| 1 | Providing Mini Mast Light |
| 2 | OD333674/2025-2026: Supply, installation, testing and commissioning of LED flood light with minimum system lumen of 12000 lm with nominal efficiency not less than 120 Lm/watt, CCT of 5700K, CRI :70, ingress protection should be minimum IP 66 with minimum surge protection 4KV inbuilt in driver and 10KV external inside housing with range of operating voltage 120-270 V AC .The housing should be made of die-cast aluminium housing with powder coated, heat resistant toughened glass with THD <10%, power factor >0.95, RoHS compliant, duly wired up for use on 230 V AC supply with all accessories for fixing the luminaries . Chip make Cree/Osram/lumilled/Nichea/Bridgelux.(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer). |
| 3 | OD333675/2025-2026: Supply, installation, testing and commissioning of LED flood light with minimum system lumen of 14400 lm with nominal efficiency not less than 120 Lm/watt, CCT of 5700K, CRI :70, ingress protection should be minimum IP 66 with minimum surge protection 4KV inbuilt in driver and 10KV external inside housing with range of operating voltage 120-270 V AC .The housing should be made of die-cast aluminium housing with powder coated, heat resistant toughened glass with THD <10%, power factor >0.95, RoHS compliant, duly wired up for use on 230 V AC supply with all accessories for fixing the luminaries . Chip make Cree/Osram/lumilled/Nichea/Bridgelux.(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer). |
| 4 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 5 | 2.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole |
| 6 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 7 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 8 | OD330976/2025-2026:Supply and providing 24 Hours analog timer for automatic ON/OFF operation of light and giving connection etc |
| 9 | OD330977/2025-2026:Supply and providing 25A 2pole AC1 rated power contactor including giving connection etc as required. |
| 10 | 90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm |
| 11 | 1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm |
| 12 | 90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 13 | 90.12.1.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 6 sq mm |
| 14 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 15 | 9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 16 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 17 | OD330973/2025-2026:Supply and providing test joint for the earthing system using 2 NOs of the following sizes of strips including cutting and bending to shape ,drilling necessary holes and fixed to the watering pipe etc as required 2x25x3 mm tinned copper strip |
| 18 | 5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 19 | 5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 20 | 5.16:Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 21 | 90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 22 | OD330971/2025-2026:Supply and providing 25x6 mm brass bolt and nut with washer including drilling holes as required |
| 23 | 14.6:Excavation of the cable trenches in hard rock not exceeding 1.5 metres in width, and lift upto 1.5 metres, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 metres. |
| 24 | 14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. |
| 25 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels |
| 26 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 27 | 90.3.17.3:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.50 mm dia GI pipe |
| 28 | OD330974/2025-2026:Supply and fixing 32A backelite fuse base with HRC fuse link in the existing meter board andgiving connections etc |
| 29 | OD330969/2025-2026:Supply and fixing 32A, 415 V, 2 way neutral link mounted on DMC/ SMC base in the existingmeter board and giving connections etc Please Enable Macros to View BoQ information |