| 1 | Taking down carefully copper /aluminium point wiring (light, fan socket or power) through stove enamelled steel conduit/pvc conduits including complete fittings such as switches, ceiling roses, pendants, regulators, sockets,, switch sockets, electrical fittings etc removing and making good disturbed surfaces of walls/ceiling etc, complete all as specified and directed. |
| 2 | Supply in replacement of LED Tube light luminaires, 20-22 watts, lumen output not lessthan 2000 (4 feet), made Engineering plastic batten housing, with high transmissivity diffuser, high lumen output, with suitable integrated electronic driver, and operated in single phase, 230 volts, 50HZ, all accessories internally pre-wired and including connecting up with three core twisted flexible copper conductor cable of from connector and ceiling rose, complete all as specified and directed. |
| 3 | Supply and fix in repair/replacement LED batten with 24W LED tube light in wall/surface connecting with all required accessories like PVC box base,flexible cable from ceiling rose etc Surface and wall mounted LED batten, Engineering plastic batten with accessories complete all as directed and specified by engr-in-charge. |
| 4 | Supply and fix LED recess/surface mounted 2x2 luminarie 35/36w fitting, 220 V, AC,50HZ suitable surge protection, high power factror,driver etc complete including flexible wire and connected accessories all as specified and directed by engr-in-charge. |
| 5 | Supply & fixing in replacement of 45/50 watt LED recess/surface mounted 2'x2' size flat panel fabricated CRCA sheet housing,duly powder coated with high efficient LED glare free full opal diffuser , IP20 andwith system efficacy of 120lm/W which provide soft light and glare free symmertical illumination suitable for armstrong / snap grid ceiling of 2'x2' size(Lumen output not lessthan 3600) complete all as specified and directed. |
| 6 | M & L for point wiring with PVC insulated unsheathed electric cable 1100 volts grade, single core, FRLSH cable having multistranded copper conductor of 1.5 Sqmm nominal cross sectional area, ISI marked, drawn in existing concealed conduit with 1.5 Sqmm green PVC insulated unsheathed multistranded copper conductor FRLSH cable, ISI marked as continuous earth conductor connected to earth dolly by providing suitable lugs including 3.0 mm new laminated hylum sheet /masonite sheet cover cover of min thick , ISI marked of Make\\" Hylem\\" of suitable sizes to be fixed/ mounting on existing MS/ GI sunkun boxes for mounting of fittings like switches, sockets, fan regulators etc fixed with galvanised screw and cup washer. complete all as specified and directed for the following. Note : Wiring to be done as per arroved colour code. (a) One light/call bell point controlled by one switch |
| 7 | (b) One fan/exhaust fan point controlled by one switch |
| 8 | (c) One 5 pin socket outlet 5 Amps on same board |
| 9 | (d) One 5 pin socket outlet 5 Amps on independent board |
| 10 | (e) One light point controlled by 2 way switch SP, 5 Amp, 240 Volts |
| 11 | Supply and fixing in repair / replacement of LED batten with 9/10 W LED tube light two feet mirror type with sensor in wall/surface connecting with all required accessories like PVC box base, flexible cable from ceiling rose etc surface and wall mounted LED batten, engineering plastic batten with accessories complete all as directed and specified by Engr-in-charge. |
| 12 | Supply and fix in repair / replacement LED batten with 20W LED tube light (four feet) with inverter type with 2 hrs backup in wall/surface connecting with all required accessories like PVC box base, flexible cable from ceiling rose etc surface and wall mounted LED batten, Engineering plastic batten with accessories complete all as directed and specified by engr-in-charge. |
| 13 | Supply and fix in repair / replacement HIGH BAY LED lights hanging / ceiling mounting type 100w fitting with PC diffuser with surge protection on existing light point with suitable hanging arrangements complete all as specified and directed. Note:- The rates includes taking down old light fitting and providing suitable necessary ladders /equipments for any height to taking down the items. |
| 14 | Supply and fix in repair / replacement Low BAY LED lights hanging / ceiling mounting type 40/45W fitting with PC diffuser with surge protection on existing light point with suitable hanging arrangements complete all as specified and directed. Note:- The rates includes taking down old light fitting and providing suitable necessary ladders /equipments for any height to taking down the items. |
| 15 | S&F in repair / replacement emergency bulb LED 10W, 230V, 50Hz, with 2/4 hour backup complete all as specified and directed. |
| 16 | Supply and fix in repair / replacement round / square type, recessed /surface 12W/14W warm white LED downlight dimmable with high lumen 230V, compatible with Legrand Dimmer as per sample complete as as directed by Engr-in-charge. |
| 17 | Supply in replacement decorative indoor wall light fixture metalic body single head wall light suitable for 20 watt maximun wattage complete all as specified and as directed. |
| 18 | Supply and fix in repair / replacement LED batten with 20/22 Watts LED tube light (four feet) with sensor in wall / surface connecting with all required accessories like PVC box base, flexible cable from ceiling rose etc Surface and wall mounted LED batten, engineering plastic batten including with accessories complete all as directed and specified by engr-in-charge. |
| 19 | M & L for point wiring with 1.5 Sqmm single core, multi stranded copper conductor 1100 V grade, ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLSH cable drawn in casing caping of 25 mm wide, with double locking type, ISI marked including all accessories casing caping as approved by EIC, with PVC 1.5 mm multi stranded insulated unsheathed FRLSH copper wire, ISI marked of green colour for continous earth, including sunken box made out of suitable thickness and not less than 60 mm in depth GI/MS/ prssed steel terminal box to be conclead in wall, duly painted including 3mm hylum /masonite sheet cover, for mounting of fittings like switches, sockets, fan regulators etc. fixed with galvanised screw and cup washer complete all as specified and directed for the followings:- Note : Wiring to be done as per approved colour code.(a) One light /fan/ call bell point controlled by one switch |
| 20 | (b). One light point controlled by 2 way switch SP, 5 Amp, 240 Volts |
| 21 | (c). one 5 amp socket point on same board |
| 22 | (d). one 5 amp multi socket indepenedent |
| 23 | All as per sl item No. 15 hereinbefore, but using 2.5 sqmm ( nominal area) multistranded FRLSH copper conductor cable/wire & 2.5 sqmm size PVC insulated unsheathed copper conductor cable for earth continuity ( green colour) for one 5 pin socket outlet 5 / 15 Amp multi purpose independent point controlled by 15 Amp switch, SP one way, 240 Volts & Socket, complete all as specified and directed. |
| 24 | All as per sl item No. 15 hereinbefore, but using 4 sqmm (nominal area) FRLSH multistranded copper conductor cable/wire for one 5/15 Amp socket point controlled by 15 Amp switch, SP one way 240 Volts & Socket, complete all as specified and directed. |
| 25 | S & F in repair / replacement Socket outlet 2 in 1, 3 pin, 6 Amp flush type (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 26 | S & F in repair /replacement Switch bell push flush type 5 Amp (ISI marked) all as per complete all as specified and directed Engineer-in-Charge. |
| 27 | S & F in repair / replacement Switch socket combination outlet 16 Amp, 5-in-1, controlled by one switch (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 28 | S & F in repair / replacement Socket outlet 2 in 1, 3 pin, 6 and 16amp flush type flush type (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and fix in repair / replacement modular bell push 6A 1 module complete all as specified and directed all specified and directed. |
| 30 | S & F in repair / replacement Bell buzzer, ding dong AC,230V, 50hz single pole complete all as specified and directed all specified and directed. |
| 31 | Supply and fix in repair / replacement modular cover plates with frame up From 1 /2 to 3 module as per site requirements all as specified and directed. |
| 32 | S & F Switch socket combination 2 in 1 3 pin, 5 A and 15Amp flush type universal complete all as specified and directed. |
| 33 | S & F socket 3 pin 5 A flush type, complete all as specified and directed. |
| 34 | S & F Bell buzzer 240v 50hz complete all as specified and directed. |
| 35 | S & F Bell push 240v 50 hz complete all as specified and directed. |
| 36 | Supply and fix in repair / replacement modular switch 1 module 6 amp one way ISI marked complete all specified and directed. |
| 37 | Supply and fix in repair / replacement modular switch 1 module 16 amp one way complete all as specified and directed. |
| 38 | M & L for concealed point wiring with 1.5 Sqmm single core, multi stranded copper conductor 1100 V grade, ISI marked , PVC insulated unsheathed cable (with approved colour code) FRLSH cable in CONCEALED PVC , ISI marked including all accessories as approved by EIC, with PVC 1.5 mm multi stranded insulated unsheathed FRLSH copper wire, ISI marked of green colour for continous earth, including sunken box made out of suitable thick and not less than 60 mm in depth GI/MS/ pressed steel terminal box to be concealed in wall, duly painted including laminated hylum/maonite sheet cover thickness 3mm for mounting of fittings like switches, sockets, fan regulators etc. fixed with galvanised screw and cup washer complete all as specified and directed for the followings:- Note : Wiring to be done as per approved colour code.(a). One light /fan/ call bell point controlled by one switch |
| 39 | (b). One 5 pin socket outlet 5 Amps on independent board |
| 40 | (c). One 5 pin socket outlet 5 Amps on same board |
| 41 | (d). One light point controlled by 2 way switch SP, 5 Amp, 240 Volts |
| 42 | All as per item No. 31 above but with 2.5 sqmm multi stranded copper conductor 1100 volts grade FRLSH PVC insulated sheathed cable with FRLSH PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continues earth on independent board, complete all as specified and directed |
| 43 | All as per item No.31 above but with 2.5 sqmm multi stranded copper conductor 1100 volts grade FRLSH PVC insulated sheathed cable with FRLSH PVC 2.5 Sqmm multi standard insulated unsheathed copper wire for continues earth on independent board, complete all as specified and directed |
| 44 | Supply and fix in repair/replacement modular cover plates with frame up from 4 to 12 module as per site requirements complete all as specified and directed |
| 45 | Supply and fix in repair/replacement modular metal flush box as per site requirements from 1/2 to 3 modules complete all as specified and directed. |
| 46 | Supply and fix in repair/replacement modular metal flush box as per site requirements from 4 to 12 modules complete all as specified and directed. |
| 47 | S&F in replacement of LED tube rod 18/20 watt with high efficacy, lumen output not lessthan 100 lm/W (4 feet), made of crystal glass, high lumen output, and operated in single phase, 230 volts, 50HZ, suited for installation in existing tube light luminaire complete all as specified and directed. |
| 48 | S&F in repair / replacement of batten MS suitable for 18/22/24W LED rod 220V, AC, 50HZ with accessories including suitable 1.5 sqmm 2 core wire for connecting with ceiling rose complete all as specified and directed. |
| 49 | S&F in replacement of mirror light batten type 10 W 230V AC, 50Hz, Pf >0.98, THD <10% on wall complete all as specified and directed by Engineer in charge. |
| 50 | S&F in replacement of LED concealed COB/spot light fixture 12 Watt , tiltable with decorative finish of warm white coloured complete all as specified and as directed by Engr in charge. |
| 51 | S&F in replacement of outdoor surface LED COB / surface light (IP 54) light fixture 12 Watt , with decorative finish of white/ warm white coloured complete all as specified and as directed by Engr in charge. |
| 52 | M&L for Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLSH cable of 4.0 Sqmm (with colour code), drawn in existing surface/ recessed steel/ PVC conduit/ PVC casing capping/suitable size, including one run of PVC insulated unsheathed, multistranded copper conductor FRLSH cable of 4.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in complete including taking down of olf wiring etc. complete all as specified and directed by Engr-in-Charge |
| 53 | All as per item No.42 above but for size 2 core 6 sqmm + 1 core 6.0 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 54 | All as per item No.42 above but for size 2 core 10 sqmm + 1 core 10.0 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 55 | All as per item No.42 above but for size 2 core 2.5 sqmm + 1 core 2.5 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 56 | M&L cutting of wall/ceiling/column for laying submain of any size including plastering ,white wash all specified and directed in charge. |
| 57 | S&F double door MCB DB made out of 18 SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts 100 Amps rated bus bar 12 way double door open able, including taking out old unsv MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 58 | S&F double door MCB DB made out of 18 SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SPN 240 volts 100 Amps rated bus bar 8 way double door open able, including taking out old unsv MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 59 | S&F double door MCB DB made out of 18 SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SPN 240 volts 100 Amps rated bus bar 4 way double door open able, including taking out old unsv MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 60 | S&F double door MCB DB made out of 18 SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SPN 240 volts 100 Amps rated bus bar 2 way double door open able, including taking out old unsv MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 61 | Supply and fixing switch piano type flush button type single pole one way 5 Amps 240V front operated complete all as specified and directed. |
| 62 | S & F ceiling rose PVC/polycarbonate, isolated body surface Bakelite 65mm dia three terminals complete all as specified and directed. |
| 63 | S & F in repair / replacement of switch piano flush button single pole one way, 6 Amp (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 64 | S & F in repair/replacement Switch socket combination 2 in 1, 3 pin, 6 Amp flush type (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 65 | S & F in repair/replacement Switch flush button, single pole two way, 6 Amp (ISI marked) complete all as specified and directed by Engineer-in-Charge. |
| 66 | S & F in repair/replacement stepped type electronic fan regulator flush type for ceiling fan of suitable size, complete all as specified and directed by Engineer-in-Charge. |
| 67 | S & F in repair / replacement Lamp holder / angle holder insulated body with black / white plate for batten fittings, complete all as specified and directed by Engr-in-Charge |
| 68 | Supply and fix in repair / replacement modular step type fan regulator 120 watt, AC, 220V, 50hz, ISI marked complete all as specified and directed by Engr-in-Charge |
| 69 | Supply and fix in repair / replacement modular socket 2 module universal type 5/6 amp one way complete all as specified and directed by Engr-in-Charge |
| 70 | Supply and fix in repair/replacement modular socket 2 module universal type 6/16 amp one way complete all as specified and directed by Engr-in-Charge |
| 71 | M&L for MS sheet of thickness 2/3mm for cover of DBs / panels including fabricaton, welding & machining of any size etc. complete all as specified and directed by Engr-in-Charge |
| 72 | S & Fix in repair / replacement RCBO 40 Amps double pole 30mA breaking capacity complete all as specified and directed. |
| 73 | S & Fix in repair / replacement RCBOs 25 Amps double pole 30mA breaking capacity complete all as specified and directed. |
| 74 | M&L for Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLSH cable of 4.0 Sqmm (with colour code), drawn in but including non metallic rigid PVC conduit of 25mm dia/casing capping/ suitable size , ISI marked including one run of PVC insulated unsheathed, multistranded copper conductor FRLSH cable of 4.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in surfaces/ recess complete including taking down of old wiring complete all as specified and directed by Engr-in-Charge |
| 75 | All as per item No.64 above but for size 2 core 6 sqmm + 1 core 6.0 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 76 | All as per item No.64 above but for size 2 core 10 sqmm + 1 core 10.0 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 77 | All as per item No.64 above but for size 2 core 2.5 sqmm + 1 core 2.5 sqmm as earth wire, complete all as specified and directed by Engr-in-Charge |
| 78 | S&F double door MCCB VTPN DB 4 WAY made out of 18SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts suitable Amps rated bus bar 4 way, including taking out of old unserviceable MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 79 | S&F double door MCCB VTPN DB 6 way made out of 18SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts suitable Amps rated bus bar 4 way, including taking out of old unserviceable MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 80 | S&F double door MCCB VTPN DB 8 way made out of 18SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts suitable Amps rated bus bar 4 way, including taking out of old unserviceable MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 81 | S&F double door MCCB VTPN DB 12 way made out of 18SWG CRCA steel sheets, Phosphates powder coated with copper bus bar, Earth stud, Din Rail, Polyamide Terminal Blocks for incoming and outgoing circuits, inbuilt loose wire box, Ground terminal blocks, duly pre-wired with thimble flame retardant copper conductors and poly layer for protection SP 240 volts suitable Amps rated bus bar 4 way, including taking out of old unserviceable MCB DB any size/type, complete all as specified and directed by Engr-in-Charge. |
| 82 | S & F in repair / replacement of MCCB 4 pole, thermal magnetic release range 160 Amps of breaking capacity 25 kA, 415 Volts, 50 Hz, complete all as specified and directed by Engr-in-Charge |
| 83 | S & F in repair / replacement MCCB 4 pole, thermal magnetic release range 100 Amps of breaking capacity 16 kA, 415 Volts, 50 Hz, complete all as specified and directed by Engr-in-Charge |
| 84 | S & Fin repair / replacement MCCB 4 pole, thermal magnetic release range 125 Amps of breaking capacity 16 kA, 415 Volts, 50 Hz, complete all as specified and directed by Engr-in-Charge |
| 85 | S & F in repair / replacement MCCB 4 pole, thermal magnetic release range 63 Amps of breaking capacity 16 kA, 415 Volts, 50 Hz, complete all as specified and directed by Engr-in-Charge |
| 86 | S & F in repair / replacement MCCB 4 pole, thermal magnetic release range 40 Amps of breaking capacity 16 kA, 415 Volts, 50 Hz, complete all as specified and directed by Engr-in-Charge |
| 87 | S&F in repair / replacement of 6 to 32 Amps, MCB single pole 240 V 10 KA (C-Series) complete all as specified and directed. |
| 88 | S&F in repair / replacement SPN 32 Amps, MCB DP 240 V 10 KA (C-Series) complete all as specified and directed. |
| 89 | S&F in repair / replacement RCBO 63 Amps double pole 30mA breaking capacity complete all as specified and directed. |
| 90 | Supply and fixing LED building security light fitting including with suitable size bracket / angle and three core flexible copper wire suitable to fixing security light of 45 watts, IP 66 protection complete all as specified and directed by Engr-in-Charge |
| 91 | M&L for preparation of steel surfaces by removing of rusted paint with brush, cleaning and applying two coats of synthetic enamel paint on existing DBs / panels / meter box of any size complete all as specified and directed by Engr-in-charge. |
| 92 | Taking down of old recess mounting 2'x2', LED light luminaire 24-36W from ceilings and re-fixing the same after doing necessary repair works or by replacing requisite spare parts of reccess light complete all as specified and as directed. Note: LED driver and surge protection device will be measured and paid separately. |
| 93 | Supply and Fixing in replacement of LED Driver 33-45 Watts with surge protection device of recess mounting 2' x 2', LED light luminaire, IP65, complete all as specified and as directed. |
| 94 | Supply and Fixing in replacement of electronic LED driver for wall security light of 30/45 Watt LED complete all as specified and as directed. Make: as per sample |
| 95 | S&F of LED Bulk head fittings 9/10W luminaire including LED light driver holder 220 V, AC, 50HZ connecting up with three core flexible copper conductor calbe of suitable size including with all acccessories complete all as specified and directed by engr-in-charge. |
| 96 | Excavation in trenches for not exc 1.5 mtr wide and not exc 1.5 mtr depth and getting out in soft/loose soil including taking out faulty cable/cable covers and GI pipe complete all as specified and directed. |
| 97 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified & directed. |
| 98 | Removing excavated materials n.exc 50m and depositing where directed at a level n.exc 1.5m above the Starting point, complete all as specified and directed |
| 99 | M & L for dry river sand as sand cushioning for protection of underground cable including punning of sand in layers complete all as specified and directed |
| 100 | Supply & laying un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm complete all as specified and directed |
| 101 | Taking out old un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm complete all as specified and directed |
| 102 | Laying only un-reinforced precast concret cable cover class LV type 1, flat size 250mm x 150mm x 40 mm complete all as specified and directed |
| 103 | S&F of 50mm bore GI pipe, light grade including with all fittings & fixtures, laid in trenches, complete all as specified and directed |
| 104 | Supply and fix flexible wire 1 sqmm X 2 core including taking down of old wire, complete all as specified and directed |
| 105 | Supply and fix in repair/replacement of led bulb of 9/10 watts complete all as specified and directed by Engr-in-Charge |
| 106 | Supply and fix of decorative light suitable for holder B-22/E-27, complete all as specified and directed by Engr-in-Chargecharge |
| 107 | Taking down of tube light, mirror light & other similar light etc after re-fixing the same after cleaning & rectifying defect complete all as specified and directed by Engr-in-Charge. |
| 108 | Supply Fabricate, install, connect, testing and commissioning of outdoor type dust & Vermin proof LT electrical panel board, 1100 volts, 50 Hz AC supply, fully compartmentalized for cable chamber and bus bar chambers with adequate space made out of 3 mm thick CRCA sheet for load bearing like all over body, front and back cover with hinges and aldrops with DC locks CRCA powder coated and 2.0 mm thick MS Sheet for non load bearing and portions, complete with one coat of powder coating including suitable angle iron/ flat iron frame work/ supports bottom 50x50x6 mm MS channel as base and chamber for metering equipment complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated and connection wirings with FRLS copper conductor complete mounted on PCC pillars foundation, arrangements for bus bar trunking system, cable connection using new lugs including with danger notice complete all as specified and directed by Engr-in-Charge and comprising of the followings provisions:-Note: (i) Existing cables which removed from old panel board will be fixed with new lugs during fixing in new panel board (as if required) (ii) Getting of approval for Panel board drawing from Engr-in-Charge is necessary before fabrication. (iii) All switch gears should be fixed with 06 mm thick Fibre sheet Make: Any CPRI approved(a) LED/Neon indicator bulb in RYB Colour - 1 Set.(b) 4 Nos. Aluminium Bus bar 250 amps with chamber(c) Digital Multi function meter for showing Amps (upto 1250 Amps) and Voltage (up to 500 voltage) with suitable CT and PT(d) MCCB 4 Pole, 415 V, adjustable type, 125 A with breaking capacity 36 KA - 1 No.Out going:(e) MCCB 4 Pole, 415 V, adjustable type, 63 A with breaking capacity 25 KA - 04 Nos.(f) suitable cable gland for incoming and outgoing cable |
| 109 | M&L for servicing / overhauling and cleaning of geyser (Internally & externally) of any capacity including taking down from existing position and re-fixing of same complete all as specified and directed by Engr-in-Charge |
| 110 | Taking down disconnecting and dismantling of ceiling fans 1200/1400mm sweep including fan blades, down rod, coupling, decorative caps, condenser housing, stator and rotor for inspection and replacement of defective parts as required at site with and including repair, rewinding, greasing, re-assembling and testing to achieve satisfactory perfomance and re-fixing after repair complete all as specified and directed by Engineer-in-Charge |
| 111 | Supply and fixing of fan rod of size 1/1.5 feet suitable for mounting ceiling fan of size 1200/1400 mm complete all as specified and directed by Engr-in-Charge |
| 112 | Supply and fixing in repair/replacement two way sheet metal enclosure with three pin socket and plug top and 20 amp single pole MCB complete all as specified and directed . |
| 113 | Taking out of two wire from meter and bus bar / MCB SPN / SP with keeping in veiw safety and replaced with 2 run of 6 sqmm wire of meter with and including suitable size of cable lugs both end and re-connection with meter and bus bar / MCB SPN / SP complete all as specified and directed by Engr-in-Charge. |
| 114 | S & F in repair / replacement of old existing sunken / terminal box of size approx 10x10cm, concealed / surface mounted alongwith hylam sheet for fixing existing switches, sockets & regulators etc and making good the disturbed surfaces of walls complete all as specified and directed by Engr-in-Charge |
| 115 | All as pr item No.104 above but for size 15x7.5cm complete all as specified and directed. |
| 116 | All as pr item No.104 above but for size 20x15cm complete all as specified and directed. |
| 117 | All as pr item No.104 above but for size 20x25cm complete all as specified and directed. |
| 118 | S&F in replacement of PVC conduit, medium grade (MMS) including with fittings, ISI marked, 20 mm dia complete all as specified and directed. |
| 119 | S&F in replacement of PVC conduit, medium grade (MMS) including with fittings, ISI marked, 25 mm dia complete all as specified and directed. |
| 120 | S&F in replacement of PVC casing & capping medium grade with fittings, ISI marked, 20 mm size complete all as specified and directed. Please Enable Macros to View BoQ information |
| 121 | S&F in replacement of PVC casing & capping medium grade with fittings, ISI marked, 20 mm size complete all as specified and directed. Please Enable Macros to View BoQ information |