. Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.7. If any refurbished material is supplied and installed, penal action will be taken as per existing rules Please Enable Macros to View BoQ information |