| 1 | 1.0) LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt)Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (i) 120 Watt |
| 2 | (ii) 150 Watt |
| 3 | 2.0) Supplying and drawing following sizes of FRLS PVC insulated copper conductor Single core cable in the existing surface/recessed steel/PVC conduit/ Pole as required.a) 3 x 1.5 Sq.mm |
| 4 | 3.0) Providing and applying two coating of dielectric paint of existing street light poles including cleaning, surface preparation etc. As complete required. |
| 5 | 4.0) Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A |
| 6 | 5.0) Supplying, installation, testing and commissioning of floor mounted feeder panel duly compartmentalized (outdoor type) double door cubicle panel board of Suitable size made out of 2mm thick CRCA MS sheet having hinged gasketed cover and screw type knob with double locking arrangement and rain protection cover mounted on MS angle iron base frame made out of 40 mm X 40 mm X 5 mm angle iron with 1 mtr. Long leg grouted with 1:3:6 foundation and should be as per drawing approved by Engineer-In-Charge. Legs should be covered with brick wall, connection, interconnection with painting after applying a coat of primer, i/c connection inter connection of the accessories mounted there on with suitable size of copper wire with thimble/lugs, earthing the body of the feeder panel i/c supplying & fixing of the following items : INCOMER a) 63A 4 pole 25 kA MCCB - 1 Nob) Ammeter with selector switch (0-25 A) - 1 Noc) Voltmeter with selector switch (0-500 V) - 1 No d) Indication Lamp (RYB) with control HRC fuse with fuse fitting- 1 set. BUS BAR 50 A TPN Al. Bus Bar (suitable size) - 1 SetOUTGOING a) 16 A TP&N 10 kA MCB - 4 Nos.b) Power contactor - 1 No.c) Astronomical Timer switch – 1 No.d) Auto/Manual toggle switch – 1 No. e) Compartment having space for DISCOM energy meter with 6mm thick Bakelite sheet for mounting energy meter.f) Danger Notice plate – 1 No.g) Lightning inside the feeder pillarNote: Foundation dully plastered and finished shall be made as per site requirement for which nothing extra shall be paid. |
| 7 | 6.0) Supplying fabrication and installation of wire mesh protection cover guard for main feeder pillar made out of 8 SWG wire mesh of suitable size with MS angle iron base frame 40 mm X 40 mm X 5 mm and 0.5 Mtr. long leg spot and MS strip with support size 40 mm X 6 mm as per drawing approved by Engineer-in-Charge i/c providing door of suitable size with S/F of godown lock, locking arrangement, painting and grouting of angle iron frame in CC 1:2:4 etc. complete as required. |
| 8 | 7.0) Earthing with G.I. Earth Pipe 4.5 mtr long, 40 mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 9 | 8.0) Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for conneciton etc. as required. |
| 10 | 9.0) Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia GI pipe from earth electrode including connection with GI nut bolt , spring washer, excavation, refilling etc. as required. |
| 11 | 10.0) Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing alongwith existing surface /recessed conduit submain wiring /cable as required. Please Enable Macros to View BoQ information |