Name of Work:- fo|qr forj.k [k.M&csgV ds dk;Z{ks= esa fctusl Iyku 2026&27 ds vUrxZr 11 ds0oh0 ohlhch cnyus] midsUnzks ij ekLVj fjys o MCyw0Vh0vkbZ0@vks0Vh0vkbZ0 cnyuk] [kjkc fjys cnyuk] 33 ds0oh0 lh0Vh0 ih0Vh0 cnyuk] Lohp;kMZ esa 11 ds0oh0 Vh0ih0,e0vks0 LFkkfir djuk] rFkk edsfudy fjys dk gVkdj fMftVy fjys cnyus dk dk;Z] ¼11 ds0oh0 oh0lh0ch0 cnyuk rFkk 33@11 ds0oh0 midsUnzks dk lqn`
Sl. No.
Item Description
1
Detail of Work
2
Providing and fixing of Electronic (E/F/& O/C PROTECTION Digitel RELAY with complete housing.
3
Safely Carriage of 33 KV PT & CT from ESC SRE to site of work including loading and unloading at both ends (distance 0 to 50 KM)
4
Safely Carriage of 11 KV Outgoing VCB 200/100/5A/11 KV Incomming VCB 300/600/5A from ESC SRE to Site of work including loading and unloading at both ends.
5
Safely Carriage of 11 KV TPMO from ESC SRE to site of work including loading and unloading at both ends (distance 50 KM)
6
Safely Installation of 11 KV TPMO with polymer pin insulator and connection properly.
7
Safely Installation of 11 KV Outgoing VCB/Incomming VCB and connection properly.
8
Water Earthing of 11 KV VCB by boring of 60 Ft deep & fixing of 60 ft. G.I pipe 11/2\\" Dia (Jindal Class B) and connecting with G.I. Strip of size 40x5 mm and G.I wire at bottom of G.I pipe to the 11 KV VCB providing of required charcoal & salt in the pipe
9
Safely installation of 33 KV Outdoor PT (33KV/110 Volt) and connection properly.
10
Safely installation of 33 KV CT (200/100/1-1-1A) and connection properly.
11
Safely removal of old and used 11 KV O/G and I/C VCB from Site to ESC SRE including loading and unloading at both ends.
12
Safely removal of old and used CT/PT from Site to ESC SRE including loading and unloading at both ends.
13
Providing and fixing of Feeder/VCB name Plate
14
Providing and installation of WTI Meter For Power T/F
15
Providing and installation of OTI Meter For Power T/F
16
Safely removal of old and used Relay from site to ESC SRE including loading and unloading at both ends.
17
Safe cartage of Dog Conductor from ESC,SRE, to the site of work including loading & unloading at both ends. (Dist. Upto 50 km.)
18
Laying, lifting, Stringing, sagging jumpring & binding of ACSR Dog Conductor for 11KV/LT Line including complete.
19
Providing and fixing MS Channel 100x50x2028 mm
20
Providing and fixing of Holding Clamp for Top channel TPMO with bolt and nut Please Enable Macros to View BoQ information