| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket, bell or power) complete including all electrical fittings & fixtures(DBs, submain,cables etc) and making good disturbed surfaces of wall , floor etc and matching wth original colour of wall, complete all as specified and directed. |
| 2 | M&L for one light/fan/exhaust fan point wiring controlled by one switch with PVC insulated unsheathed multi stranded copper conductor (FRLS) of size 1.5 Sqmm (for Phase colour code Red and for Neutral colour code Black) and one run of size 1.5 Sqmm PVC insulated unsheathed multi stranded copper conductor (FRLS) (as earth wire, colour code green) and connected to common earth dolly all as specified. , drawn through in and in existing concealed / surface PVC Conduit/ saddle medium grade, ISI marked 20 mm dia along with conduit fixing accessories and with pressed steel terminal box thickness 1.6 mm painted with one coat of black bituminous paint as a primary and two coats of enamel paint with 3 mm thick laminated sheet for provision of switches/regulators complete all as specified and directed.Note : After rewiring cutting chasing portion should be matched with existing finishes of walls. |
| 3 | All as per item No 02 above but 5 Amp socket outlet, independent. |
| 4 | All as per item No 02 above but on the same board . |
| 5 | All as per item No 02 above but for one bell/Buzzer point controlled by one push button on the same board with other switches or independent with 1.50 sqmm size cable. |
| 6 | All as per item No 02 above but 2.5 sq mm wire for one 15 Amps socket outlet independent with continuous PVC insulated single core green colour copper earth wire of size 2.5 sq mm connected to common earth dolly. |
| 7 | M&L for one light/fan/exhaust fan point wiring controlled by one switch with PVC insulated unsheathed multi stranded copper conductor (FRLS) of size 1.5 Sqmm (for Phase colour code Red and for Neutral colour code Black) and one run of size 1.5 Sqmm PVC insulated unsheathed multi stranded copper conductor (FRLS) (as earth wire, colour code green) and connected to common earth dolly all as specified. , drawn through PVC casing caping of ISI marked with fixing accessories and with pressed steel terminal box thickness 1.6 mm painted with one coat of black bituminous paint as a primary and two coats of enamel paint with 3 mm thick laminated sheet for provision of switches/regulators complete all as specified and directed by Engineer-in-Charge. Note : After rewiring cutting chasing portion should be matched with existing finishes of walls. |
| 8 | All as per item No 07 above but 5 Amp socket outlet, independent . |
| 9 | All as per item No 07 above but on the same board. |
| 10 | All as per item No 07 above but 2.5 sq mm wire for one 15 Amps socket outlet independent with continuous PVC insulated single core green colour copper earth wire of size 2.5 sq mm connected to common earth dolly complete all as specified and directed. |
| 11 | Supply & fixing in replacement of switch piano type 5 amp SP one way ISI Marked complete all as specified and directed. |
| 12 | Supply & fixing in replacement of switch 15 Amps SP one way ISI Marked complete all as specified and directed. |
| 13 | Supply & fixing in replacement of socket outlet 3 pin 5 Amps flush type complete all as specified and directed. |
| 14 | Supply & fixing in replacement of socket outlet 2-in-1, 3 pin 5 amps and 15 amps flush type complete all as specified and directed. |
| 15 | Supply & fixing in replacement of stepped type electronic fan regulator flush type on the existing phenolic sheet etc complete all as specified and directed. |
| 16 | S&F in replacement for modular switches 6 amps single pole one way complete all as specified and directed. |
| 17 | S&F in replacement for modular sockets out let 6 amps 6 pin 2 module with shutter complete all as specified and directed. |
| 18 | S&F in replacement for modular switches 16 Amps single pole one way complete all as specified and directed. |
| 19 | S&Fin replacement modular socket out let 6-16 Amps 3 pin combined shuttered complete all as specified and directed. |
| 20 | Supply & fixing in replacement of stepped type electronic fan regulator modular complete all as specified and directed. |
| 21 | S&F in repair ceiling rose complete all as specified and directed. |
| 22 | Supply & fixing in replacement of ding dong bell electric 230 volt AC complete all as specified and directed. |
| 23 | S&F bell push, in repairs, flush type 5 Amps complete all as specified and directed. |
| 24 | S&F single pole blanking plate in the existing cover plate complete all as specified and directed. |
| 25 | Supply and fix modular white cover plate with frame 3 module ISI marked complete all as specified and as directed. |
| 26 | Supply and fix modular white cover plate with frame 4 module ISI marked complete all as specified and as directed. |
| 27 | Supply and fix modular white cover plate with frame 6 module ISI marked complete all as specified and as directed. |
| 28 | Supply and fix modular white cover plate with frame 8 module ISI marked complete all as specified and as directed. |
| 29 | Supply and fix modular metal flush box 3 module ISI marked complete all as specified and as directed. |
| 30 | Supply and fix modular metal flush box 4 module ISI marked complete all as specified and as directed. |
| 31 | Supply and fix modular metal flush box 6 module ISI marked complete all as specified and as directed. |
| 32 | Supply and fix modular metal flush box 8 module ISI marked complete all as specified and as directed. |
| 33 | Supply and fix flushed inside the wall MS sunken box more than 1mm thicknes of size 4\\"x4\\" complete all as specified and as directed. |
| 34 | Supply and fix flushed inside the wall MS sunken box more than 1mm thicknes of size 7\\"x4\\" complete all as specified and as directed. |
| 35 | Supply and fix flushed inside the wall MS sunken box more than 1mm thicknes of size 8\\"x10\\" complete all as specified and as directed. |
| 36 | Supply & fixing in replacement of SPN enclosure with two pin and earth plug and socket complete with on SP MCB 20 Amps complete all as specified and directed. |
| 37 | M&L PVC insulated FRLS single core with strandard copper cable of size 6 Sqmm in two run and 6 Sqmm one run for earth and drawing through existing concealed conduit including taking down old UNSV cable acomplete all as specified and directed.Note :- 2 runs of 6 Sqmm cable and one run of 6 sqmm cable will be measured as one running meter for the purpose of measurement and payment. |
| 38 | All as per item No 37 above but copper cable single core of size 4 Sqmm in two run with earth wire 4 Sqmm single run for continuity.NOTE :- 2 runs of 4 Sqmm cable and one run of 4 sqmm cable will be measured as one running meter for the purpose of measurement and payment. |
| 39 | All as per item No 37 above here-in-before but copper cable single core of size 2.5 Sqmm in two run with earth wire 2.5 Sqmm single run for continuity .NOTE :- 2 runs of 2.5 Sqmm cable and one run of 2.5 sqmm cable will be measured as one running meter for the purpose of measurement and payment. |
| 40 | M&L PVC insulated FRLS single core with strandard copper cable of size 2.5 Sqmm in two run and 2.5 Sqmm one run for earth and drawing through ISI marked casing caping including taking down old UNSV cable acomplete all as specified and directed.NOTE :- 2 runs of 2.5 Sqmm cable and one run of 6 sqmm cable will be measured as one running meter for the purpose of measurement and payment. |
| 41 | Supply and fix in replacement post top lantern LED 40 W or next highest wattage having IP65 protction for single phase connection 50 Hz 230 Volts complete all as specified and directed. |
| 42 | Supply and fix in replacement LED bollard fitting 9 Watt with luminaire with MS Pipe housing with glare free PMMA diffuser , IP65 of height 800 mm suitable for single phase connection 50 Hz 230 Volts complete all as specified and directed. |
| 43 | M&L for Recess mounted 15 Watt high efficancy recess LED slim round downlighter IP20 with high brightness LED for glare free homogenous illumination celing light complete with electronic driver complete all as specified and directed. |
| 44 | S&F in replacement wall mounting box type LED tube light fitting , extruded aluminium heat sink provided for efficient heat dissipation & Integrated electronic driver 1x20 watt comprising of strong jointless CRCA body complete with all accessories and all as specified and directed by Engineer-in-Charge |
| 45 | M&L for Recess mounted 36/ 40 Watt high efficancy 2x2 recess LED flat panel with high brightness LED for glare free homogenous illumination celing light complete with electronic driver complete all as specified and directed. |
| 46 | Supply and Fixing LED street light fitting 60 Watt pressure die case aluminium housing LED street light luminaires suitable for existing street light pole including all fixing accessaries complete all as specified and directed. |
| 47 | Supply and fixing in replacement of old unsv GI bracket made out of 32 mm bore,light grade 1.2 m long bent to shape suitable for street light fitting including MS flat clamp 50 x 6 mm 2 Nos for each bracket with nut & bolt complete all as specified and directed by Engineer-in-Charge. |
| 48 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape with galvanised steel wire or tape and overall PVC sheathed 2 core 6 sq. mm nominal cross section in service connections complete all as specified and directed. |
| 49 | S&F sheet metal enclosures DB Double door Verticle distribution type, 04 way, TPN DB , IP43, 415V & suitable for 4 POLE MCCB as incomming including shruded neutral bar & Pan assy with earthing terminal as provided by manufacturer complete all as specified and directed.Note : - MCCB shall be measured and paid separately |
| 50 | S&F sheet metal enclosures DB Double door Verticle distribution type, 08 way, TPN DB , IP43, 415V & suitable for 4 POLE MCCB as incomming including shruded neutral bar & Pan assy with earthing terminal as provided by manufacturer complete all as specified and directed.Note : - MCCB shall be measured and paid separately |
| 51 | S&Fix in replacement MCB DB TPN 4 Way factory made IP 42 protection class metal double door with 200 Amp rating bus bar 240 for fixing of MCBs/Isolators/RCCBs etc complete all as specified and directed. |
| 52 | S&Fix in replacement MCB DB SPN 4 Way factory made IP 42 protection class metal double door with 200 Amp rating bus bar 240 for fixing of MCBs/Isolators/RCCBs etc complete all as specified and directed. |
| 53 | S&Fix in replacement MCB DB SPN 6 Way factory made IP 42 protection class metal double door with 200 Amp rating bus bar 240 for fixing of MCBs/Isolators/RCCBs etc complete all as specified and directed. |
| 54 | S&Fix in replacement MCB DB SPN 8 Way factory made IP 42 protection class metal double door with 200 Amp rating bus bar 240 for fixing of MCBs/Isolators/RCCBs etc complete all as specified and directed. |
| 55 | S&Fix in replacement MCB DB SPN 12 Way factory made IP 42 protection class metal double door with 200 Amp rating bus bar 240 for fixing of MCBs/Isolators/RCCBs etc complete all as specified and directed. |
| 56 | Supply & fixing in replacement of MCB TPN 63Amps 16KA complete all as specified and directed. |
| 57 | S&F in replacement of MCCB TPN 125 Amps 415 Volts 16 KA as per suitable sample of size complete all as specified and directed. |
| 58 | S&F in replacement of MCCB TPN 100 Amps 415 Volts 16 KA as per suitable sample of size complete all as specified and directed. |
| 59 | S&F in repairs MCB SP 6 to 32 Amps 240 Volts.\\"B\\" grade complete all as specified and directed. |
| 60 | S&F in repairs MCB,SP 40 Amps, 240 Volts.\\"B\\" grade complete all as specified and directed. |
| 61 | S&F in repairs MCB SPN, 40 Amps, 240Volts .\\"B\\" grade complete all as specified and directed. |
| 62 | S&F in repairs MCB SPN, 63 Amps, 240Volts.\\"B\\" grade complete all as specified and directed. |
| 63 | S&F in repairs MCB TPN, 63 to 100 Amps,415Volts .\\"B\\" grade complete all as specified and directed. |
| 64 | Supplying and fixing PVC conduit 25 MM dia along with accessories in surface/recess I/C or cutting the wall and making good the same in case of recessed conduit as required complete all as specified and directed. |
| 65 | S&F in replacement of Casing capping double lock type supper quality size 15 mm width ISI marked with fixing accessories complete all as specified and directed. |
| 66 | Supply and fix modular type gang box(3 module for one socket and one switche) suitable for 5/15amp 6pin including plate cover plastic sunken box etc including suitable size of switches and sockets complete all as specified and directed. |
| 67 | Taking down ceiling fan complete any type size from existing location and cleaning body blades etc including servicing, greasing,oiling,replacing wornout bearing ,bush and refixing the same at site complete all as specified and directed. |
| 68 | All as per item No 67 above but for Exhaust fan complete. |
| 69 | Rewinding unserviceable ceiling fan 1200/1400 mm Sweep from site by strip opening,cutting removing the burnt winding from starter cleaning the slots and rewind the same with original guage of super enameled copper winding wire, insulation materials and all accessories & varnishing etc replacement of service wire copper twisted size 23/0.0076 including reassembling the fan complete all as specified and directed. |
| 70 | All as per item No 69 above but for Exhaust fan 300 mm sweep complete |
| 71 | M&L Painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc complete all as specified and directed. |
| 72 | Material and Labour for Replacement of old unserviceable fan blades, (ISI Marked), suitable for 1200mm sweep ceiling fan duly painted in white/brown by using spray gun method(fully furnished) complete all as specified and directed. |
| 73 | Material and Labour for Repalcement of old unserviceable down rod of ceiling fan of dia 20mm bore \\"medium grade\\" complete with split pin, hanging clamp and rubber real (length of rod not less than 45cm and not more than 60cm) dully painted in white/brown by using spray gun method (fully furnished) complete all as specified and directed. |
| 74 | Supply and Fix cable PVC insulated and overall sheathed with flexible copper conductor cable of size 0.5 sqmm,3 core cut to size of approx 0.30 metre from block of fan to ceiling rose complete all as specified and directed. |
| 75 | Material and Labour for Replacement of old unserviceable gun metal bush of ceiling fan including neceassry laith, Grinding and welding work complete all as specified and directed. |
| 76 | Material and Labour for Replacement of old unserviceable shackle assembly kit (Rubber real -01, MS split clamp two Nos, nuts and bolts washers- 2 Nos & split pin -02 Nos) suitable for ceiling fan of 1200/1400mm sweep complete all as specified and directed. |
| 77 | Material and Labour for Replacement of old unserviceable steel screw of size 5mm to 8mm (to be used for fixing of fan blade) complete all as specified and directed. |
| 78 | S&F BLDC ceiling fans complete with blades, down rods, and accessories 230V, 1200/1400mm sweep motor complete all as specified and directed. |
| 79 | Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers complete all as specified and directed. |
| 80 | Supply and fix exhaust fan sweep 250 mm in replacement made up of sturdy engineering metal body complete with louvers shutter , voltage 230 V , 50 Hz , 1200 RPM copper wound complete all as specified and directed. |
| 81 | Supply and fix Ventilation fan PVC (250 mm Sweep) with louvers and acessories complete all as specified and directed. |
| 82 | Supply and fix Ventilation fan PVC (200 mm Sweep) with louvers and acessories complete all as specified and directed. |
| 83 | Material and Labour for Replacement of old unserviceable capacitor AC 400/415 volts 2.5 mfd (ISI marked) complete all as specified and directed. |
| 84 | Material and Labour for Replacement of old unserviceable capacitor AC 400/415 volts 3.15 mfd (ISI marked) complete all as specified and directed. |
| 85 | Material and Labour for servicing of split type AC's of capacity 1.5/2 TR comprising of the following tasks installed at different locations including testing complete all as specified and directed by Engineer-in-Charge. (a) Inspecting and checking the Indoor/outdoor units for noise free operation.(b) Checking the electrical connection for tightness(c) Cleaning the condenser with cleaning agent followed with pressurized water and cleaning the cooling coil with air blower with water pressure gun.(d) Greasing/Oiling of condenser fan motor and blower motor.(e) Checking for any refrigerant leakage by pressure testing and repair it.(f) Checking for serviceability of remote control unit and replace with new battery. |
| 86 | Material and Labour for servicing of window type AC's of capacity 1.5 TR comprising of the following tasks at different locations including Refixing, commissioning and testing complete all as specified and directed by Engineer-in-Charge.(a) Inspecting, taking down, brushing cleaning with water pressure gun including acid/detergent wash of condenser and cooling coil.(b) Carry out operation of blower and compressor and ensure that satisfactory functioning of all parts.(c) Inspecting the leakage in the system by pressure test and repair it.(d) Checking of the earth continuity of electrical parts.(e) Checking the functioning of thermostat.(f) Inspection of all electrical parts.(g) Testing the machine for satisfactory operation. |
| 87 | Material and Labour for repair to leaking area of split type AC unit of capacity 1.5/2 TR capacity including nitrozen pressure testing, dehydration and any type of gas charging complete all as specified and directed. |
| 88 | Material and Labour for repair to leaking area of window type AC unit of capacity 1.5 capacity including pressure testing, dehydration and any type of gas charging complete all as specified and directed. |
| 89 | Supply and charging Refrigerant(R410,R32,R134 and existing refrigerent) to any type of AC unit including CFC free and non CFC Free AC complete all as specified and directed. |
| 90 | Supply and fixing in replacement of starting relay 25 Amps for split type AC units of capacity 2 /1.5TR as required at site complete all as specified and directed. |
| 91 | Supply and fixing in replacement of start run capacitor 45/60 MFD for split type A/C's of capacity 1.5/2 TR complete all as specified and directed by Engineer-in-Charge. |
| 92 | Supply & fixing in replacement of running capacitor for 36/60 mfd for AC window type 1.5 TR as required at site complete all as specified and directed. |
| 93 | Supply & fixing in replacement of running capacitor 6 mfd for blower motor as required at site complete all as specified and directed. |
| 94 | Taking out and replacement of condenser fan motor DC of split type AC 1.5/2 ton units of capacity 1.5/ 2 TR complete all as specified and directed. |
| 95 | Taking out and replacement of condenser fan motor AC of split type AC units of capacity 1.5/ 2 TR complete all as specified and directed. |
| 96 | Material & Labour for Fixing the new blower motor DC in replacement of for split type A/C unit as per existing model complete all as specified and directed. |
| 97 | Supply & Fixing the new blower motor AC for split type A/C unit as per existing model complete all as specified and directed. |
| 98 | Supply and fixing in replacement of new blower motor for window ac as required at site single phase 230 volts double shaft with clamp bolts, nuts and rubber bushes including testing & commissioning complete all as specified and directed. |
| 99 | S&F in replacement the new swing motor as per existing model/make for split type AC 1.5/2TR unit complete all as specified and directed. |
| 100 | Supply and fix out door fan blade in existing model complete all as specified and directed. |
| 101 | Material and Labour for replacement of defective electronic components / IC Circuits of PCB card with display unit suitable of 1.5/2 ton split AC indoor unit as required on site complete all as specified and directed by Engr-in-Charge including replacement of defective electronic components / IC Circuits complete all as specified and directed. |
| 102 | Material and Labour for replacement PCB card suitable of 1.5/2 ton inverter split AC as required on site complete all as specified and directed by Engr-in-Charge including sensor complete all as specified and as directed. |
| 103 | Material and Labour for replacement PCB card suitable of 1.5/2 ton window as required on site complete all as specified and directed by Engr-in-Charge including sensor complete all as specified and as directed. |
| 104 | Disconnecting and taking down burnt condenser coil of capacity 1.5TR from split type AC unit and Supply and Fix new copper condesor coil as per existing model complete including testing complete all as specified and directed. |
| 105 | Materal and Labour for replacement of cooling coil assembly complete suitable for 1.5 / 2 ton indoor unit Split type AC incl testing for satisfactory working condition complete all as specified and directed. |
| 106 | Materal and Labour for replacement cooling coil of window type AC 1.5 TR including after taking out old unserviceable one,soldering/welding dehydration complete achieve complete all as specified and directed. |
| 107 | Disconnecting & taking down of window type AC of any make for replacement of condenser coil of existing size including soldering/welding and resting commissioning complete all as specified and directed. |
| 108 | Disconnecting and taking down burnt compressor of capacity 1.5TR from split type AC unit and Supply and fix new one as per existing model complete including testing complete all as specified and directed. |
| 109 | Disconnecting and taking down burnt compressor of capacity 2TR from split type AC unit and Supply and fix new one as per existing model complete including testing complete all as specified and directed. |
| 110 | Material and labour for replacement of 'R' type compressor for Window type AC,1.5 TR as per existing make including taking out old unserviceable one,flushing, dehydration and gas changing complete all as specified and directed. |
| 111 | Labour for dismantling of Split AC 1.5/2 ton complete unit from the existing place complete all as specified and directed. |
| 112 | Labour for fixing of Split AC 1.5/2 ton including masonary work complete unit complete all as specified and directed. |
| 113 | Labour for dismantling of window AC 1.5 ton from the existing place complete all as specified and directed. |
| 114 | Labour for fixing of window AC 1.5 ton complete all as directed. |
| 115 | Material and labour install wall mounted stand for mounting indoor unit of split AC complete with all fixing arrangement complete all as specified and directed. |
| 116 | Material and labour wall mounted stand for mounting outdoor unit of split AC complete with all fixing arrangement complete all as specified and directed. |
| 117 | M&L in repairs copper tubing 3/8” outer dia suitable for AC 2TR capacity complete all as specified and directed. |
| 118 | All as per item No 34 but here in before but 5/8” outer dia. complete all as specified and directed. |
| 119 | Material and Labour for providing insulation 9mm thick for dia 1/4\\",3/8\\",1/2\\",5/8\\",6/8\\" copper tubing’s from Indoor to outdoor units with foam insulation followed with clamps complete all as specified and directed. |
| 120 | Material and labour for the new remote with battery as per existing model for 1.5/2 TR split type A/C unit complete all as specified and directed. |
| 121 | Material and labour in replacement of wall mounted Voltage stabilizers 4/5 KVA single phase,230 Volts AC,voltage variation between 140- 300,intelligent time delay system,digital display,low and high voltage cut-off system, complete all as specified and directed. |
| 122 | M & L for Taking out unserviceable indoor unit and supply and fix the new indoor unit of 1.5/2 TR capacity split AC 230 Volts single phase including installing ,charging complete all as specified and directed. |
| 123 | Material and labour in replacement 3 core copper PVC insulated of size 4 Sqmm complete all as specified and directed. |
| 124 | M & L for Taking out unserviceable outdoor unit and supply and fix the new OUTDOOR unit of 1.5/2 TR capacity split AC 230 Volts single phase including installing ,charging complete all as specified and directed. |
| 125 | Repair & maintenance of Refrigerator / Water Cooler /deep freezer any capacity comprising of the following tasks at different locationcomplete all as specified and directed.(a) Inspecting, taking down, brushing cleaning with blower including acid/detergent wash of condenser and cooling coil.(b) Carry out operation of blower and compressor and ensure that satisfactory functioning of all parts.(c) Inspecting the leakage in the system.(d) Checking of the earth continuity of electrical parts.(e) Checking the functioning of thermostat.(f) Inspection of all electrical parts.(g) Testing the machine for satisfactory operation.(h) Check and correct all electrical wiring & test its functioning(j) Testing of Refrigerator after repair. |
| 126 | M & L for replacement of unserviceable sealed compressor with new hermetic sealed compressor of existing make including charging of refrigerant gas and testing on full load complete all as specified and directed. |
| 127 | M & L for replacement of unserviceable compressor with new compressor of existing make including charging of refrigerant gas and testing on full load complete all as specified and directed. |
| 128 | Taking down desert cooler of any size by disconnecting electrical supply, cleaning, oiling of all moving part of pump & exhaust fan/kit, Replacing PVC pipes, nozzles, distributors, pads, checking electrical connections complete all as specified and directed. |
| 129 | Material and labour in replacement of wood pads(set of three)as per sample complete all as specified and directed. |
| 130 | Material and labour in replacement the new desert cooler pump.including testing for proper functioning complete all as specified and directed. |
| 131 | Material and labour in replacement the new exhaust fan kit with leg assembly 450mm sweep complete all as specified and directed. |
| 132 | Material and labour in replacement the new exhaust fan motor with leg assembly 450mm sweep complete all as specified and directed. |
| 133 | Material and labour in replacement the new exhaust fan blade 450mm sweep, Make Khaitan/Elpar all as specified and directed by Engineer-in-charge. |
| 134 | Material and labour in replacement new body of desert cooler of 600 x 600 x 900 mm size or in next higher size in volume duly painted of 20 SWG sheet with 22 SWG flops, front grill, PVC pipe, nozzle,selector switches,swinging motor,distributor and nut bolts washers for fixing fan clamps, complete all as specified and directed. |
| 135 | Material and labour front grill of desert cooler as per sample complete all as specified and directed. |
| 136 | Material and labour for PVC flexible distributor heavy duty with nozzle as per sample complete all as specified and directed. |
| 137 | Material and labour in replacement of 3 pin socket metalic plug top industrial type complete all as specified and directed. |
| 138 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground earth pit not less than 2.25 M deep below ground level with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of 25x4 mm by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to and including earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus earth, GI pipe for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C1 chamber with chamber cover in RCC 1:2:4 type B1 complete all as specified and directed. |
| 139 | M & L in repairs earthing complete with galvanised steel earth plate electode 600 x 600 x 6.0 mm thick burried directly in ground earth pit not less than 2.25 mtr deep below ground level connected to & including galvanised steel wire 4.0 mm dia size means of nuts and bolt check nuts and washers of galvanised rion sheet all as shown in electrical plate Nos 5 of SSR Part - I and connected to earthing test point complete including testing filling of adquate quantity of charcoal dust and common salt including refilling earth and removal of surplus soil upto 50 mtrs PCC 1:3:6 type CI chamber precast RCC cover 40 mm thick reinforced with 6 mm dia MS bar 3 Nos both way with handle made out of 6 mm dia MS bar water pipe with wire mesh and connecting testing etc complete all as specified and directed. Please Enable Macros to View BoQ information |
| 140 | M & L in repairs earthing complete with galvanised steel earth plate electode 600 x 600 x 6.0 mm thick burried directly in ground earth pit not less than 2.25 mtr deep below ground level connected to & including galvanised steel wire 4.0 mm dia size means of nuts and bolt check nuts and washers of galvanised rion sheet all as shown in electrical plate Nos 5 of SSR Part - I and connected to earthing test point complete including testing filling of adquate quantity of charcoal dust and common salt including refilling earth and removal of surplus soil upto 50 mtrs PCC 1:3:6 type CI chamber precast RCC cover 40 mm thick reinforced with 6 mm dia MS bar 3 Nos both way with handle made out of 6 mm dia MS bar water pipe with wire mesh and connecting testing etc complete all as specified and directed. Please Enable Macros to View BoQ information |