| 1 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisationthickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joinedwith connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GIangle, GI bolts & nuts, fastner etc as required.150 mm width X 50 mm depth X 1.6 mm thickness |
| 2 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 5 x 4 sq. mm |
| 3 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisationthickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joinedwith connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GIangle, GI bolts & nuts, fastner etc as required.450 mm width X 50 mm depth X 2.0 mm thickness |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 2 x 2.5 sq. mm |
| 5 | Supply of Electrician/Technician for Fixing Lights |
| 6 | Supply of Helper (Technician) for Fixing Lights |
| 7 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole and neutral |
| 8 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A |
| 9 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 10 | Supplying and fixing Cable End Box (Junction Box/Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required. |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way , Double door |
| 12 | Supply of LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy >135 lm/Watt) Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, Watt output. 50 watt Please Enable Macros to View BoQ information |