| 1 | RAW WATER PUMPING PLANT:- |
| 2 | Cost towards all labour, tools, tackles and technician for taking out old and damaged VT pump set from Intake well along with column pipe with all accessories, demolition of mounting channel for installation of new VT pump set. |
| 3 | Supplying, Installation, Testing & Commissioning of Vertical Turbine pump set at raw water pumping plant urawan, capable of discharge 90.92m3/hr against a total head of 40 meters Make- Kirloskar/Mather and Platt/ Jyoti / WPIL coupled with suitable SPDP vertical hollow shaft V.T squirrel cage induction motor 3 ph, 415 V ± 10% , 1450-1500 RPM, Make- Kirloskar/ Jyoti / C.G /ABB with suitable discharge head, base plate and accessories such as suitable M.S column pipe flanged type 60 ft. (10 ft. long – 06 nos.) spider bearing, line shaft, cut less bush, foot valve with strainer, pressure gauge, double flanged C.I Sluice valve and C.I N.R valve rating PN 1.6 etc. all complete job. Testing of pump set on full load at site. |
| 4 | Cost towards supply and fitting 25 H.P fully automatic air break star delta starter , Make- L&T /Havell’s/ Siemens / Schneider/ BCH |
| 5 | Cost towards replacement of damaged panel by new supplying installation and commissioning of free standing type floor mounting industrial panel board compressing 150 Amp. Copper bus bar 4 nos. in M.S steel (14 SWG) housing and consisting of 150 amp. TPN DTH MCCB- 01 no. incoming feeder and 100 amp T.P.N DTH MCCB-02 no. outgoing feeder, 0 to 500 V voltmeter - 01. nos., 0 to 200 Amp. ammeter- 02 nos. with selector switch, indicating lamp 03 Nos., single phase preventer,32 amp. MCB -01 no and 63 amp. Switch fuse 01 no for internal & external lighting load and internal connection with copper wire etc. |
| 6 | Supplying and laying of 50 mm sq. 1.1 K.V grade, 3.5 core P.V.C insulated and sheathed unarmored Aluminum cable in air /wall from Transformer to stabilizer to panel board as required with lugs socketing, making connection all complete. make – Polycab / Havell’s /KEI, ISI marked, |
| 7 | Cost of supply & laying, commissioning of 3 core 25 mm² copper conductor cable 1.1 KV grade PVC insulated and PVC sheathed unarmored cable from panel to starter and starter to motor with lugs socketing. Make- Polycab / Havell’s /KEI, ISI marked.. |
| 8 | Cost towards making earthing connection from earth pit to change over, stabilizer, panel, starter, motor with 6 SWG G.I wire. |
| 9 | Supply and fitting 300 amp TPN switch fuse unit-01 no. before stabilizer on the wall, including required materials such as clamp, nut, bolts, etc, for the job. make – L&T/ Havell’s /C&S any Reputed make ISI Marked. |
| 10 | Providing and fixing 300 Amp. TPN on/off load change over switch with side handle operation, in sheet enclosure with allied materials. In replace of burnt and damaged change over switch for stabilizer. Make- Havells/ BCH/ C&S or ISI marked. |
| 11 | Supply, fitting & commissioning of lighting arrangement at pump hose and outside of pump house such as tube light 40 W complete set 2 no and 70 W LED lamp complete set 3 nos. and making wiring, light point, fan point etc. as required. |
| 12 | CLEAR WATER PUMPING PLANT:- |
| 13 | Cost towards dismantling of old 50 HP C/F pump motor from base plate by gas cutter, cost for breaking of old existing foundation and removing of all garbage from pump house with all labour tools, tackles and technician cost. |
| 14 | Supplying, installation and commissioning of HSC Centrifugal pump set (make: Kirloskar / WPIL/ Mather & Platt) as per IS:5120, capable for discharging 57 M3/Hrs against a head of 80 m , consisting of stainless steel impellers, stainless steel pump shaft, etc. with all accessories coupled with energy efficient (IE3) TEFC squirrel cage induction motor having 15% more BHP than that of pump, operating on 1450-1500 rpm, 415V, 3 PH, 50 HZ [make: Kirloskar /ABB/CGL/Marathon] all complete with 4”dia ms suction pipe-30’ long,3” dia ms delivery pipe-15’ long,Ms flange-10 nos,required size of sluice valve and non- return valve standard fitting, strainers, reducer, foot valve, pressure gauge, , common header, nuts & bolts, packings, fitting & fixing, labour & technician etc. including transportation, loading & unloading charge etc. all complete job as per site requirement and direction of E/I. |
| 15 | Cost towards replacement of damaged panel by new supplying installation and commissioning of free standing type floor mounting industrial panel board compressing 200 Amp. Copper bus bar 4 nos. in M.S steel (14 SWG) housing and consisting of 200 amp. TPN DTH MCCB- 01 no. incoming feeder and 100 amp T.P.N DTH MCCB-02 no. outgoing feeder, 0 to 500 V voltmeter - 01. nos., 0 to 250 Amp. ammeter- 02 nos. with selector switch, indicating lamp 03 Nos., single phase preventer,32 amp. MCB -01 no and 63 amp. Switch fuse 01 no for internal & external lighting load and internal connection with copper wire etc. |
| 16 | Supplying & laying 195 mm2 x 3.5 core PVC insulated, armoured 1.1 KV grade Aluminium cable (make:polycab/havells/other ISI reputed brand) from Transformer to Control Panel. |
| 17 | Cost for Supplying and laying of 3Core 35 Sq. mm, Copper Cable unarmoured, P.V.C insulated and P.V.C. Sheathed 1100 V grade from motor to starter. Make- Finolex/ Havells/ Polycab/ Mescab/ Any reputed ISI marked |
| 18 | Supply and fitting 400 amp TPN switch fuse unit-01 no. before stabilizer on the wall, including required materials such as clamp, nut, bolts, etc, for the job. make – L&T/ Havell’s /C&S any Reputed make ISI Marked. |
| 19 | Providing and fixing 400 Amp. TPN on/off load change over switch with side handle operation, in sheet enclosure with allied materials. In replace of burnt and damaged change over switch for stabilizer. Make- Havells/ BCH/ C&S or ISI marked. |
| 20 | Cost towards making earthing connection from earth pit to change over, stabilizer, panel, starter, motor with 8 SWG G.I wire. |
| 21 | Supply, fitting & commissioning of lighting arrangement at pump hose and outside of pump house such as tube light 40 W complete set 4 no and 70 W LED lamp complete set 3 nos. and making wiring, light point, fan point etc. as required. Please Enable Macros to View BoQ information |