| 1 | HSR Items |
| 2 | [24.5.2.4]MISCELLANEOUS ITEMS 2.4. S/E mark double walled corrugated (DWC) HDPE, pipe 10 kg/Cm2 ,laid 0.75 Metre below ground level including digging and refilling of earth including cost of suitable size socket/coupler for HDPE pipe including the cost of labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in charge of the work. DWC/HDPE pipe 90/75 mm outer dia/inner dia [Through Rate] |
| 3 | [33.7.1.1]Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire and running charges of all equipments, tools, plants and machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre and up to 150 metre depth below ground level. 1.1. All types of soil 300 mm dia [Through Rate] |
| 4 | [33.8.3]Supplying, assembling, lowering and fixing in vertical position in bore well, Unplasticised PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings and accessories etc. all complete, for all depths, as per direction of Engineer -in-charge. 3. 200 mm nominal size dia [Through Rate] |
| 5 | [20.11.2]Providing and fixing cast iron double flanged swing check type reflux (non return) valves PN-1.6 marked with IS:5312 including nuts and bolts marked with IS:1363, rubber sheet marked with IS:638 etc., carriage loading, unloading, stacking, handling, re-handling etc. Complete in all respect to the satisfaction of Engineer-incharge 2. 100 mm i/d [Through Rate] |
| 6 | [20.14.1]Providing and fixing cast iron double air valves of size given below marked with IS: 14845 including carriage, loading, unloading stacking, handling, re-handling etc., drilling, tapping, screwing in valves connections complete in all respects to the satisfaction of Engineer-in- charge. (Rate is same for 65mm/80mm/100 i/d pipes) 1. 65 mm i/d [Through Rate] |
| 7 | [20.114.2]Supplying erection, testing of fully automatic electric control panel board for T/Wells in Pump Chamber consisting of MS sheet of thickness 14 gauge duly painted box type floor mounted made ofangle Frame containing 1 no. fully automatic air brake starter suitable for Motor of the following capacity, Minswitch of suitable range with HRC fuse, 1 no. volt meter (0 to 500 volts), 1 No. Amp. Meter of 0 to 100 amp. 3 sets of indicating lamp capacitor of suitablecapacity and 1 no. single phase preventers with the timer switch including wiring in panel board and suitable electric energy meter wiring in Electric Control PanelBoard complete in all respect as per specification given in Schedule No. II, Including MCB, suitable, Capacitor,Wooden Box etc as per site requirement complete in all respect. 2. 15 HP Motor [Through rate] |
| 8 | [24.5.1.5]MISCELLANEOUS ITEMS 1.5. Supply and jointing three core submersible flat cables of approved make with bare bunched copper conductor insulated and sheathed with PVC for submersible pump motors /fountain lights etc with voltage grade 1100 volts marked with IS:694, 1990 including cost of jointing, materials as well as carriage, loading, unloading etc. complete in all respect up to the entire satisfaction of Engineer- in-Charge. Submersible Copper Cable 3 Core 10 sqmm [Through rate] |
| 9 | [20.124.5]Supplying, erection, testing and commissioning of submersible pumping sets as per BIS SPECIFICATION No. 8034-1989 (as amended upto date for pumps) and IS 9283-1979 (as amended upto date for motor) the pump motor sets should be capable of pumping clear fresh cold water having characteristics as specified in Clause4 of IS 8034-1989 and Clause 4.1 of IS 9283-1979. 5. LPM 600Head 70 BHP 15.56 Say Round BHP 15.00 [Through Rate] |
| 10 | [23.7.6.4]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.4. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 40 mm dia. [Through Rate] |
| 11 | [22.87.9]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 9. 100 mm nominal inner dia Pipes [Through Rate] Please Enable Macros to View BoQ information |