| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board including connection etc as required:- |
| 2 | Short Point :- |
| 3 | Medium Point :- |
| 4 | Long Point :- |
| 5 | Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2x1.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modular switch board, earthing the 3rd pin etc. as required:- |
| 6 | Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required:-. |
| 7 | Wiring for circuit /Sub-main with following sizes PVC insulated copper conductor cable (FR) in PVC casing and capping etc. as required. |
| 8 | 2 x 1.5 sq.mm:- |
| 9 | 2 x 2.5 sq.mm:- |
| 10 | 2 x 4 sq.mm:- |
| 11 | 4 x 16 sq.mm:- |
| 12 | 4 x 25 sq.mm:- |
| 13 | Wiring for Circuit/Sub-main wiring with the following sizes PVC insulated copper conductor cable (FR) in existing PVC casing capping/conduit in recess/surface including connection etc. as required. |
| 14 | 1 x 1.5 sq.mm:- |
| 15 | 1 x 2.5 sq.mm:- |
| 16 | 1 x 4 sq.mm:- |
| 17 | 1 x 10 sq.mm:- |
| 18 | 2 x 1.5 sq.mm:- |
| 19 | 2 x 2.5 sq.mm:- |
| 20 | 2 x 4 sq.mm:- |
| 21 | Supplying and fixing of the following Modular accessories including necessary connection etc. as required |
| 22 | 5 step fan regulator (2M) |
| 23 | Blank plate (1M):- |
| 24 | 20/25 amps single phase motor starter switch (2M):- |
| 25 | Earthing with Copper earth plate 600 mm x 600 mm x 3 mm thick i/c accessories and providing masonry enclosure with CI cover plate Size 12\\"x 12\\" having locking arrangement, along with 20 mm dia (medium gauge) watering pipe including CC work etc as required:- |
| 26 | Extra for using salt (12 kg) and charcoal (96kg) for plate earth electrode as required. |
| 27 | Proving and fixing / Drawing 4.06 mm dia (8 SWG) Copper wire on surface or in existing G.I / PVC / Polythene pipe for loop earthing as required. |
| 28 | Providing earthing system with maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminal size 32mmx 6mm including accessories with masonry enclosure of CI cover plate size 12\\"x 12\\" having locking arrangement including CC works etc as required:- |
| 29 | Supplying & fixing of 1200 mm sweep white color AC ceiling fan capacitor type double ball bearing complete with 300 mm down rod,canopies,shackles, 3nos blades, including wiring the down rod with 2x1.5 sqmm PVC insulated Copper conductor cable(FR) (ISI marked, BEE 1 star/minimum service value 4.0 m3/min/W). |
| 30 | Supplying and fixing of following surface/recess mounted LED luminaries in powder coated die cast housing complete with high efficiency polycarbonate diffuser and necessary connection etc. as required (with 50000 burning hours and minimum lumen output of 100 lm/watt):- |
| 31 | Surface mounted box type batten suitable for single 18/20 watt integrated LED tube lamp (without lamp). |
| 32 | Supplying and fixing of following LED Tubes, retrofit bulbs/lamps for LED luminaries including necessary connection etc. as required:- |
| 33 | 18/20 watt LED tube with integral driver and polycarbonate diffuser (50000 burning hours and minimum lumen output of 100lm/watt):- |
| 34 | 9 watt LED retrofit lamp with polycarbonate body and aluminium heatsink :- |
| 35 | Supplying and fixing of the following ratings switch disconnector fuse unit(main switch) made of sheet steel enclosure with all accessories including drilling holes on the board/MS clamp and necessary connection etc. as required |
| 36 | 100 amps 415 volts TPN main switch (rewireable):- |
| 37 | Supplying and installation of Bus bar chamber of the following ratings and sizes made of steel sheet enclosure with all accessories including necessary connection etc. as required:- |
| 38 | 100 amps 415 volts four strip Copper busbar chamber 4 ways of size (455mmx330mmx120mm):- |
| 39 | Supplying and installation of fuse unit kitkat/HRC/HBC of the following ratings in existing main switch/panel board including necessary connection etc as required:- |
| 40 | 100 amps rewireable(kitkat) porcelain fuse unit with base. |
| 41 | Supplying and fixing of powder coated sheet steel enclosure on surface/recess, suitable for 240/415 volts MCB/ Isolator/ RCCB (SP/ SPN/ DP/ TP/ TPN/FP) complete with necessary bus bar, neutral link,din rail ,earth bar, etc. i/c connection as required . |
| 42 | 4 way SPN MCB DB (double door):- |
| 43 | (2+10) / 12 way SPN MCB DB (double door):- |
| 44 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connection as required: |
| 45 | 6 to 32 amps SP MCB:- |
| 46 | Supplying & installation of isolators of following ratings in the existing MCB DB including connection etc as required:- |
| 47 | 40 amps DP isolator:- |
| 48 | Supplying & installation of RCCB (sensitivity 30mA to 300mA) of following ratings in the existing MCB DB including connection etc as required:- |
| 49 | 100 amps FP RCCB:- |
| 50 | Supplying and fixing of MS frame made of (25mm x 25mm x 5mm) MS angle with necessary support by (40mm x 6mm) MS flat and 12 mm thick marine plywood on top, grouted on wall with 4 nos legs (25mmx25mmx5mm MS angle 20 cm long) finished with red oxide and 2 coat synthetic enamel paint including necessary cc work, mending the damages & painting etc as required:- Please Enable Macros to View BoQ information |