| 1 | Testing of 11 kv. Incoming/Outgoing panel including testing of CTR by primary injection. Testing of relay, checking closing and triping operation of VCB on remote/manual and protection trip, checking of whole trip circuit of VCB, rewiring of VCB, relay and master trip relay if needed for proper tripping, trip testing by command generated through Primary injection, Lubrication & tightening of all contacts testing of relay and control wiring and other associated work |
| 2 | Testing of 33/11 KV 05/10/15 MVA Power Transformer installed at various substations of 33 KV Vrindavan division, Amausi zone Lucknow tests to be carried out on transformers are :- a) No load Ratio Test, b) Short circuit test c) Magnetization Current Test, d) Magnetic Balance Test, e) Insulation Test (I.R.Value test), f) Buchholz OTI/WTI Circuit test, g), measurement of earth resistance of transformer neaural, testing of complete circuit of bushels relay, PRV, MOG, annunciation/indication circuit etc. preparing & submitting of complete test report. |
| 3 | Testing of 33 KV breaker panel breakers including testing of CTR by primary Injection kit. Works Includes clearing and adjustment of relay contacts & checking/setting of relay configuration for proper tripping, checking of Closing and tripping of breakers on remote/manual switches, checking of protection trip Command through realy and CT by means of Primary Injection, Lubrication & tightening of all contacts testing of relay and control wiring and other associated work. |
| 4 | Retrofitting of different make protection relay i.e. O/C&E/F, diff. relay after cutting of proper size slot in control panel if needed, complete wiring of relay, configuration of relay as per UPPCL standard/requirement, testing of proper operation of relay by primary/secondary injection test kit, testing of trip/close and indication circuit of associated VCB and removing of wiring fault, if any. |
| 5 | Overhauling including proper cleaning of all moving parts, cleaning of electrical contacts with CRC, lubrication & proper adjustment of mechanism of 33KV & 11KV different make VCB for proper operation of VCB, tracking & removing of wiring fault in VCB, if any. |
| 6 | Opening of complete 11 KV Bush bar in case of emergency break down, its cleaning with thinner & rebolting & replacement of damage, if required & proper checking 11 KV bush bar nut bolt tightness. |
| 7 | Attending emergency break down of 11 KV VCB including cleaning of all electrical contacts with CRC, cleaning of dust/smoke deposited in panel cubical with thinner, cleaning of spouts, replacement of damaged/burnt parts of VCB, tracing & removing of burnt wiring rewiring & proper dressing of wiring in VCB. |
| 8 | In emergency break down replacement of defective and damaged CT by new CT with all its accessories with proper fixing 11 KV/33KV Breaker, (CT will be provided by the department) |
| 9 | Attending emergency break down occurred in 33kv Out Door Vacuumed Circuit Breaker mechanism for smooth operation for tripping of breaker including cleaning of dust/smoke deposited in panel with thinner, cleaning of spouts all electrical contacts with CRC, setting alignment of close/trip coil assembly with panel of Breaker. |
| 10 | Repairing/Recondition of spring charging assembly, replacement of damaged charging gear, ratchet, roller bearing including replacement of damage bush, nut bolt and washer. |
| 11 | Providing and fixing of 11 KV Vacuum interrupter of different make VCB |
| 12 | Providing and fixing of Spout Different make VCB. |
| 13 | Providing and fixing of Closing Coil Different make VCB. |
| 14 | Providing and fixing of Tripping Coil Different make VCB |
| 15 | Providing and fixing of Male contract for different make VCB |
| 16 | Providing and fixing of Female Contract for different make VCB |
| 17 | Providing and fixing of breaker control switch (TNC) for different make VCB |
| 18 | Providing and fixing of Auxiliary rotary switch for different make 33 kv and 11 kv VCB Please Enable Macros to View BoQ information |