| 1 | Supply & Fix & connecting totally enclosed CMRI Certified in replacement of LED flameproof wellglass suitable for hazardous area Aluminum housing with heat resistant toughened glass cemented into a retaining ring fixed with screws to the main housing external reflector 50W including matching control gears and lamp complete all as specified. |
| 2 | Taking down of old unserviceable copper / aluminium point wiring (light) with conduit complete including fitting & fixture such as switches, ceiling roses, light fitting etc and making good disturbed surfaces of walls, floors etc complete all as specified. |
| 3 | All as per Ser item No 2 Above but without conduit |
| 4 | Taking down old unserviceable sub main wiring of any size complete all as specified. |
| 5 | M&L concealed point wiring complete with two runs of 2.5 sqmm, single core multi stranded copper conductor PVC insulated and unsheathed FRLS cable, 1100volts grade IS-694 marked drawn through and including rigid steel ERW conduit min 20mm dia ( stove enameled) heavy duty as per IS 9537 Part I and including all necessary flame proof , weather proof conduit accessories and fitting fixed to concealed in wall/ceiling with teflon tape sealed in all threaded joints in conduit and fittings for light points and including 2.5 sqmm single core multi stranded copper conductor PVC insulated and unsheathed FRLS cable 1100 volts grade earth continuity wire (connecting to earth dolly) & wiring shall be done as directed for the following :- |
| 6 | Two light points controlled by one Rotary switch/MCB |
| 7 | Three light points controlled by one Rotary switch/MCB |
| 8 | All as per Ser item No 5 Above but for Two light points controlled by one switch/MCB with copper cables 2.5 sqmm size. (in existing conduit) |
| 9 | All as per Ser item No 5 Above but for three light points controlled by one switch/MCB with copper cables 2.5 sqmm size. (in existing conduit) |
| 10 | Supply and fixing in replacement of factory made mild steel flame proof distribution boards, class LM-6 , protection class (IP-55) CMRI certified suitable for gas group IIA & IIB suitable for mounting MCB/RCCBs, DBs TP&N 4 way, 415 volts conforming to IS-2143 with minimum 200A rating copper bus bar Comprising of following :-(i) Lighting distribution panel(ii) Incoming: - MCB , 4P 63AMP - 01 Nos(iii) Outgoing :- MCB, 1P, 6 to 32 AMP -12Nos |
| 11 | Supply and fixing in replacement of switch flame proof rotary type with termination box in LM6, 16 Amps single pole, 250 volts epoxy painted complete all as specified.. |
| 12 | Supply and fixing in replacement of switch flame proof rotary type with termination box in LM6, 25 Amps double pole, 250 volts epoxy painted complete all as specified.. |
| 13 | Supply and fixing in replacement of LED flameproof tube light fitting CMRI certified 1x20W LED tube light fixture complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified |
| 14 | Supply and fixing in replacement of LED flameproof tube light fitting CMRI certified 2x20W LED tube light fixture complete with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified |
| 15 | Supply and fixing in replacement of MCB SPN 6 amp, 10KA rupturing capacity class-c (ISI marked IS -8828) fixing in DBs complete all as specified |
| 16 | Supply and fixing in replacement of MCB SPN 16 amp, 10KA rupturing capacity class-c (ISI marked IS -8828) fixing in DBs complete all as specified |
| 17 | Supply and fixing in replacement of MCB TPN 32 amp, 10KA rupturing capacity class-c (ISI marked IS -8828) fixing in DBs complete all as specified |
| 18 | Supply in repair MCCB 63 Amp, 4 Pole, fixed type breaking capacity 16 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified |
| 19 | Supply in repair MCCB 100 Amp, 4 Pole, fixed type breaking capacity 16 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified |
| 20 | Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes :- |
| 21 | 25 Sqmm 4 core |
| 22 | 16 Sqmm 4 core |
| 23 | 16 Sqmm 2 core |
| 24 | 10 Sqmm 2 core |
| 25 | Excavation in trenches in soft/loose soil not exceeding 1.50 Mtrs wide and not exc. 1.5 Mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified. |
| 26 | Demolition of Concrete in ground floors and pavings not exc 15cm thick( below or above ground floors) complete all as specified. |
| 27 | Returning, filling in including spreading leveling, watering and well ramming in layers not exc 25 cm thick after the cable have been laid and tested complete all as specified. |
| 28 | Removal of excavated surplus soil to a distance not exc. 50 Mtrs and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified. |
| 29 | M&L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm complete all as specified.. Note : Punned thickness shall be measured. |
| 30 | Supply and laying of sub class 'B' bricks in trenches over cables for protection cover across the length of cable complete all as specified. |
| 31 | M&L for driling hole in hard standing / road for laying of pipe for protection of cable etc by adopting method of horizontal manual drilling (trenchless technology) without disturbing the top surface or cutting and making good the disturbed surface to the existing surface. |
| 32 | Supply and laying in replacement of GI tube light grade 40 mm bore complete all as specified. |
| 33 | M&L sub main wiring with two runs of single core PVC insulated but unsheathed FRLS cable of 4 sqmm with multi stranded copper conductors, 1100 volts grade, IS-694 marked , drawn-through rigid steel ERW conduit (stove enameled) 20 mm dia heavy duty and including suitable size and fittings/accessories, concealed in wall and also including the one run of 4 sqmm earth continuity conductor of similar type cable complete all as specified and directed. Note :- Two runs of single core of 4 sqmm, one run of 4 sqmm earth continuity conductors and one run of 20mm dia ERW conduit with accessories shall be measured as one unit run length. Please Enable Macros to View BoQ information |
| 34 | M&L sub main wiring with two runs of single core PVC insulated but unsheathed FRLS cable of 4 sqmm with multi stranded copper conductors, 1100 volts grade, IS-694 marked , drawn-through rigid steel ERW conduit (stove enameled) 20 mm dia heavy duty and including suitable size and fittings/accessories, concealed in wall and also including the one run of 4 sqmm earth continuity conductor of similar type cable complete all as specified and directed. Note :- Two runs of single core of 4 sqmm, one run of 4 sqmm earth continuity conductors and one run of 20mm dia ERW conduit with accessories shall be measured as one unit run length. Please Enable Macros to View BoQ information |