| 1 | Supplying and drawing following sizes of PVC insulated copper conductor round multicore cable in the existing poles and bracket from cable termination connector to the fitting i/c providing suitable copper lugs connections etc. as reqd. |
| 2 | 3 x 2.5 sq.mm |
| 3 | Supply of XLPE insulated and PVC sheathed / XLPE armoured aluminium conductor power cable (As per IS 7098 (Part-1) of 1.1 KV grade i/c connection testing etc.as required. |
| 4 | 2 x 10 sq. mm |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required |
| 6 | Up to 35 Sq mm |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 8 | 63 mm dia (OD-63mm & ID-51 mm nominal) |
| 9 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 10 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required |
| 11 | 2 X 10sq. mm (19mm) |
| 12 | Supplying, replacement, Testing & Commissioning 200W of LED Flood Light, powder coated pressure die castaluminium body with built in or separate driver asper the requirement with Driverefficiency >85%,Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to52 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10%as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection,EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin) SDCM(Standard Deviation Color Matching) <5,Maximum power consumption should not morethan the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/cexternal connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) DSR.8.15.5 |
| 13 | Supplying, replacement, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F..0.95, IP-66,IK-10, CRI >70,under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000‹K / 4000‹K / 5700‹K /6500‹K (As perANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90‹C). |
| 14 | 72 watt |
| 15 | 120 watt |
| 16 | 45 watt |
| 17 | Supplying and replacement(including deduction of cost for replaced item) of PVC insulated copper wire FRLS of following size in the existing surface/ recessed conduit i/c connection, testing etc.as required. |
| 18 | 1.5 sq.mm |
| 19 | 2.5 sq.mm |
| 20 | 4.0 sq.mm |
| 21 | Supplying & replacement of following MCB's/MCCBs for Electrical Panel Board/ feeder pillar/ pole including testing etc as reqd. |
| 22 | 6 A, to 32 A, ratings, SP MCB, \\"C\\" curve, 10 KA breaking capacity |
| 23 | 6 A, to 32 A, ratings, SPN MCB, \\"C\\" curve, 10 KA breaking capacity |
| 24 | 6 A, to 32 A, ratings, DP MCB, \\"C\\" curve, 10 KA breaking capacity |
| 25 | 6 A, to 32 A, ratings, TP MCB, \\"C\\" curve, 10 KA breaking capacity |
| 26 | 6 A, to 32 A, ratings, TPN MCB, \\"C\\" curve, 10 KA breaking capacity |
| 27 | 40 A, 2 pole isolator |
| 28 | 63 A, 4 pole isolator |
| 29 | 100A,36 KA, FP MCCB |
| 30 | 125A,36 KA, FP MCCB |
| 31 | 200 A,36KA,FPMCCB |
| 32 | 250 A,36KA,FPMCCB |
| 33 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connection but excluding modular plate etc. as required. |
| 34 | 5/6 Amp Switch. |
| 35 | 15/16 Amp Switch. |
| 36 | 3 pin 5/6 Amp Socket outlet. |
| 37 | 6 pin 15/16 Amp socket outlet. |
| 38 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement withDriver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating andFixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required withMinimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape sizeand CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 39 | 18- 22 Watt |
| 40 | Supply and Replacement of MNX-80 Contactor as per requirement at site |
| 41 | Supplying, Installation, Testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 42 | 1 output per phase and suitable for single phase supply |
| 43 | 3 output ( 01 output per phase ) and suitable for three phase supply |
| 44 | Supply, replacement, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, remote, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. a)1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 45 | Supplying and Replacement of the existing worn-out Battery and P/F New 12 Volt 18 Ah capacity Sealed maintenance free battery with Nut bolt type battery terminals with complete battery charging including interconnection wire if required and testing etc. at site as required and taking away the dismantled battery as credit item on buy back basis etc. complete as required |
| 46 | Supplying, replacement, Testing & Commissioning of 18 W LED Recessed/ surface Down lighter (Round/ square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast Extruded aluminium Body including trim with Aluminium Reflector. |
| 47 | Supplying of LED Flood Light fixture not more than 500 watt and lumen output not less than 60000 Lumens (having minimum fixture efficacy of 120 Lm/Watt ) fitting with suitable clamp. The luminaire should be confirming to IP 66 & IK 08 (for impact resistance), External Surge protection of 15 KV/7.5 KA and Internal Surge protection of 5 KV/2.5 KA (integrated to the driver unit) CCT = 5700 ± 350° K, CRI ≥70, TLCI≥90, Life L70≥ 50K hrs. Fitting may be integrated type (with driver unit) or non integrated type (with separate driver unit). The LM 79, LM 80 & TTC Certificates shall have to be submitted form NABL/ UL/ third party lab to verify the above parameters) The complete item shall be as per specification and additional conditions attached, complete etc. as required. |
| 48 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) of following bodymaterials. Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector A) 30 watt |
| 49 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 50 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. Please Enable Macros to View BoQ information |