| 1 | Substation,HT/LT Network |
| 2 | Supply,loading, unloading at site ,Carriage, Installation, testing & commisioing of 400 kVA ,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound ), and with LV box having detachable Aluminium Gland Plate |
| 3 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 9mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards |
| 4 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 8mtr Long SP-15 with base plate & cap for LT. Strictly as per REC standards |
| 5 | Supply,loading , unloading at site ,Laying, stringing, tensioning & binding of ACSR 30mmsq (weasel) Conductor. |
| 6 | Supply/Fixing & commissioning of GI Channel/Angle/Flat of Sizes including clamps |
| 7 | Supply,loading , unloading at site ,Laying, stringing, tensioning & binding of ACSR 50mmsq (Rabbit) Conductor. |
| 8 | Supplying and fixing of GI Channel “V’ cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole [email protected] kg each |
| 9 | Supplying and fixing of pole Earthing Complete by Spike Earthing Rod 20mm 2.5 Mtr long with GI strip (25x3)mm to each LT and HT pole |
| 10 | Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened. |
| 11 | Supply,fixing, testing & commissioning of 11KV GO Set, AB Switch as per IS Standards |
| 12 | Supply,fixing, testing & commissioning of 11KV DO Fuse Set as per IS Standards |
| 13 | Supply,fixing, testing & commissioning of 11KV LA Set Gap less as per IS Standards |
| 14 | Supply,fixing, testing & commissioning of 11KV Pin Polymer Insulators with GI pins complete. |
| 15 | Cement bottoming 1:2:4 mix as per REC Standards 0.48cum/pole |
| 16 | Supply and fixing of 300 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type |
| 17 | Providing & fixing of 11 kV polymeric composite disc insulator 12 kV , min failing load 45 kN, lighting impulse 75 kV positive and 80 kV negative, creepage distance 320mm |
| 18 | Providing & fixing of LT Shackles Insulator with GI mukhi clamps including Nuts & Bolts |
| 19 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm No.minal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 20 | Providing and Fixing of GI Nuts and Bolts. |
| 21 | Providing and Fixing of Wedge Connectors / PG Clamp |
| 22 | Supply, installtion of Danger Plates with Clamps |
| 23 | Providing and fixing of GI Barbed Wire for Anti Climbing |
| 24 | Cement bottoming 1:2:4 mix as per REC Standards 0.4cum/pole |
| 25 | Supply and fixing of LT Distribution Box for 400 kVA DTR with 630 Amp MCCB 3P 36 kA for incomer & 200 Amp MCCB 3P 16 kA 4 No.s for Outgoing |
| 26 | 400KVA Servo Voltage Stablizer |
| 27 | Supply, installation, testing, and commissioning of 400 kVA servo-controlled automatic voltage stabilizer with a digital microprocessor-based controller, conforming to IS 9815. The stabilizer shall be copper wound (EC grade), oil cooled with minimum 1000 litres of insulating oil as per IS 335:2018 (UN type), and of the unbalanced type with a bypass arrangement. It shall operate within an input voltage range of 190-450 V (P-P) and 110-260 V (P-N), and provide a stable output voltage of 415 V AC ±1%. The unit shall have an overload capacity of up to 120% and operate at a frequency of 50 Hz with deviation as per IS. It shall include all necessary protection mechanisms as detailed in the technical specifications (Annexure A) and be supplied along with appropriately rated cables on both input and output sides. Make: Hindustan Power Products, PureVolt New Delhi, Jindal electric Faridabad, Servocon, Electric Field, Sen & Pandit Systems, Moto line Electronics, Power Bank (AMPLE) India, Baid Power Services Pvt ltd. Automatic Electric (AE) ,Fiji Electronics Pvt Ltd. |
| 28 | Supply, lying, testing and commissioning of LT Cable 3-1/2 core, 120 mmsq aluminium Un-armoured cable XLPE type (with complete accessories), conforming to IS:7098 Part 1. Havells , Polycab, KEI, Gupta , Plaza , Grindlays , RR kabels , APAR industries, Torrent Finolex) |
| 29 | SITC of 400 Amp MCCB 4 Pole Including cost of outdoor type,MS Steel enclosure made out of 14/16 SWG duly power coated paint with locking arrangement including extension of terminal bus bar for both sides for termination of cable, cable glands and lugs. (L&T, Siemens , Schenieder, Legrand , Havells , Finolex, C&S, Crompton make) |
| 30 | SITC of HT Metring Unit CT PT Operated for detailed estmate refer to Annexure C |
| 31 | Construction of Concrete Bed along canopy for housing Servo Voltage Stabilizer for detailed estimate refer to Annexure B Please Enable Macros to View BoQ information |