| 1 | Supply and Fixing in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts, grade 3, cross sectional area 95 sq. mm |
| 2 | Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, cable etc n exc 10 sqm on plan and n exc 1.5 m in depth and getting out in soft /loose soil |
| 3 | Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and as directed. |
| 4 | M/L for Returning , filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed. |
| 5 | Supply and laying double wall corrugated pipe (DWC) conforming of size 120mm outer dia and 103.5 mm inner dia complete all as specified and as directed |
| 6 | Supply, laying, testing and commissioning Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm |
| 7 | Supply, laying, testing and commissioning Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. |
| 8 | Supply, Laying, testing and commissioning Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. |
| 9 | Supply and lay in replacement of pipe galvanized, “Medium class”, including fittings 80 mm (3”) dia laid in trenches |
| 10 | Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) .complete all as specified and as directed. |
| 11 | M/L for cement concrete 1:2:4 type B-2, (using 40mm graded stone aggregate) 150mm thick complete all as specified and as directed. |
| 12 | Cable route indicator comprising of CI wiser of size 100mm dia embossed as HT power cable fixed to MS angle iron of size 50x50x6mm (embended in PCC 1:3:6 blocks of size 300 x 300 x 450 mm) including two coats of aluminium paint over a coat of aluminium red oxide primer and neceessay earth work complete all as specified and directed. Please Enable Macros to View BoQ information |