| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority :- EXECUTIVE ENGINEER ELECTRICAL DIVISION PWD B&R JALANDHAR Name of Work:- Special Repair & Upgradation of Olympian Surjit Singh Hockey Stadium, Burlton Park, Jalandhar (Punjab) (Providing External Electrical Services ) Contract No: ELECTRICAL WORKS Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Work Name Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Providing External Electrical Services |
| 3 | Providing Flood Lighting & Campus Lighting |
| 4 | Supply and Erection of Decorative Pole 6 Meter long with Decorative bracket. poles designed to suit single or multi arms brackets in order to install one or more light sources. Product Description:- • Pole made of Galvanized and mild steel tube and painted with Polyurathen paint / Pure polyster, power coated of desired colour. • Pole design parameters vary depending on the type of bracket and loading factor. • Conical pole are welded using saw welding technique by certified welders by using automatic machine with precision welding. • Other Welding using special v groove technique by certified welders using high end MIG welding processes. • Built-in control box with service door and safety rope. • Service door is contoured to the shape of the pole with rubber gasket. • The control gear tray is prewired with MCB, terminal connectors for loop-in / loop-out arrangement. • The foundation bolt holes in the base plate are designed to be elongated for fine adjustments / alignment of the pole during installation. • Base plate size (250-300mm) X (250-300mm) X 12mm. made of steel grade E250 & foundation bolt of grade 4.6, complete in all respects as approved and desired by the Engineer in-charge at site. (Including RCC foundation) |
| 5 | Supply and Erection of 50/60W LED decorative drop down light made of cast aluminium span Aluminium clear Acrylic (A9) housing fitted with clear/ Polycarbonate diffuser Alluminium heat sinks. input power 60W with THD % less than 10% with driver effieciency greater than 55% operating voltage range 100-270 volts with output open circuit protection, short circuit protection and over voltage protection with internal surge protection greater than 5 kv and external surge protection greater than 5 kv, luminuos flux 6000K with coloured temperature 6000k IP grade 66. Minimum, CRI > 70, PF < 0.55, LED life - 50,000 hrs (min). Complete in all respects as approved and desired by the Engineer in-charge at site. |
| 6 | Supply and erection of LED Street Light 70W (including LED driver) in aluminium pressure die cast housing with toughned glass cover (IP66 Protection) and secondary lenses with IP66 protection having efficiency of LED fixture minimum 120 lumens per watt and operating voltage between 140 to 270volt, input frequency 50Hz + 3% complete along with erection of the same with connections, testing etc. Street light should install on existing G.I. Bracket installed on parapet complete in all respects as approved and desired by the Engineer-in-charge at site. The certification and Specification of the LED fitting should be as approved by O/o Advisor(Technical), Govt. of Punjab vide Letter no. AT/2021/GL/1410-1422 Dated 06/05/2021.Besides this the lighting fixture manufacturer should have inhouse NABL accredited lab. |
| 7 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE): |
| 8 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 9 | Overall size 10sq.mm (4Core) Un-armoured (Loose) |
| 10 | XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE): |
| 11 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:- |
| 12 | Overall size 10sq.mm (2Core) Un-armoured (On-Surface) |
| 13 | G.I. EARTHING: |
| 14 | Earthing with G.I. wire/ rope in G.I. pipe partly recessed and partly on surface complete with 150cm long 50mm dia. G.I. earth pipe (Cutting threads and 36 Nos. holes, 1cm dia. to make a mesh around the GI Pipe) with G.I. reducing socket including erection of the same, 4.50 metre (14.76 feet) below ground level with 20Kg. charcoal & salt mixture etc., up to 8 metre in length (including boring & refilling). |
| 15 | Earthing with 7/14 S.W.G. (7/2.18mm dia.) G.I. rope in 20mm dia G.I. pipe with G.I. reducing socket 50mm x 20mm (upto 8Metre in length) |
| 16 | Earthing earth rod 20 mm dia for providing earth connections upto line earth with G.I. Wire 8 S.W.G. (4mm dia.). The rod shall be tapered at one end and flatted on other end. The hole size 10mm dia shall be drilled on the flatened side for facilitating connection with G.I. wire and thimble etc. The rod shall be erected in ground upto complete length vertically:- |
| 17 | GI Earth rod 20 mm dia., 3 mtr. Long |
| 18 | PVC INSULATED FR COPPER CONDUCTOR CABLES: |
| 19 | Supply and erection of PVC insulated PVC sheathed (3 core) round flexible wire with copper conductor (FR) cable (ISI marked) confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 20 | Overall size 1.5sq.mm (48/0.20mm), 3Core |
| 21 | SHEET METAL CUBICAL PEDESTAL, TOWER STRUCTURES, HT & LT LINE ITEMS, MS CHANNELS, BRASS GLANDS, ALUMINIUM & COPPER THIMBLES: CUBICAL PEDESTAL: |
| 22 | Supply and erection of Sheet metal cubical pedestal made from 50mmx50mmx6mm thick MS angle iron frame with 5 sides welded & covered with MS sheet 2mm thick & front side hinged with 4\\" hinges & locking system with single/ double door openable placed on MS strip of size 12.5mm x 2.5mm thick welded with MS sheet, 4Nos. legs of 50mmx50mmx6mm thick MS angle iron each of 600mm long with MS sheet 100mmx100mmx6mm thick at the bottom end of the legs. Front door welded x-sectionally with MS flat 25mmx5mm. The front side with MS sheet each 75mm wide & a bend of 75mm width outwards & inwards on all sides with tappered top 200mm high and pedestal with 4 Nos. supporting members each of MS flat 50mmx6mm thick according to cubical size duly welded & complete pedestal to be painted with 1 coat of red oxide & 2 coats of paint & bonding to the existing earth. The Pedestal platform should be filled with 1:2:4 cement concrete mixture and erected 150mm high from the top of the cement concrete platform. The job is to be completed as approved by Engineer-in-charge:- |
| 23 | Cubical Size 1200mm high, 900mm wide and 350mm deep with platform dimensions 1000mm x 450mm x 450mm |
| 24 | MCCB's (FOR PANELS & SHEET ENCLOSURE):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- |
| 25 | MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 26 | MS SHEET ENCLOSURE FOR MCCB's: |
| 27 | Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:- |
| 28 | MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm) |
| 29 | MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's: |
| 30 | MINIATURE CIRCUIT BREAKERS: |
| 31 | Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 32 | MCB Double Pole 6-32amp. (10kA, Curve-C) |
| 33 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 34 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's: |
| 35 | Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 36 | TP&N Horizontal Double Door Distribution Board 4 way each |
| 37 | Supply and erection of G.I. Pipe (A-Class) Single arm bracket of suitable length to give a total overhang at a tentative angle of 100/105º, the bracket should be fixed on the existing surface/ wall with 2nos. MS flat clamp 25mm x 5mm, 30cm long and 4nos. fastner 10mm x 75mm long with two coats of an approved aluminium paint complete in all respect as approved by the Engineer-in-charge at site:- |
| 38 | Single Arm Bracket 1 metre Long G.I. Pipe 40mm Dia. |
| 39 | Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 40 | Double Walled Corrugated HDPE Pipe 50/ 38mm (Outer/ Inner dia.) |
| 41 | 630 KVA CSS & Main LT Panels |
| 42 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE): |
| 43 | Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:- |
| 44 | Overall size 240sq.mm (3½ Core) Un-armoured (Loose) |
| 45 | Overall size 300sq.mm (3½ Core) Un-armoured (Loose) |
| 46 | Overall size 400sq.mm (3½ Core) Un-armoured (Loose) |
| 47 | XLPE INSULATED HT ARMOURED CABLES (LOOSE): |
| 48 | Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid loose in the existing trench or pipe:- |
| 49 | HT Cable Overall size 70sq.mm (3Core) |
| 50 | COPPER EARTHING (Upto 8 metre in Length): |
| 51 | Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 52 | Earthing with 20mm x 3mm Copper Tape (upto 8Metre in Length) |
| 53 | Earthing with 25mm x 5mm Copper Tape (upto 8Metre in Length) |
| 54 | COPPER EARTHING STRIP (As Additional Length): |
| 55 | Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:- |
| 56 | Additional Length 20mm x 3mm thick Copper Tape |
| 57 | Additional Length 25mm x 5mm thick Copper Tape |
| 58 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: |
| 59 | Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 60 | Double Walled Corrugated HDPE Pipe 90/76mm (Outer/ Inner dia.) |
| 61 | Double Walled Corrugated HDPE Pipe 120/ 103.5mm (Outer/ Inner dia.) |
| 62 | Main LT Panel |
| 63 | Designing, Supplying, installation, testing &commissioning of Indoor cubical TTA type Main LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel as per IEC 61439-1&2 Totally Type Tested panel with IP 42 (indoor type).LT Panel shall be tested for all type test with aluminum busbar,The manufacturer shall submit the all type test reports during drawing approval. (Dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system,IP54/55 and minimum 50kA. The Panel shall be fully type tested at an Independent Laboratory and shall comply to IEC 60439-1&2 . The Panel shall be (Indoor) type, weather, dust and vermin proof suitable for humidity up to 95%. Average daily temperature: +35°C max, Ambient temperature: -5°C to 40°C. The Supervision,Inspection & testing at Manufactuers site(By department)Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet,,conforming to IS:8623. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The door should be double door design without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. |
| 64 | The Panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel.The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.Painting:- The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7 tank Powder coated process should present in company pemises) after necessary putty work . Busbar :- The panel shall be provided with TPN aluminium busbar of suitable size according to the size of ACB/MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports.The main busbar would be supported upon non-hygroscopic supports and Breaker should be compatible for communication on Modbus TCP/IP for future scope. ACB terminals should be rotatable type. |
| 65 | Metering :- The panel shall complete with also have digital metering unit with selector switch (volt meter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. The switchboard Main distribution panel shall restrict the internal arcs faults within the compartment to ensure maximum safety to the operating personnel.The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker),Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO9001:2015 standerd) and NABL Lab reports of calibiration. The Concerened contactor shall be provide the detailed drawing of panel with attested and submitted to department for approval with complete specification and approved from the Engineer in charge at site.Bus Bar :- 2000A, TPN Aluminium Busbar suitable for with standing fault level of 50KA with heat shrinkable coloured sleeves i/c SMC/DMC bus bar supports at required intervals. (Current density shall be maximum 1.3 A/sqmm) Detail of ACB/MCCB's to be installed in the cubical panel Enclosure as per following . |
| 66 | Bus Bar :- 1200A.TPN aluminium main bus bar,load wise sub feeder bus bar colour coated heat shrink bus bar sleave nut-bolt,washer ,hardware etc.Main Incomer:- 1. ACB 1000 Amps. EDO type FP, Icu = Ics = Icw (1 Sec.) = 50kA, microprocessor based trip sytem with thermal memory, zone selective interlocking, pre trip alarm, individual fault indicating LED, release with LSIG protection = 1No. and Multi Function Meter with display parameter of Voltage, Ampere, KW, KWH, KVA, Frequency, PF, % THD, phase angle and LED Cluster Indicating lamps and 2 Amp control MCB suitable size CTs = 1No.Outgoings:- . 1. MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting = 2 Nos.2. MCCB Four Pole 160amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting = 4 Nos.3. MCCB Four Pole 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting = 6 Nos.Changeover Switch : On Load Change Over Switch Four Pole 630amp., 415volts=1 No. complete in all respects as approved by engineer in charge at site. |
| 67 | Sub LT Panel For Highmast |
| 68 | Designing, Supplying, installation, testing &commissioning of Indoor cubical TTA type Sub LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet steel as per IEC 61439-1&2 Totally Type Tested panel with IP 42 (indoor type).LT Panel shall be tested for all type test with aluminum busbar,The manufacturer shall submit the all type test reports during drawing approval. (Dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system,IP54/55 and minimum 50kA. The Panel shall be fully type tested at an Independent Laboratory and shall comply to IEC 60439-1&2 . The Panel shall be (Indoor) type, weather, dust and vermin proof suitable for humidity up to 95%. Average daily temperature: +35°C max, Ambient temperature: -5°C to 40°C. The Supervision,Inspection & testing at Manufactuers site(By department)Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet,,conforming to IS:8623. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The door should be double door design without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. |
| 69 | The Panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel.The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.Painting:- The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7 tank Powder coated process should present in company pemises) after necessary putty work . Busbar :- The panel shall be provided with TPN aluminium busbar of suitable size according to the size of ACB/MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports.The main busbar would be supported upon non-hygroscopic supports and Breaker should be compatible for communication on Modbus TCP/IP for future scope. ACB terminals should be rotatable type. |
| 70 | Metering :- The panel shall complete with also have digital metering unit with selector switch (volt meter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. The switchboard Main distribution panel shall restrict the internal arcs faults within the compartment to ensure maximum safety to the operating personnel.The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker),Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO9001:2015 standerd) and NABL Lab reports of calibiration. The Concerened contactor shall be provide the detailed drawing of panel with attested and submitted to department for approval with complete specification and approved from the Engineer in charge at site.Bus Bar :- 2000A, TPN Aluminium Busbar suitable for with standing fault level of 50KA with heat shrinkable coloured sleeves i/c SMC/DMC bus bar supports at required intervals. (Current density shall be maximum 1.3 A/sqmm) Detail of ACB/MCCB's to be installed in the cubical panel Enclosure as per following . |
| 71 | Bus Bar :- 400A.TPN aluminium main bus bar,load wise sub feeder bus bar colour coated heat shrink bus bar sleave nut-bolt,washer ,hardware etc.Main Incomer:- MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting and Multi Function Meter with display parameter of Voltage, Ampere, KW, KWH, KVA, Frequency, PF, % THD, phase angle and LED Cluster Indicating lamps and 2 Amp control MCB suitable size CTs = 1No.Outgoings:- . 1. MCCB Four Pole 160amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting =2 Nos.2. MCCB Four Pole 125amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting =1 No.Changeover Switch : On Load Change Over Switch Four Pole 320amp., 415volts = 2 nos. complete in all respects as approved by engineer in charge at site. |
| 72 | 630 KVA CSS |
| 73 | Supply, erection, testing and commissioning of package type 630 KVA Compact Sub Station (Outdoor Type) Made from G.I. enclosure complete as per required conforming to IEC 62271-202 only and relevant IS specifications as applicable for the rating, Internal Arc of 21KA/1 Sec. IAC A & B on HT Compartment. complet with suitable sizes of GI pipe for incoming/outgoing cable/earthing strips etc. and consisting of following complete as required. Angle iron frame of size 40x40x5mm NS all along the corner of the foundation. Vacuum Interrupter,RMU,LT Switchgear and CSS Enciosure shall be with the Following descriptions: |
| 74 | Transformer: 630 KVA 11KV/433V DYN-11 Oil type, sealed energy efficiency level-2 transformer with corrugated wall, without conservator, type of design & Top Bushings for HT & LT with Off load tap changing switch of rating +5% to -10% @2.5%. Temp Rise-oil/Winding40/45 Deg cel. Losses (As per IS-1180 amended up to date. Impedance of 5%(Subject to IS Tolerance(as per IS1180-2014).The transformer shall be confirming to IS: 2026 and IS: 1180(part-I).1. Winding Temperature Indicator with Alarm and trip Contact. |
| 75 | HT Switchgear: 11kV 630Amps 21KA 3 sec. Non-Extensible Ring Main Unit Compact switchgear consisting of 1 no fixed motorized VCB module and one direct cable module in SF6 insulated stainless steel enclosure (2.5mm thick). Microprocessor based IDMT Relay for protection against overcurrent fault, earth fault, over voltage, open circuit, short circuit, Earth fault relay and Master relay. All the Load Break switch will have Fault Passage indicator. Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO. Multifunction meter with Modbus RS485 port & class 0.5 accuracy for each VCB module. CT shall be minimum 60/1A ,2.5VA for protection- 3 nos. 11KV/1.732/110V/1.732 Cast resin Bus PT single phase- 03 set. SF6 Gas pressure indicator.All modules of the RMU shall be suitable for cable termination of 3Cx300sq.mm AI XLPE Cable, incoming cable termination is included within the scope of work-1 Set. |
| 76 | LT Panel: Incoming:1000 Amps 433V 4P 50Hz 50KA Fixed Manual Type Air Circuit Breaker (ACB) microprocessor based 4 pole (100% FOR PHASES AND 100% FOR NEUTRAL) . LT panel made up of 1.5/2 mm thick CRCA sheet. Multifunction meter with Suitable CT. |
| 77 | BusBar: 1600 AMPS 4 pole Aluminium BUSBAR (100% FOR PHASES AND 100% FOR NEUTRAL) |
| 78 | Outdoor Encloser: Outdoor type encloser of 1.5 mm (For non load bearing members) & 2.0 mm (For load bearing members) thickness having modular construction of Galvanised Sheet Steel in suitable design for better heat dissipation and providing robust construction. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP 23 degree of protection for transformer compartment.The enclosure extior shall be painted with epoxy based powder paint (colour RAL7032).Each compartment will be provided with the door and pad locking arrangement. The design of the enclosure should be type tested for suitablly handling any arcing inside the compartment for providing better safety to the operator. The compartment illumination lamp with door operated switch shall be provided for each compartment. Vacuum Interrupter,RMU,LT Switchgear, Multifunctio meter and CSS Enciosure shall be of same make to ensure life cycle optimization. complete in all respects as approved by engineer in charge at site. |
| 79 | Providing Advance Lightning Protection System:- |
| 80 | Supply, installation, testing & commissioning of fully autonomous Early Streamer Emission Lightning Air Terminal (ESEAT) comprising of floating panels/body isolated from an earthed central finial/tip (elevated sharp tip) on top of the highest point to protect from direct lightning strikes with the following technical parameters. As per NF C 17-102 : 2011, (Annexe C), Clause C.3.4 ESE terminal is tested & certified for the below parameters. • ESE air terminal should be tested for an Impulse current (10/350 micro sec)=103 KA • Charge (Q) = 54.9 A.s • Specific Energy (W/R) = 2500 KJ/Ω and as per Clause C.3 all the tests should be carried out on a sample (preferably all tests in one lab) according to the flow chart in figure C.1 (Sequence of testing) pg 69 i. General tests, ii. Mechanical tests, iii. Environmental tests, iv. Electrical tests, v. Early Streamer Test (Δt in 10μs to 60 μs and standard deviation) • For the local certification, the ESE air terminal should be tested for switching impulse current of 40 KA (8/20 micro sec) or more. LPI is Tested & certified by CPRI (Central Power Research Institute), Govt of India for the Impulse current of 70 KA with 5 positive & 5 negative impulse • The International testing laboratory should be duly accredited by ILAC / IEC / ENAC / EZU / UL to ensure the genuine testing and the quality of the product. The serial number displayed on the ese lightning arrester is duly supported with the \\"certificate of country of origin\\" issued and duly sealed by the Australian Government \\"Chamber of Commerce & Industry\\". Complete in all respect and as per design and size approved by engineer incharge at site. |
| 81 | GALVANIZED IRON PIPES AND G.I. EARTHING: Supply & erection of G.I. pipe (A-Class) as per IS:1239 (Part-I) 2004 including sockets, bends, inspection boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:- |
| 82 | Galvanized Iron Pipe 50mm dia. (A-class) Flushed |
| 83 | COPPER EARTHING (Upto 14 metre in Length):-iii- Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 84 | Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length) |
| 85 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 86 | Overall size 70sq.mm (Un-sheathed) |
| 87 | Add 1% Cultural Cess Total in Figures 10620219.0 10620219.0 INR One Crore Six Lakh Twenty Thousand Two Hundred & Nineteen Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |