|
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Superintending Engineer, ESWC, Aligarh. Name of Work: New proposed 2x5 MVA, 33/11 KV Sub Station Kamalpur District- Aligarh along with associates 33 and 11 Kv line (Under Business Plan 2026-27) Turn Key E-Tender No: ESWCA-01/2026-27 |
| 2 | Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Work Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Rates Quoted Per Unit with GST & All Taxes Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT With GST & All Taxes TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 3 | Safe Carriage of following store items with loading & unloading at both ends respectively. (under jurisdiction of DVVNL) to praposed site |
| 4 | 33KV Line Isolator 800 Amp. |
| 5 | 33KV Bus Isolator 800 Amp. |
| 6 | 33 KV 1 Ph CT 400/200/1 Amp. |
| 7 | 33 KV 1 Ph CT 200/100/1 Amp. |
| 8 | 33KV 1 Ph PT 33KV/110 V |
| 9 | 33 KV VCB 800/750 MVA with Structure |
| 10 | 33 KV VCB 1250A with Structure |
| 11 | 33KV Post Insulator |
| 12 | 33KV Lightning Arrestor with surge counter |
| 13 | 90 lbs Rail Pieces for Transformer 44.64 Kg/M |
| 14 | 11KV 3x300 mm2 XLPE Al. Cable |
| 15 | 11KV 3x185 mm2 XLPE Al. Cable |
| 16 | 11KV 3x70 mm2 XLPE Al. Cable |
| 17 | LT Aluminium XLPE Insulated Armoured Cable of size 3.5x70 sqmm. |
| 18 | ACSR Dog Conductor |
| 19 | 11 KV Composite Polymer Pin Insulator with Nut and washers |
| 20 | 11 KV Polymeric Disc Insulator T&C type 45KN |
| 21 | 11 KV Polymeric Disc Fitting B&S type 45 KN |
| 22 | 33kV Control Panel for Double T/F Control with Differential Relay |
| 23 | 33kV Control Panel for Single Feeder with Differential Relay |
| 24 | 11KV Incoming CTR 600/300/5A, 350MVA |
| 25 | 11KV Outgoing CTR 200/100/5A 350 MVA |
| 26 | 11KV Bus Coupler 350 MVA |
| 27 | 8.5 Meter long PCC Pole |
| 28 | 11 Meter long PCC Pole |
| 29 | 9 Meter long PCC Pole |
| 30 | 13 Meter long STP (SP-72) |
| 31 | M.S. Wire 6 SWG |
| 32 | M.S. Wire 8 SWG |
| 33 | Earthing of Pole by MS Earthing Rod of 20x2500 mm. with 6 SWG earthing wire fitted with Nut, bolts & Washers etc. |
| 34 | V-Type Cross Arm 100x50x6 mm M.S. channel for 33KV line |
| 35 | ACSR Rabbit Conductor |
| 36 | 11/0.44 KV 63 KVA Transformer |
| 37 | 33 KV Composite Polymer Pin Insulator with Nut and washers |
| 38 | 33 KV Polymeric Disc Insulator B&S type 70KN |
| 39 | 33 KV Disc Fitting T&C type 70 KN |
| 40 | 11KV DO Fuse Set (3 Phase) |
| 41 | 11KV TPMO complete set (As per Specification) |
| 42 | V-Type Cross arm 65x65x6 mm, M.S. Angle for 11KV Line |
| 43 | 33KV 3x300 mm2 XLPE Al. Cable |
| 44 | 33 KV Fuse Set |
| 45 | Stay set complete (Stay rod 16x1800mm, Stay wire 7/10 SWG 5 Kg, Guy insulator, Stay clamp, bolt, nut & wasther with concrete grouting) for 11KV line. |
| 46 | Supply Providing at site of follwoing materials (Decentralized materials) by contractor including safely loading ,unloading & carriage with all Associatas accessories like all Type Clamps, Nut& Bolts etc. |
| 47 | 24 Volt Battery and Battery Charger cum Inverter with cabinet complete set |
| 48 | Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x300 Sq.mm. cable |
| 49 | Heat Shrinkable indoor type end termination cable jointing kit suitable for 11KV XLPE 3x300 Sq.mm. cable |
| 50 | Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x185 Sq.mm. cable |
| 51 | Heat Shrinkable indoor type end termination cable jointing kit suitable for 11KV XLPE 3x185 Sq.mm. cable |
| 52 | Heat Shrinkable outdoor type end termination cable jointing kit suitable for 11KV XLPE 3x70 Sq.mm. cable |
| 53 | Heat Shrinkable indoor type end termination cable jointing kit suitable for 11KV XLPE 3x70 Sq.mm. cable |
| 54 | Heat Shrinkable outdoor type end termination cable jointing kit suitable for 33KV XLPE 3x300 Sq. mm.cable |
| 55 | LT Distribution Pannel with Meetring Equipment & fixing Arregment |
| 56 | Stay set complete (Stay rod 20x1800mm, Stay wire 7/8SWG 10Kg, Guy insulator, Stay clamp, bolt, nut & wasther with concrete grouting) for 33KV line. |
| 57 | Holding Clamp for Top Channel, M.S. Channel with nuts, bolts, washers for 11KV line. |
| 58 | Holding Clamp for Top Channel, M.S. Channel with nuts, bolts, washers for 33KV line. |
| 59 | M.S. Cross arm holding Clamp with nuts, bolts, washers for 11KV line. |
| 60 | 11KV `F' Bracket of 65x8mm size with Nut, Bolt & washers |
| 61 | M.S.Cross arm holding Clamp of with nuts, bolts,washers for 33KV line for PCC/STP |
| 62 | HDPE Pipe PE-80,PN-6, DN-200mm for Cable laying (Pipe to be laid by HDD Method) (For Road Crossing/ Power Transmmsion) |
| 63 | Outdoor Switchyard Earthing with 32mm size Earth Mat with Delta earthing on Power Transformer Body & 33KV LA as per resspo Specification |
| 64 | Terminal Gantry Structure as per resspo Specification |
| 65 | 33 KV Main bus bar complete with structure with Penthar Conductor with all P.G.clamp & connectors as per resspo Specification |
| 66 | Structure for 33 KV Isolator with Plinth & Foundation |
| 67 | M.S. Bolt, Nuts & Washar |
| 68 | Structure for 33 KV Fuse set with Plinth & Foundation |
| 69 | Structure for 33 KV Lightning Arrester with Plinth & Foundation |
| 70 | Structure 33 KV CT & PT with Plinth & Foundation with Junction Box |
| 71 | 33 KV VCB Plinth & Foundation |
| 72 | Structure for 33 KV Post Insulator with Plinth & Foundation |
| 73 | Power Transformer Nutral M.S. L-Type Stand of size 100x50x6mm channel as per specification |
| 74 | 4x2.5 mm Sq. Armoured Copper Control Cable with laying and connection with VCB/CT/PT/Power T/f etc. |
| 75 | 2x2.5 mm Sq. Armoured Copper Control Cable with laying and connection with VCB/CT/PT/Power T/f etc. |
| 76 | Indoor Earthing for 33/11KV Sub-station |
| 77 | T & P of Sub-Station Switchgears as per Specification. |
| 78 | Furniture of Substation as per Specification. (6–Chairs, 2–Table, 1–Bench, 1–Rack, 1–Stool) |
| 79 | 1.0 X 2.0 mtr. Size Rubber mat 20 mm. thick |
| 80 | 4.5 Kg. CO2 Fire Extinguisher, portable type (As per specification) |
| 81 | 5 Kg. Dry chemical powder fire extinguisher, portable type (As per specification) |
| 82 | 06 Nos. Fire Buckets with stand, filled with dry sand |
| 83 | Outdoor Switchyard Lighting complete in all respect 06 Nos. Lighting with Pole and related Matarial |
| 84 | 33/11KV S/S Name board with stand |
| 85 | 33KV Danger board with clamp of 25x3mm size with Nut & Bolts |
| 86 | 33KV Number plate with clamp 25x3mm size with Nut & Bolts |
| 87 | P.G. Clamp for ACSR Dog to Dog Conductor |
| 88 | Stone Pad (300x300x75mm) |
| 89 | Aluminium Binding Wire - 6 SWG |
| 90 | G.I. Barbed Wire |
| 91 | M.S. Top Channel 125x65x6mm, 3200 mm long (13.10kg/mt) with with Clamps of 75×10 MM Size, bolts, nuts and washers for 33KV line double pole/Four Pole |
| 92 | M.S. Angle Iron 65x65x6mm, (5.80kg/mt) 4300 mm long bracing with 4 Nos. with clamps of 65x6mm, bolts, nuts and washers for 33KV line |
| 93 | M.S. Guarding angle 65x65x6 mm, (5.80kg/mt) 2200 mm long with with holding clamp 65x8mm, packing piece, nut & bolts etc. for 33KV line |
| 94 | 33KV 'E' Bracket with Nut, Bolt & washers |
| 95 | 33KV 'F' Bracket with Nut, Bolt & washers |
| 96 | 11KV Danger Board with clamp 25x3mm size with Nut & Bolts |
| 97 | 11KV Number Plate with clamp 25x3mm size with Nut & Bolts |
| 98 | P.G. Clamp for ACSR Rabbit to Rabbit Conductor |
| 99 | G.I. Pipe 6\\" dia . |
| 100 | M.S.Holding Clamp of 65x8mm size With Nuts, Bolts & Washers for G.I.Pipe 4\\", 6\\", 33KV & 11KV Cable/ Line |
| 101 | Eye Bolt |
| 102 | M.S.Top Channel 100x50x6x2240 mm long (9.56kg/mt) with 2 Nos. with Clamp of 65x8mm for 11KV line double pole |
| 103 | M.S. Channel 100x50x6x2028mm (9.56kg/mt) with 2 Nos. with Clamp of 65x8mm for Dropper for fuse set & double pole for 33 KV Line/11KV Line |
| 104 | M.S.T-off Channel 100x50x6 mm 1300 mm long (9.56kg/mt) with Clamp of 65x8mm for 11KV line |
| 105 | M.S. Angle Iron 65x65x6 mm, (5.80kg/mt) 2700 mm long bracing complete with 4 Nos. with clamps of 65x6mm, Nut, bolt and washers for 11KV line |
| 106 | M.S. Guarding angle 65x65x6 mm, (5.80kg/mt) 1600 mm long with holding clamp 65x8mm, packing piece, nut & bolts etc. for 11KV line |
| 107 | M.S. Holding Clamps 65x8mm size for TPMO & Fuse Set etc. with nuts, bolts & washers |
| 108 | 11KV 'E' Bracket of 65x8mm size with Nut, Bolt & washers |
| 109 | Red Oxide Paint |
| 110 | Aluminium Paint |
| 111 | M.S. Cable support Structure of size 65x65x6mm angle as per specification |
| 112 | Stay Insulator |
| 113 | Cable Route Marker |
| 114 | Earth wire Clamp |
| 115 | T-off Clamp |
| 116 | Top & Dropper Clamps with Nut & Bolt |
| 117 | Outdoor Equipment (Earth Mat) |
| 118 | Silica Gel Breather with pot For 5 MVA Power Transformer |
| 119 | OTI For 5 MVA Power Transformer |
| 120 | WTI For 5 MVA Power Transformer |
| 121 | HV Side Brass connectors with Nut & Bolts |
| 122 | LV Side Brass connectors with Nut & Bolts |
| 123 | Erection/Fixing of following Material & Miscellaneous Electrical Works. Including Centralized & Decentralized All Materials (As Per resspo Norms) :- |
| 124 | Plinth & Foundation of 33 KV PT (1 No), 33KV CT (3 No), 33 KV Bus Type Isolator (2 No), Post Insulator (4 No), 33 KV Lightening Arrestors (3 No), 33 KV Fuse Set (2 No), 33 KV Line Isolator (1 No) as per Resspo Noms. |
| 125 | Plinth for 5 MVA Transformer Qty 02 Nos. |
| 126 | Construction of plinth for 5 MVA, 33/11 KV Transformer of (3.46x4.46x1.0)m (0.50m below ground level and 0.5 m above ground level) as per details & drawing attached (All required matrials provided/Supply by the contractor own his cost):-Excavation of earth in foundation. |
| 127 | Cement concrete in foundation in ratio 1:6:12, Cement, Sand & Brick ballast. |
| 128 | First Class Brick work in ratio 1:4 with Cement & Coarse sand mortar. |
| 129 | Cement concreting inner side of plinth in ratio 1:4:8, Cement, Coarse sand and stone shingle. |
| 130 | M.S.work for re-inforcement 12mm. Tor at a distance of 15Cms. apart, including cutting, bending & binding by wire to each other for making JAL in two layer, 12 to 15Cms. apart. M.S.12mm Tor bar provided by the contractor his own cost. |
| 131 | Fixing of 3.46 Mtr.long, 2No. Rail Pices, 90Lbs, on top of Plinth at proper distance in alignment by C.C. |
| 132 | Cement concrete in ratio 1:2:4, Cement, Coarse sand & Stone shingle, on top of the plinth, including fixing of M.S.Tor Jal. |
| 133 | 12mm.thick Cement Plaster in ratio 1:4, Cement & Sand mortar, on all side of plinth. |
| 134 | Neat cement coating 3mm.thick on top surface of plinth. |
| 135 | Plinth for 33 KV V.C.B. |
| 136 | Construction of plinth for the structure of 33 KV VCB & C.T.’s as per details for . (All required materials provided / Supply by the contractor own his cost) :-Excavation of earth of size 2x(2.0x2.0x1.0)m pits for construction of plinth. |
| 137 | Brick Ballast ratio (1:4:8) (cement, sand & brick ballast) for foundation work 2x(2.0x2.0x0.5)m plinth. |
| 138 | R.C.C. work in ratio 1:2:4 (cement, coarse sand & stone grit) of 20m size for making plinth of size 2x(2.0x2.0x1.0)m and grouting of foundation bolts 04 Nos. for 33 KV VCB. |
| 139 | 12mm thick plaster with cement mortar in ratio 1:4 (cement & fine sand) of plinth of 0.4m upper side |
| 140 | INSTALLATION OF SWITCH GEARS IN CONTROL ROOM:- Errection and instalation of 11 K.V. V.C.B's (Incoming, Outgoing & Bus Couplar in aligment and connecting interconnecting bus bars and 11 K.V. cables. |
| 141 | Earthing of indoor equipment, details as given below:- |
| 142 | Cutting of 32mm.dia M.S. Bar-3Mtr.long and making one end in conical shape by forging process and driving it into the earth at each corner of bridge outside control room and proper welding with M.S.Bars. |
| 143 | Digging of Pits for making Bridge on both side of control room by laying 32mm. dia M.S.Round in rectangular shape. Electric welding on cross joints by providing “U” Clamp in size 25x6mm. of M.S.Flat and inter connecting both by M.S.Round 32mm.dia through control room trench, with over lap joint by providing M.S.Round-12mm dia, on both sides of over lap joints of M.S.Round, by electric welding. All joints shall be painted with black bituminious paint. |
| 144 | Water level earthing by Boring and lowering of G.I. pipe size 40 mm dia & thickness 3mm into the ground at 30 Mtr depth or upto the water level with the lower end of solid copper cone Approx 225 mm long and 750 gm in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG from the cone up to the ground surface where it will be bolted to the M.S. earth Strip for Transformer neutral connection, the M.S.Earth strip size 50x6mm will be welded to the G.I. pipe and neutral earthing support & other installed equipment in switchyard. All required material provided / supply by the contractor own his cost. |
| 145 | Outdoor Switchyard Earthing with 32mm size Earth Mat with Delta earthing on Power Transformer 02 Nos. Body Earth, 33KV LA , 33 KV CT, 33 KV PT, 33KV Fuse Set, 33KV Bus Isolater, 33KV VCB & 33KV PI Including connecting MS Strip of size 50x6 mm at both site (As per Resspo Specification) |
| 146 | Installation of 5 MVA Transformer and other accessories equipments. |
| 147 | Fabrication and erection of neutral earthing L Type support made of M.S. Channel size 100x50mm. Structure shall be 4 Mtr. Long with 1 Mtr. Arms. Structure shall be grouted in ratio 1:3:6 in block size 300x300x700mm and painted of welding joint with one coat of Ready Mixed primer and Two coat of enamel Aluminium paint work includes connecting neutral bushing rod of power Transformer and M.S. Earthing strip with the help of flexible copper bond, M.S. Bolt and washer. |
| 148 | Fabrication and erection of cable support made of two pieces of M.S. Angle (65x65x6)mm, 2.75 meter long, joined to each other by means of 5 Nos. M.S. Flat (50x6) mm pieces of size 750 mm long each by welding at equal intervals and grouting in a block of size (300x300x700)mm in C.C. 1:3:6 (cement, coarse sand and stone ballast) complete and painted of welding joint with one coat of Ready Mixed primer and Two coat of enamel Aluminium paint. Work includes providing of three Nos. M.S. clamps made of (50x6)mm M.S. Flat for holding the cable including nuts and bolts. |
| 149 | Fixing of properly Control Cable connections for OTI, WTI, PRV,33 KV Breaker, 33KV CT, 33KV PT, Single/Double Control & Relay pannel Buck holz relay. |
| 150 | Fabrication and grouting of M.S. frames 3 mtr. long for support of copper Bus Bar. Bus Bar will be provided in L.V. side of Power transformer. The M.S. frame shall be made of M.S. channel (100x50)mm in ‘T’ shape. Providing 2 Nos. support of M.S. Angle iron (50x50x6)mm, 0.60mt. long below the top channel, drilling of 3 Nos. hole on the top channel for fixing of post insulator and painted of welding joint with one coat of Ready Mixed primer and Two coat of enamel Aluminium paint and grouting the frame in C.C. ratio 1:3:6 (cement, coarse sand and stone ballast) in a block of size (300x300x700) mm. The work also includes the fixing of 3 Nos. Post Insulator and Screwing the copper Bus Bar with the Post Insulator. |
| 151 | Providing & Fabrication of copper bus bar of size (2500x50x6)mm in L.V. side of 5 MVA 33/11 KV, power transformer, Work includes connection of outside bus bar in L.V. side busing rod of Power Transformer and other side with outdoor 11 KV cable box as well as providing empire tape and H.T. tape etc. for proper insulation work. (Supply/Providing by Contractor) |
| 152 | H.T. Power Cable Laying (11 KV 3X300sqmm): Laying 11 KV, (3x300) mm2 XLPE, Cable from power transformer to 11 KV incoming switch gear in the cable trench 0.45 m wide, 0.90m depth. Providing 150 mm local sand for cushion beneath and 150 mm above the cable (quality of local sand required 0.375 cum/m in length). The cable shall be dully protected by brick. On both side of cable by laying brick vertically and bricks would also be laid bricks along the single cable (minimum 18 Nos. of bricks are to be laid top and outer side along the single cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal’s, back filling of earth and testing and commissioning of power cable etc. Spare cable shall be left over and laid in the trenches in shape of 6 m ring at both ends. |
| 153 | Cable Laying (11 KV 3X185sqmm): Laying 11 KV, 3x185mm2 XLPE, Power cable from outgoing switch gear to 11 KV double poles in the cable trench 0.50m wide, 0.90m depth. Providing 150 thickness mm local sand for cushion beneath and 150mm above the cable (quantity of local sand required 0.375 cubm/m in length). The cable shall be duly protected by brick. On both side of cable by laying bricks vertically and bricks would also be laid horizontally on top of vertically laid bricks along the single cable (minimum 18 Nos. of bricks are to be laid top and outer side along the single cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal’s, back filling of earth and testing and commissioning of power cables etc. Spare cable shall be left over and laid in the trenches in shape of 6m rings at both ends. At the end of feeder cables, where the cable is to be laid across pucca/main road, 100 mm dia G.I. pipe will be weared over the cable in the cable trench for the protection of cable. |
| 154 | Cable Laying (11 KV 3X70sqmm): Laying 11 KV, 3x70mm2 XLPE, Power cable from outgoing switch gear to 11 KV double poles in the cable trench 0.50m wide, 0.90m depth. Providing 150 thickness mm local sand for cushion beneath and 150mm above the cable (quantity of local sand required 0.375 cubm/m in length). The cable shall be duly protected by brick. On both side of cable by laying bricks vertically and bricks would also be laid horizontally on top of vertically laid bricks along the single cable (minimum 18 Nos. of bricks are to be laid top and outer side along the single cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal’s, back filling of earth and testing and commissioning of power cables etc. Spare cable shall be left over and laid in the trenches in shape of 6m rings at both ends. At the end of feeder cables, where the cable is to be laid across pucca/main road, 100 mm dia G.I. pipe will be weared over the cable in the cable trench for the protection of cable. |
| 155 | Preparation of 11 KV Power Cable Jointing Kits: Making of 11 KV XLPE Heat shrinkable outdoor jointing kits 3x300Sq.mm/3x185Sq.mm/3x70Sq.mm after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs |
| 156 | Installation of 24V Battery and Battery Charger: Assembling and installation of the cabinet of 24V battery and battery charger in switch gear control room including grouting of foundation bolts as per drawing of manufacture, including providing the foundation nuts and bolts of proper size. The electrical connection between battery and battery charge with flexible copper lead of size 7/20 SWG shall be done properly. The work includes installation, wiring upto control panel, testing and commissioning complete in all respect. |
| 157 | Laying of Control Cables (2x2.5)mm2/ (4x2.5)mm : Laying of different size of (2x2.5)mm2/ (4x2.5)mm2 control cables i.e. from Buchholz realy to Marshalling box Marshalling box to indication protection board in switch gear room, 33 KV CT’s to CT’s Junction Box, 33 KV CT, 33 KV PT, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box and indication board as per required for installed equipment. |
| 158 | Erection of 11 KV Feeder Double Pole: Erection and grouting of 2 Nos. STP SP-55-11Mtr/PCC 8.5/11 Mtr. long for making DP Structure including fabrication fixing of M.S. Channel, M.S.Angle, TPMO, Fuse Set, disc, insulators, pin insulators No. Plate, Danger board, barbed Wire (02 Kg per Pole) etc. the work includes supply and fixing of necessary clamps size 75x10mm with M.S.Nuts bolt & washer, bolts and washers. The work also includes grouting of Double pole support in C.C. 1:3:6 (cement, Core sand & stone ballast) in block of size (0.45m x 0.45 x 1/6 length of the pole) including earthing of Double pole with M.S. earthing rod complete in all respect. |
| 159 | Providing & wearing of 6 inch dia, 6.0 mtr long G.I. pipe in the feeder cable & 11 KV Cable of size of (3x300, 3x185)mm2 XLPE 33KV/11KV power cable before making the outdoor cable boxes. The work includes the sealing of G.I. Pipe, top end and lower end of the pipe is to be buried in to the ground about ½ m and proper dressing of cable etc. The work includes lifting, mounting and clamping of 11 KV feeder cable boxes on the feeder with double pole structure and making connections including supply of cable mounting clamps etc. |
| 160 | Providing & fixing of Danger board & Number Plate for 11 KV Double & 11 KV Line at each location as per specification of the drawing. Size 200mmx250mm & 3mm thickness with M.S.Clamp & nut & bolt |
| 161 | Providing & fixing of Danger board & Number Plate for 33 KV Double & 33 KV Line at each location as per specification of the drawing. Size 200mmx250mm & 3mm thickness with M.S.Clamp & nut & bolt |
| 162 | Grouting of stay rods (16x1800)mm/(20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc. |
| 163 | Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 33 KV/11KV and Stay Clamps. |
| 164 | Painting of Structures : Painting of the all structures with one coat of ready mixed primer and two coats of ISI Mark Aluminium paint after rubbing with sand paper to the surface of the structure including labour and T&P complete in all respect. |
| 165 | Installation of 33 KV Isolators: Assembling and installation of Bus Isolator/ Line Isolator on the isolator structure. Adjusting of operating mechanism in proper alignment so as to ensure smooth operation of the same. In case of Line Isolator proper operation of earth links shall also be ensured. The work includes complete with earthing and line connections & fabrication for proper fixing if required. |
| 166 | Installation of 33 KV Lightning Arrestors: Assembling and installation/mounting of 3 Nos. lighting arrestors on the L.A.’s structure/terminal gentry, complete with earthing and line connections. The work includes fabrication for proper fixing, if required. |
| 167 | Installation of 33 KV Post Insulators: Installation of 6 Nos. PI on structure. The work includes complete with earthing and line connections & fabrication for proper fixing, if required. |
| 168 | Installation of 33 KV Fuse Set: Assembling and installation of fuse set on the fuse set structure. The work includes complete with earthing and line connections & fabrication for proper fixing, if required. |
| 169 | Installation of 33 KV VCB : Assembling and installation of 33 KV VCB on the VCB out door structure on the plinth. Adjustment of operating mechanism in proper alignment for smooth operation of the same. The work also includes complete with earthing and line connections & fabrication of addition arrangement for proper fixing, if required. |
| 170 | Installation of 33 KV VCB Control Panel for single T/F & Double T/F Control Panel. Carefully and safely shifting of 33 KV VCB control panel from outside of the switch gear room to inside of the switch gear room, grouting with anchor bolts in the floor, work also includes cutting & proper finishing of floor if necessary for completion of work. Placing and fixing of panel on foundation, bolts of proper size in proper position and alignment. |
| 171 | Installation of 33 KV C.T.’s: Installation of 3 Nos. C.T.’s on the C.T’s structure. The work includes complete with earthing and line connections & fabrication for proper fixing, if required to complete the work. |
| 172 | 33 KV CT’s Junction Box: Providing & fixing of junction box of size (400x400x150) mm made of M.S. sheet of 16 SWG in between 33 KV CT’s & control panel. The work also include making proper connection on the junction box and making all connection in between CT’s and control panel complete as per manufacture’s panel drawing including testing and commissioning of work etc. complete the work. |
| 173 | 33 KV Bus Bar Jumpering: Jumpering, including clamping/binding with ACSR Dog conductor/33KV 3x300mm2 XLPE cable with providing P.G.Clamp & Connector HV side of T/F and other accessories with complet Job. |
| 174 | Installation of Terminal Gantry Structure as per resspo Specification |
| 175 | Installation of 33 KV Main bus bar complete with structure with ACSR Penthar Conductor with all P.G.clamp & connectors as per resspo Specification |
| 176 | Laying of HDPE Pipe Underground minimum 3 Mtr. Below by HDD Method along with laying of 33 KV 3x300 sqmm. XLPE cable in HDPE pipe (200 mm DIA) (pipe to be laid by HDD method) (Double Circuit) |
| 177 | Laying,saging & Stringing of ACSR Dog conductor with fitting all accessories including Sundry items |
| 178 | Single support PCC Pole 09 Mtr Long Excvation Fabrication,Erection,Fixing all clamps and other acccessories such as No plate danger board barbed wire etc with earthing of supports (33 kv Lines) |
| 179 | Single support ST Pole/PCC 11 Mtr Long Excvation Fabrication,Erection,Fixing all clamps and other acccessories such as No plate danger board barbed wire ,painting etc with earting of supports (33 kv Lines) |
| 180 | single support ST Pole 13 Mtr Long SP-72 Excvation Fabrication,Erection,Fixing all clamps and other acccessories such as No plate danger board barbed wire ,painting etc with earting of supports (33 kv Lines) |
| 181 | laying & mounting D/P ,termination and connections of 33 KV 3 Core XLPE Cable Al. 3x300 Sq.mm |
| 182 | Fixing ,prepare and Making 33 KV outddoor of 3x300 Sq. mm XLPE Cable Jointing Kit |
| 183 | Double Pole structure 11 Mtr Long SP-55/11Mtr. PCC/PCC 9 Mtr. Pole Excvation Fabrication,Erection,Fixing all clamps and other accessories such as Top Channel, Dropper Channet, Cross Bracing & No plate danger board barbed wire ,painting etc with earting of supports for 33KV line. |
| 184 | Tri Pole structure 11 Mtr Long SP-55/PCC 9 Mtr./11 Mtr. PCC Pole Excvation Fabrication,Erection,Fixing all clamps and other accessories such as Top Channel, Dropper Channet, Cross Bracing & No plate danger board barbed wire ,painting etc with earting of supports for 33KV line. |
| 185 | Four Pole structure 11 Mtr Long /11 Mtr. PCC/PCC 9 Mtr. Pole Excvation Fabrication,Erection,Fixing all clamps and other accessories such as Top Channel, Dropper Channet, Cross Bracing & No plate danger board barbed wire ,painting etc with earting of supports for 33KV line. |
| 186 | Hosting of 33kv 3x300sqmm XLPE cable on double pole/Tri Pole including G.I. Pipe 6 inch dia M long including its jumpring complet with Sundry Items for 33KV line. |
| 187 | Grouting of 13 Mtr. S.T.P. Pole & 11/9 Mtr. PCC/8.5 Mtr. PCC per pole with concreted with1:4:8 cement concrete mmixture.(make foundation 450x450mm plinth will be 300mm above the ground level)as per drawing resspo. Norms |
| 188 | Chooping of branches of Tree along the route of the line and disposal of the same. (33 kv/11 KV Line) |
| 189 | Cable Route Marker |
| 190 | Painting of STP Poles : Painting of the all STP 11/13 Mtr. Long in 33 KV/11 KV line V-type Coross arm clamps with one coat of ready mixed primer and two coats of ISI Mark Aluminium paint after rubbing with sand paper to the surface of the structure including labour and T&P complete in all respect. |
| 191 | Laying,saging & Stringing of ACSR Rabbit conductor with fitting all accessories including Sundry items |
| 192 | Single support PCC Pole 8.5 Mtr Long Excvation Fabrication,Erection,Fixing all clamps and other acccessories such as No plate danger board barbed wire etc with earthing of supports |
| 193 | Double Pole structure PCC 9 Mtr/8.5 Mtr. Pole Excvation Fabrication,Erection,Fixing all clamps and other accessories such as Top Channel, Dropper Channet, Cross Bracing & No plate danger board barbed wire ,painting etc with earting of supports |
| 194 | Earthing of 8.5 Mtr. long PCC/11 Mtr. STP poles complete as per construction manual and drawings with G.I. Wire fitted M.S. Nut Bolt & Washer. |
| 195 | Fixing of Tee channel as per relevant drawing. |
| 196 | Guarding between two poles/double poles etc. to guard LT/11 KV/Road and line crossing etc. with M.S. wire including fixing of guarding channel with clamps etc. |
| 197 | Providing and fixing of Silica Gel Breather with pot For 5 MVA Power Transformer, OTI , WTI, HV Side Brass connectors with Nut & Bolts, LV Side Brass connectors with Nut & Bolts & Etc. |
| 198 | Painting of 05 MVA Power T/F with one coat of red oxide primer and two coat of grey colour enable paints with proper rubbing and cleaning of Power T/F all required materials will be provided by firms |
| 199 | Oil leackage work like top cover plate, radiator, H.V. bushing & L.V. bushing any leackage of Power T/F work will be done by contrator all required materials will be provided by firms |
| 200 | Applying of All type NOCs like documentation/NOCs from NHAI/Electricity Safety/Forest/Irrigation etc. with the depositing of Processing Fees upto approval and energistion work of the line after all required approvels. Total in Figures 0.0 23 Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |