| 1 | S/F of 11 KV section dead and double pole structure (RISER) made of following types of supports duly grouted plinthed plastered, painted and numbered in the same manner as already specified for supports as per design incluidng channels, clamps, S.T. pole grouted with 1:4:8 cement concrete (1-cement , 4fine sand and 8-OBB of 40mm. nominal size) including plinthing with 20 mm. nominal size stone grit 10 Cm. Below the G.L. and 30Cm. Above the G.L. and plastering with 1:4 cement mortar painting and numbering of pole and making strip with enamel paint complete with all material and T&P etc. required for proper completion of work. S.T. GI BOTTOM Pole SP-55, 11.00 Mtrs. Long page no....... |
| 2 | Supply delivery, testing and commissioning of 11KV (E) XLPE cable having compacted circular stranded aluminium conductor, conductor screening of extruded semi conducting compound. Cross linked polythylance (XLPE) insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098/Part-II/ with latest ammendment for following mentioned sizes.It should be operational at 11KV, 50 Hz AC system. Complete in all respects. 300 sq mm 3 core H.T. Cablepage no....... |
| 3 | Drilling of road parallely and road crossing at depth 2/3 mtr as required and laying charges of cable and 160 mm dia HDPE pipe. complete with all material, labour, drilling machien and T&P etc. required for proper completion of work.page no....... |
| 4 | Supply of HDPE pipes (upto PN 6 Kg Pressure Rating material Grade PE 80, Pressure Rating PN 6.0, Nominal Dia (MM):160) as per relevants IS suitable for HT XLPE cable & as Required and as per relevant tecnnical specification. 160 mm dia HDPE Pipepage no....... |
| 5 | S/F of G.I. Pipe of following sizes for cable duly clamped with supports by 2 No. with clamps of 50 x 6 mm M.S. flats bolts, nuts and washer required for proper completion of work. (M.R.) 100mm dia page no....... |
| 6 | S/Making of suitable Earth of O/H line pole with 2.5 Mtr. Long 20 mm dia M.S. rod complete with 7/16 SWG G.S. wire in 2.00 Mtr. Long 15 mm dia G.I. Pipe (0.96 Kg/Mtr.) duly clamped on pole with 3 Nos. 20 x 3 mm M.S. flate clamp with bolts nuts and washers complete with all material labour and T&P etc. rerquired for proper completion of work. page no....... |
| 7 | Supply and jointing of In-door/Out-door type 11 KV Jointing Kit (HEAT SINK) for XLPE cable including cost of all material labour T&P etc. as per proper completion of work. (make:- Raychem/ Dension/ 3M). |
| 8 | Outdoor type DSR-2022, 10.5.4(i) 300 sq mm outdoor type Jointing Kit |
| 9 | Supply, Delivery Installation, Testing & Commissioning of 11 KV Straight through cable jointing kit of 3 core cable jointing Complete in all respects as required for proper completion of work.(make:- Raychem/ Dension/ 3M) As per DSR-2022, 10.6.4 |
| 10 | (i) 3CX240/300 sq.mm. |
| 11 | S/F of Danger board of size 200 x 250 x 1.6 mm of M.S. sheet fixed with clamp of 20 x 3 mm M.S. flate including bolts, nuts and washer duly painted completed with all material, labour and T&P etc. required for proper completion of work. page no....... |
| 12 | S/F of Barbed wire 1.5 Kg. Duly clamped with 2 No. clamps made of 20 x 3 mm at both end on poles, flate including bolts, required for nuts and washer complete with all material labour and T&P etc. for proper completion of work. page no....... |
| 13 | S/Fixing of cable rout marker made of 1:2:4 R.C.C. Block size 1000x400x100 mm grouted with 1:3:6 cement stone grit coresand 30 cm below G.L. With Painting, numbering & Marking etc. Complete with all Required material T&P etc. Complete in all respects as per direction of E./I. page no....... Please Enable Macros to View BoQ information |