| 1 | Item Wise BoQ BoQ_Ver3.0 Item Wise Normal INR Only INR Select, Excess (+), Less (-) Tender Inviting Authority: Superintending Engineer, Electricity Construction & Work Circle-I, P.V.V.N.L., Meerut Bought Out Name of Work: Work for (1) Construction of proposed 33 KV line to tape Existing 33 KV line of 33/11 KV Sub-Station LACHEDA (Distt. Muzaffarnagar) to old & used 33 KV line Begrajpur Industrial emanating from 132 KV Sub-Station PURA Muzaffarnagar) (2) 63 MVA transformer installed at the 220 KV transmission substation KANDELA (Shamli) is overloaded, laying of 33 KV cable work to transfer the load to another 63 KVA transformer. Direct Tender Reference No : 22/ECWC-I/MRT/2026-27 Quote for Supply Portion only Bidder Name : Quote for Erection Portion only PRICE BID1. This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns after validating the sheet, else the bidder is liable to be rejected for this tender.2. Bidders are allowed to enter the Bidder Name and Unit Ex-Works Price and GST in %age only.3. All the material and erection practices shall be as per tender specification.5. Above Schedule Structure and quantities is provisional and may vary as per site requirement with due approval.6. Indicative scope of works and quantity of Items/Materials required for above work shall be as per the Price Bid. Any other material if required to complete the job and not mentioned above, shall have to be provided by the bidder without additional cost.7. Financial evaluation and selection of 'L1 Bidder' shall be done on the basis of total amount. The rates received in the tender will be final after the approval of the Competent Authority/Committee and the competent Authority/committee will have the right to negotiate in tender rate/amount.8. Tenderer must be fill-up the enclosed terms & conditions sheet and attached with 1st Part of Tender as well as scanned copy of same will be uploaded on NIC Website alongwith other documents.9. Bidders must be filled up the GST in %age, Otherwise it is assumed G.S.T. rates are included in the given ex-works price (Rs./Unit). NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Works Item Code Tender Qty. Unit Estimated Rate Bought-out/Direct Specify Bought-out/Direct Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Unit Ex-Works Price(Rs./unit) Excise Duty(Rs/Unit) CST/VAT(Rs/Unit) Other Taxes & Duties(Rs/Unit) Freight & Insurance Charges(in Rs./Unit) Unit FOR Dest. Supply Price incl. all Taxes and Duties(in Rs./Unit)(F+G+H+I+J) Total Value for Supply or Erection (In Rs.)(C x F) GST (in Rs.) in %age Total Value for GST (in Rs.) (F*M/100) Total Unit Price incl. GST (in Rs.) Total Amount excl. GST (in Rs.) (4×13) Total Amount incl. GST (in Rs.) (4×26) TOTAL AMOUNT In Words |
| 2 | Supply of following materialM.S.Angle Iron 65x65x6mm. 4300mm long Bracing |
| 3 | M.S Channel 125x65x3200 mm. (Top Channel) |
| 4 | Dropper channel 100×50mm, 2028 mm. Long |
| 5 | Dropper channel 100×50mm, 2240 mm. Long |
| 6 | Cross Arm Holding clamp for Pole |
| 7 | Channel Holding Clamp for (Top & Dropper channel) |
| 8 | Stay Clamp for Pole |
| 9 | F Bracket for 33 KV |
| 10 | E Bracket for 33 KV |
| 11 | Danger Board with clamp for Pole |
| 12 | Number Plate with clamp for Pole |
| 13 | Alluminium Binding Wire 6 SWG |
| 14 | Red Oxide |
| 15 | Alluminium Paint |
| 16 | G.I. Barbed wire |
| 17 | M.S. Bolts Nuts & Washers |
| 18 | Earth wire clamp with Nut & Bolts |
| 19 | Stone pad (300×300×75)mm |
| 20 | P.G. clamp for Dog to Dog conductor |
| 21 | Insulator for stay |
| 22 | Holding Clamp for GI Pipe |
| 23 | Holding Clamp for pole |
| 24 | Lug for ACSR Dog Conductor |
| 25 | G.I. Pipe 160mm dia ,3.00 Mtr. long for mounting 3×300mm2 33 KV XLPE Cable on double/four pole structure including cost of clamp etc. |
| 26 | Supply of HDPE Pipe PE-80, PN-6, DN-160mm dia Pipe for laying of 33KV,3x300Sq.mm |
| 27 | Cable route marker |
| 28 | Safe carriage of with loading & unloading at both ends respectively. (under jurisdiction of PVVNL)Steel Tublar Pole SP-72 13Mtr (Bottom Portion Galvanized) |
| 29 | 11 Mtr Long PCC pole |
| 30 | 33 KV, 3×300mm² XLPE Cable |
| 31 | Outdoor Type cable Jointing kit for 33 KV XLPE cable 3×300 mm² |
| 32 | Stay Sets (20×1800)mm |
| 33 | Stay wire G.I 7/8 SWG |
| 34 | M.S. Earthing Rod |
| 35 | V Type Cross Arm 33 KV |
| 36 | ACSR Dog Conductor |
| 37 | 33 KV Pin Isulators (Polymer) |
| 38 | Disc Insulators B&S 7000 Kg. (Polymer) |
| 39 | Disc Fittings B&S for Dog 70 KN (Polymer) |
| 40 | Erection of Following materialA- Erection of support after excavation of foundation pit in mix soil/normal soil/soft & hard rock and its back filling and leveling etc. The size of the pit will be (900×600)mm and having depth of 1/6th of the full length of the support & Erection of support. The work includes carriage and handling of supports from site store to pit site.(i) 11 Mtr Long PCC pole |
| 41 | (ii) 13 Mtr Long STP, SP-72 Round Pole |
| 42 | B- Fixing of all clamps, Cross Bracing Sets 3.5 Mtr. from M.S. Angle 65×65×6mm/50×50×6mm & other accessories on the supports as per drawing. Work includes cutting of holes and providing M.S. Bolts of 16×40mm size in the middle of cross bracing with 1 no. spring washer. The work also includes carriage & handling of accessories from sectional store to pit site as well as any fabrication work if required.(i) Single Pole (a) 13 Mtr Long STP, SP-72 Round Pole |
| 43 | (ii) Double Pole Structures (a) 13 Mtr Long STP, SP-72 Round Pole |
| 44 | (b) 11 Mtr Long PCC pole (End pole) |
| 45 | Grouting of supports in CC 1:4:8 (Cement, sand & 40 mm brick ballast) Grouting will be done in the block of size (450×450)mm ×1/6th of full length of the support, up to ground level, 300 mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grit) with muffing as per drawing, work includes back filling and proper ramming.(i) 11 Mtr Long PCC pole |
| 46 | (ii) 13 Mtr Long STP, SP-72 Round Pole |
| 47 | Grouting of stay rods (20×1800)mm including all work of excavation, cement concrete in size (0.60 × 0.60 × 0.30)m in ratio 1:4:8 cement, sand, 40mm brick ballast) as per drg. including back filling, proper ramming etc and fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing. |
| 48 | Earthing of supports with MS earth Rod of (20×2500)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connecting below the earth electrodes with the help of G.I. wire no. 8 SWG and earthing lugs. |
| 49 | Laying, spreading, lifting and final sagging of 3 phases of ACSR Dog conductor in accordance with profile and sag chart including binding, Jumpering and fixing of P.G. Clamp as per requirement in 03 Nos. conductor in parallel. |
| 50 | Fixing of 33 KV danger board at each location as per specification of the drawing with clamps etc. |
| 51 | Fixing of Number plate with clamp |
| 52 | Making H.T. Connections of the proposed line, on to the existing 33 KV bay/line from where line is eminating and another at the end of line to the terminal gantry at proposed 33 KV Sub-station. The work consists of fixing of tension fitting, insulators, jumpering, clamping and binding etc. at the end as per site conditions. |
| 53 | Painting of following supports/structures with 2 coats of synthetic enamel paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work. Painting will be done by red oxide paint at all clamp , all channel , cross bracing, cross arm etc. and after it one coat of Aluminium paint.(i) Single supports(a) 13 Mtr Long STP, SP-72 Round Pole |
| 54 | (i) Double supports(a) Steel Tublar Pole SP-72 13M |
| 55 | b) 11 Mtr Long PCC pole (End pole) |
| 56 | Wrapping of barbed wire on 33 KV PCC Poles/SP-55 ST & SP-72 ST Poles as anti-climbing device for a length of 0.9 Mtr., wire pitch/gap 13mm and fixing upper and lower end keeping lower end at a height of 2.75 Mtr. from the ground complete with supply and fixing of lower end & upper end clamps made of M.S. Flat 40×5mm complete with nuts & bolts & all other required material. |
| 57 | Digging & laying of 33 KV cable(Double CKT) in Trench with sand and Brics including loop |
| 58 | Laying of 33 KV cable in Air |
| 59 | Laying of HDPE Pipe PE-80, PN-6, DN-160mm dia Pipe for laying of 33KV, 3x300Sq.mm, XLPE Cable with HDD (trenchless) method including cable laying. |
| 60 | Making of 33 KV O/D type 3×300mm² cable J/kit |
| 61 | Road restoration charges for Kuccha Road (Inter locking Tiles, Bricks Road & Developed green belt only). |
| 62 | Road restoration charges for Pucca Road (Cemented, Concrete & Black road only). |
| 63 | Fixing of cable route marker along the route of 33KV cable. |
| 64 | Fixing of G.I. Pipe 160mm dia ,3.00 Mtr. long for mounting 3×300mm2 ,33 KV XLPE Cable on double/four pole structure including cost of clamp etc. |
| 65 | Sundries Item |
| 66 | Dismantling charge old & used 33 KV line (steel scrap of ples - 500 kg , aluminium scrap of conductor 75 kg) Total in Figures 0.0 0.0 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select % 0.0 0.0 Zero Only Quoted Rate in Words Zero Only Please Enable Macros to View BoQ information |