| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 6 | 4 X 25 sq. mm + 2 X 10 sq. mm earth wire |
| 7 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 8 | Group C |
| 9 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 10 | 3 x 2.5 sq. mm |
| 11 | Supplying and fixing of following sizes of medium class PVC/Flexible PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 12 | 20 mm |
| 13 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 14 | 5/6 amps switch |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 17 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 18 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 19 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 20 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 21 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 22 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 23 | Group B |
| 24 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 25 | Supply and fixing following size DLP plastic trunking including all necessory accessories |
| 26 | DLP Pastic Trunking 105x50mm with cover including all accessories (flexible cover,end cap, junctions, joints, wall crossing, VDI accessories etc. as per site condition) |
| 27 | Supplying and fixing suitable size modular plate and cover in front on existing DLP trunking, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet (3 modular) and 15/16 A modular switch, connections etc. as required. |
| 28 | Supply and fixing following size DLP plastic trunking including all necessory accessories - Supplying and fixing suitable size modular plate and cover in front on existing DLP trunking, including providing and fixing 3 pin 5/6 A modular socket outlet (3 modular) and 5/6 A modular switch, connections etc. as required. |
| 29 | MCCB, MCB & DB'S |
| 30 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board/SMDB including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 31 | 100 A, 16 KA,TPMCCB |
| 32 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 33 | 6 way , Double door |
| 34 | 8 way , Double door |
| 35 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 36 | 8 way (4 + 24), Double door |
| 37 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 38 | Single pole |
| 39 | Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. |
| 40 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 41 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 42 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCB and MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 43 | 6 way (160 MCCB + 18), Double door |
| 44 | Supplying and fixing following rating, following pole, 415 V, C curve MCB suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 45 | 40-63 A TP |
| 46 | 40-63 A FP |
| 47 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release, Electronic earth leakage module and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 48 | 100 A, 16 KA with electronic earth leakage module |
| 49 | CABLE TRAYS |
| 50 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 51 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 52 | EARTHING |
| 53 | Supplying and fixing 12 SWG copper wire on surface or in recess for loop earthing as required. |
| 54 | LED LIGHT |
| 55 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim |
| 56 | 18 watt |
| 57 | LED Suspended Luminnaire |
| 58 | Supply and fixing of 20W Suspended downlight luminaire downlight having 52mm wide aluminum extruded Profile finished in white powder coated. Snap fit high translucent frosted PS diffuser, 5700K, CRI >80, Efficacy >110 lm/watt, THD <10% driver efficiency >90 PF> 0.95 cool white LED including 4kV Surge protection, IP 40 or higher rated protection, complete with all accessories etc, as required. (TCP-145-20-57-HL2-DP-12-NWH) *** Bidder should submit OEM warranty certificate minimum 03 year or above along with supply of product at site. |
| 59 | BLDC FAN |
| 60 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 61 | 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 230 CM/Min (Minimum) |
| 62 | MV CABLE LAYING |
| 63 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 64 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 65 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 66 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 67 | MV CABLE JOINTING & END TERMINATION |
| 68 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 69 | 3½ X 25 sq. mm (28mm) |
| 70 | 3½ X 35 sq. mm (32mm) |
| 71 | LABOUR |
| 72 | Removing following items, handing over to EMU store safely as required. |
| 73 | Tube light and Light fixture with/with out rad/clamp |
| 74 | Cealing fan with rad, regulator from switch board, including stacking of fan leafs |
| 75 | Switch board of any size including wires, switches(modular/piano type) switch board, clamps, GI/plastic box etc. as required |
| 76 | CABLE |
| 77 | Supply of following size PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988 |
| 78 | 3.5x35 Sq.mm |
| 79 | 3.5x25 Sq.mm Please Enable Macros to View BoQ information |