| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority: Executive Engineer DTIDC Name of Work: M/o ISBT's Sarai Kale Khan.SH: SITC of High Mast Pole 3 Nos., Electrical Maim LT Panel & flood lights etc.in new commercial developing parking area in ISBT Sarai kale khan. Contract No: NIT 26/026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl No. Item Description Item Code / Make Quantity Units Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | 1.Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 3 | b)Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 4 | c)Above 95 sq. mm and upto 185 sq. mm (clamped with25/40x3mm MS flat clamp) |
| 5 | 2.Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation,sand cushioning, protective covering and refilling the trench etc as required. a) Above 35 sq. mm and upto 95 sq. mm |
| 6 | b) Above 95 sq. mm and upto 185 sq. mm |
| 7 | 3.Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc.with charcoal/ coke and salt as required. |
| 8 | 4.Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring,washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm). |
| 9 | 5.Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 10 | 6.Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 11 | 7.Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in a) 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 12 | b)160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 13 | 8.Providing and fixing of 400 A,50KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 14 | 9.Supplying,Installation,Testing Commissioning of Flood light fixture of 400 Watts LED Flood Light, High performance floodlight luminaire with pressure die-cast housing,toughened glass and secondary lens optics with IP66 ingress protection. E cacy 140 lm/W. at high mast ploes complete etc. as required. (Make -Bajaj/Havells/Crompton) |
| 15 | 10.Supplying,Installtion,Testing & Commissioning of 25M high mast shaft in THREE sections suitable for wind speed as per IS: 875 part-III, with head frame,winch mounting bracket, luminaries carriage suitable to install 12 nos Flood light luminaries in symmetrical arrangement having Plate thickness of Top/Middle/Bottom Section of 3mm/4mm/4mm with no negative tolerance allowed. Top and Bottom Dia shall be 150mm and 460mm. Highmast shaft shall be 20 sided polygon with Galvanisation as per BS EN IS0 1461. Mast should have Lightning protection finial of G.I spike. HM Supplying,Installtion,Testing & Commissioning of 25M high mast shaft in THREE sections suitable for wind speed as per IS: 875 part-III, with head frame,winch mounting bracket, luminaries carriage suitable to install 12 nos Flood light luminaries in symmetrical arrangement having Plate thickness of Top/Middle/Bottom Section of 3mm/4mm/4mm with no negative tolerance allowed. Top and Bottom Dia shall be 150mm and 460mm. Highmast shaft shall be 20 sided polygon with Galvanisation as per BS EN IS0 1461. Mast should have Lightning protection finial of G.I spike. HM Sheet raw material shall be of reputed make.Highmast base plate shall have diameter of 670mm and thickness of 25mm. Type / diameter / length of foundation bolts shall be TS 600 / 30 mm dia / 850 mm long.Winch should be Doube drum, SWL 750kg minimum with Integral motor of 1.5 HP, 6 pole single speed Lantern carriage shall be made of 50 NB ERW Class B - M.S. Pipe with ID of ring as 711mm suitable for carrying 12x400W Fixtures Highmast accessories should include raising lowering system comprisin double drum winch, 5mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle,junction box, lightening finial. (Wiring material from JB to individual luminaire & MCB in base compartment are not included and are a part of installation).Technical Specification 2: HIGH MAST SYSTEM Make : Bajaj Electricals Ltd. Height of mast : 25 Meter,No. of sections : Three, Material construction : HR sheet steel conform to IS 2062 / BS EN 10025 or Equivalent. Base dia. and top diameter (A/F) : Top : 150 mm, Bottom : 460 mm Plate thickness : Top : 3 mm,Middle : 4 mm,Bottom : 4 mm Cross section of Mast : 20 side polygon.Standard for of galvanisation : As per BS EN ISO 1461 Size of opening and door at base : 1200 x 250 mm Diameter of base plate : 670 mm Thickness of base plate : 25 mm ,Lightning protection finial : G.I single mini spike Max.wind speed : 47 m/s as per IS : 875 (Part - III) Number of foundation bolts : 12nos. PCD of foundation bolts : 590 mm Type / diameter / length of foundation bolts : TS 600 / 30 mm dia / 850 mm long LUMINAIRES CARRIAGE Material of construction : 40 NB ERW Class B - M. S. Pipe Diameter of carriage ring (mm) : 711 mm (ID) Construction : 12 Arm, Welded, 2 sections Load carrying capacity : 24 Luminaire symmetrical TRAILING CABLE Conductor : Copper, 5 core, 2.5 sq mm insulation : PVC flexible ,No. of circuits per mast : One no. cable per mast ,WINCH / POWER TOOL ,Type / SWL of winch : Double drum, SWL 750 Kg Method of operation : Integral Motor Motor capacity : 1.5 HP No of speeds : 6 Pole, Single speed Torque limitor : With mechanical tripping facility STAINLESS STEEL WIRE ROPE Grade / construction : AISI 304, 7/19onstruction Number of ropes : Two continuous Diameter (mm) : 5 mm Breaking load capacity : 2350 kg x 2 |
| 16 | 11. Supplying & fixing of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template as per high mast poles hight 25 meter as per specification at item no.10.Construction of Shallow foundation including reinforced steel with M20 grade concrete or cement mixture for high mast considering the safe soil bearing capacity 12T/Sq.mtr @ 2.2M depth with all material and labor as per our specified drawing & erection work with suitable Hydra complete etc. as requiredSteel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 17 | 12.Supplying & fixing of LED type single dome aviation obstruction light as per high mast poles hight 25 meter as per specification at item no.10. complete etc. as required. |
| 18 | 13 Supplying & fixing of outdoor stand mounted feeder pillaras per high mast poles height 25 meter for siitable for 12x 400 watts as per specification at item no.10 & following capacity of automatic street light cubicle control panel painted with anti corrosive -alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, isolating switch,metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect. 63 A TPN complete etc. as required. |
| 19 | 14.Supply, installation, testing and commissioning of Main LT outdoor LT feeder pillar of size 6.5’ x 4.5’ minimium made of modular construction fabricated from 16 SWG CRCA sheet with hinged cover and locking arrangement etc. complete of suitable size as per site requirement. The feeder pillar shall be floor mounted on brick platform grouting in CC foundation as per site requirement Inter connection with 19 x18 size of PVC insulated copper conductor cable with copper lugs earthing, brass compression glands for termination of cables and uts, Bolts, Washers, Ferul Numbers, Cable Ties, TieBase, Copper PVC Control Wire, Power Wire, Copper Thimbles, Panel Locks, I-Hooks, PVC Tape, Insulators Etype, L-Type , Round Type, MCB Chanel, Pvc Chanel,Connector Chanel, Connectors, Foam Gaskit Etc.comprising of following items in it including painting complete etc. as required.Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) (a) 400A FP 36KA MCCB WITH SPREADER LINK WITHROTARY HANDLE - TMRO/L, S/C (Incomer) METERING,MULTIFUNCTION METER, -1 no set (b) 160A FP 36KA MCCB WITH SPREADER LINK WITHOTARY HANDLE - TMR O/L, S/C , E/F-(outgoing)-6 Nos ,(c)400/5A CT CLASS-1-03 Nos,(d)INDICATING LED LAMP RYB- 3 Nose)2A SP MCB-4 Nos,(f) Al. Bus Bar 500 Amp-1 Setg) Volt meter- 1 No.(h) Ammeter-1 No.(i) 63A FP MCB 10KA- 03 Nos (j) 63A DP MCB 10KA |
| 20 | 15.Supply of following sizes of PVC insulated and PVC sheathed aluminium conductor armored cable complete as required. a) 4X10 Sq.mm |
| 21 | b)3.5.x50 sq. mm |
| 22 | c)3.5X150 sq.mm Total in Figures 4695027.0 4695027.0 INR Forty Six Lakh Ninety Five Thousand &Twenty Seven Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |