| 1 | ELECTRIFICATION WORK |
| 2 | 90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame) |
| 3 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 4 | OD98851/2025-2026:Supply and fixing 200A fuse |
| 5 | OD98854/2025-2026:Supply and fixing 100 A Nuetral link. |
| 6 | OD98857/2025-2026:Supply and fixing 200/5 A,15 VA,Accuracy class 0.5,Resin cast metering CT |
| 7 | 90.12.7.32:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm |
| 8 | 9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) |
| 9 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 10 | 90.14.3.4:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardSupply and providing 40 x 3mm heavy duty flat neoprene gasket in the panel board |
| 11 | 2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 12 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 13 | OD98915/2025-2026:Supply and fixing led indicators for all voltage ranges |
| 14 | OD98930/2025-2026:Supply and wiring with pvc insulated strandedsingle core copper conductor cables for interconnecting the control devices/equipments including wiring firm by suitable tie/tie mounts/pvc duct etc as required.1.5 sqmm single run |
| 15 | 90.14.11.2:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 125A to 200A with CBCT. |
| 16 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 17 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 18 | 90.14.10.13:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 19 | 90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 20 | 90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 21 | 90.14.10.10:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16A -100A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 22 | 2.10.5:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole and neutral |
| 23 | 2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N |
| 24 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 25 | 2.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole |
| 26 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 27 | OD125439/2025-2026:Earthing with G.I. earth pipe 2 metre long 40 mm dia (medium class) including providing 12 mm dia drilled holes minimum 20 nos along the entire length in alternate arrangement providing 40x25 mm GI reducer at top and test joint using 2 nos ,25x3mm GI Strip minimum size 25 cm suitably shaped and tightly clamped to the pipe electrode using 25x6 mm steel bolts nut and washer and providing 2 nos, 6 mm dia drilled holes for clamping and bolting earth lead , and making masonry champer with cover plate having locking arrangement and etc. ( charcoal and salt as required shall be filled at 30 cm dia around the earth electrode) |
| 28 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 29 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 30 | 90.11.1.16:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 31 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 32 | 90.12.1.15:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3 core 16 sq mm |
| 33 | 2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 34 | 2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 35 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 36 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 37 | 90.12.1.27:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 25 sq mm |
| 38 | 90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm |
| 39 | 1.14.3:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 40 | OD125479/2025-2026:Charges for preparing drawing of the complete Electrical installation after completion of the present work and preparing completion report with KSEB service connection application form and submitting to the consumer for availng 1 phase service connection/Load regularization |
| 41 | 9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 42 | 9.1.8:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 16 sq. mm (25mm) |
| 43 | OD125485/2025-2026:Supply and wiring with pvc insulated stranded single core copper conductor cables for interconnecting the equipments including wiring firm by suitable tie/tie mounts/pvc duct etc as required 10 sqmm single run |
| 44 | OD125487/2025-2026:Supply and wiring with pvc insulated stranded single core copper conductor cables for interconnecting the equipments including wiring firm by suitable tie/tie mounts/pvc duct etc as required 6 sqmm single run |
| 45 | OD125488/2025-2026:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 40/32 mm or nearest size |
| 46 | 90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm |
| 47 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 48 | 90.6.5.13:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 4.00 sq mm |
| 49 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 50 | 1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 51 | OD127831/2025-2026:Supply & Fixing 2module metal box with white/ off-white front plate provided with one 20A DP switch modular type in recess including making good the damages, colour washing etc as required (ROHS) including giving connections (Modular boxes ,switches and accessaries ,Make-Legrand Myrius/MK Blenz/Havells Oro/Hager/L&T) |
| 52 | OD127841/2025-2026:Supply, Installation, Testing and Commissioning of wall mounting split air conditioner unit of the following ratings conforming to relevant IS suitable for operating on 230V, 50Hz single phase AC supply, filled with R32/410A ecofriendly refrigerant gas, high energy efficient, RoHS complaint, capable of performing functions like cooling, dehumidifying, air circulating, filtering etc of following capacity including refrigerant copper piping 3m with insulation, control cable up to 3-5m, 3 m drain pipe, Copper Condenser, stand, microprocessor control with cordless remote control etc. PCB should have minimum 5 year warranty and 10 year warranty on compressor(warranty card are to be provided). Minimum 2 Nos free service per year for the entire guarantee period and it should be ensured that the air conditioner is in perfect working condition during this period. 2 TR 5 Star Inverter A.C unit, (Blue star/LG/ Daikin carrier/Panasonic/Hitachi or equivalent). |
| 53 | OD127847/2025-2026:Supply, Installation, Testing and Commissioning of wall mounting split air conditioner unit of the following ratings conforming to relevant IS suitable for operating on 230V, 50Hz single phase AC supply, filled with R32/410A eco friendly refrigerant gas, high energy efficient, RoHS complaint, capable of performing functions like cooling, dehumidifying, air circulating, filtering etc of following capacity including refrigerant copper piping 3m with insulation, control cable up to 3-5m, 3 m drain pipe, Copper Condenser, stand, microprocessor control with cordless remote control etc. PCB should have minimum 5 year warranty and 10 year warranty on compressor(warranty card are to be provided). Minimum 2 Nos free service per year for the entire guarantee period and it should be ensured that the air conditioner is in perfect working condition during this period. 1 TR 5 Star Inverter A.C unit, (Blue star/LG/ Daikin carrier/Panasonic/Hitachi or equivalent). |
| 54 | OD127848/2025-2026:Supply conveyance installation testing and commissioning of 4 KVA Voltage stabiliser (V-guard) with input voltage 170 to 270 V and out put voltage range of 210 to 230 V with over load protection(cutt off) time delay,indicators,etc.as required. |
| 55 | OD127849/2025-2026:Supply and Fixing of 5 KVA voltage stabilizer for split type A/C unit with voltage range of 175-275V and out put range of 210 - 240V Suitable for 2 TR AC unite (V-Guard or its equivalent) - (Rate exclusive of GST) |
| 56 | OD127851/2025-2026: Supply and providing 20MM ISI watering pipe (M) |
| 57 | OD127852/2025-2026:supply and providing additional length of 22 gauge soft drawn copper pipe 5/8/equivlent size as suction pipe including insulation suitable rubber seal from the sleeve and giving connection etc as required |
| 58 | OD127853/2025-2026:Supply and providing additional length of 22 gauge soft drawn copper pipe 3/8/equivlent size as delivery pipe including insulation suitable rubber seal from sleeve and giving connection etc as required |
| 59 | 90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point |
| 60 | 90.3.20.4:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 2X20W LED Lamp with box type fixture Please Enable Macros to View BoQ information |