| 1 | ERECTION WORKS |
| 2 | Erection of following as per instruction manual of various equipment and technical specifications including shifting of material/equipment from store to erection site including all other associated work to complete the job satisfactory as per direction of supervising engineer. |
| 3 | 33 KV VCB with structure |
| 4 | 33 KV Line isolator with 1 Earth Switch |
| 5 | 33 KV Bus Isolators |
| 6 | 33 KV CT |
| 7 | Junction Box of CT |
| 8 | 33kv Porcelain type Surge Arrestor. |
| 9 | Erection of 33 KV Tripple feeder control & Relay panel including shifting from store to control room and proper grouting and earthing. |
| 10 | Erection of Enegymeter(ABT) 0.2S Class |
| 11 | Erection of Sublighting Outdoor Panel |
| 12 | Erection of main and auxiliary structure consisting of columns, beams, peaks, masts etc. and auxiliary structure required for installation of isolators, CT's, PT's, CVT's, LA's and all other equipments. The job consists of shifting of all material i.e. structure parts, nuts, bolts washers etc from store to site of erection. Erection of structure as per relevant drawing and practices using flat and spring washer with each bolt. Matching of holes, cutting matching of members if required shall also be done by the contractor without any extra cost of complete the work satisfactory. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactory completion of work shall be arranged by the contractor at his own cost including all other associated work to complete the job satisfactorily as per direction of supervising engineer (app. 3MT) |
| 13 | ABL Structure |
| 14 | ALP Structure |
| 15 | EKR Structure |
| 16 | BBR Stucture |
| 17 | APR Structure |
| 18 | Interconnection work between 33 KV main bus to bus isolator and bus isolator to 33 KV VCB and 33 KV VCB to 33 KV CT to PT and 33 KV CT to line isolator and 33 KV line isolator to 33 Kv transfer bus isolator 33 KV Transfer bus isolator to 33 KV Transfer bus, with single/double by panther conductor including cutting laying, fixing and proper tightening with the help of skilled labour & T&P including all other associated work to complete the job satisfactorily as per direction of supervising engineer. |
| 19 | Laying of flowing sizes of control cable in the cable trench from various equipment to control and relay pane, marshalling boxes ec. From switchyard as per cable schedule, its saddling at every 750mm distance with M.S. saddles of size 25x3mm. Size including carriage of cable drums from store to laying site and shifting back to store and all other associated work to complete the job satisfactorily as per direction of supervising engineer. |
| 20 | 6x2.5 Sq.mm |
| 21 | 4x2.5 Sq.mm |
| 22 | 2x2.5 Sq.mm |
| 23 | Termination of following size of cable as laid above as per cable schedule including making necessary holes in glands plates or box wherever required, supply and fixing of cable flands of appropriate size, supply and providing ferrules and Nos. for each core. (The rate of temination of control cables include the all cores of cable at one end with lug) including all other associated work to complete the job satisfactorily as per direction of supervising engineer. |
| 24 | 6x2.5Sq.mm (each end) |
| 25 | 4x2.5 Sq.mm (each end) |
| 26 | 2x2.5Sq.mm (each end) |
| 27 | Cutting Straightening, Bending, Laying 600 mm below in side ground and above ground of with 75x10 mm size) of M.S. flat and for earthing of main structure, Auxiliary strucutre, C.T., C.B., B.I., L.I., with by 50x6 and 25x6MS Flat MS Round 40mm with newly laid earth mat 'x' & 'y' aixs below 600mm ground and above by excavation of trenches its back filling, straightening, cutting, bending work also includes painting of M.S. earth strip above ground level with one coat of red oxide and two coat of bus green enameled paint, and below ground each earth point raising from main earthmat 'x' & 'y' axis should be painted with bitumen black japan paint and all other associated work as required to complete the work satisfactorily as per direction of supervising engineer (excluding the cost of M.S. flat). |
| 28 | Preparation of Inter connection diagram and cable schedule as per drawing to complete above job for C&R and circuit breaker. |
| 29 | TRANSPORTATATION WORK |
| 30 | Safe carriage of any other material required for bay construction from any substation store under E400 KV S/S Div. Aligarh & 132 KV Substation Akrabad. |
| 31 | Sorting/Counting/Stacking, erection mark wise and proper loading of GI substation structure (ALP/ABL/EKR/BBR etc.) in trucks/trailor at EFU Naini Allahabad and safe carriage of loaded structure from EFU Naini Allahabad to 132 KV Substation Gangiri and unloading of carriage structure from the truck/trailor at 132 KV Substation Akrabad under E.400KV S/S Div. Aligrah Its sorting, counting and proper stacking at the substation premises as per direction of supervisory engineer to complete the job satisfactorily (approx 4 MT) |
| 32 | SUPPLY |
| 33 | Supply of M.S. Electrode 3Mtr x 40mm Dia |
| 34 | Supply of P.G. clamp made of LM-6 alloy along with Galv. Nut, Bolt & Washer suitable for Panther to Panther conductor. |
| 35 | Supply of P.G. Clamp made of LM-6 alloy along with Galv. Nut, Bolt & Washer suitable for Moose to Panther conductor. |
| 36 | Supply of 4.5kg Manual CO2 Fire Extinguisher |
| 37 | Supply of 4.5kg Manual Dry Chemical Type Fire Extinguisher |
| 38 | 50 litres Mechanical Foam Type Portable / Trolley / Wheel mounted Fire Extinguisher. |
| 39 | Supply of Sand Bucket as per tech. Specification |
| 40 | Supply of Sand bucket stand suitable for 10 Nos. Bucket as per technical Specification. |
| 41 | Supply of GI Perforated Cable Tray size 75mm wide |
| 42 | Supply of tinned copper bond size 15x550mm long made of 12 mm multi stranded rope type 450mm long should be joined together and cramped with copper lug (20 mm hole) on both ends as per sample. |
| 43 | Supply of 75x10 Sq.mm MS Flat |
| 44 | Supply of 50x6 Sq.mm MS Flat |
| 45 | Supply of Sublighting Outdoor Panel |
| 46 | Supply of LED Flood Light Luminaries type FL1 [150W]CGL make Please Enable Macros to View BoQ information |